Reference Guide
Thank you for choosing Leviton Network Solutions. Our copper, fiber, power, and
Connected Home solutions are ideal for today's most demanding applications,
consistently exceeding our customers expectations. Leviton CAT 6A structured
cabling solutions are no exception. UTP eXtreme 6A channel- and component-rated
performance options plus a shielded solution meet the needs of any application.
Our component-rated UTP CAT 6A connectivity solution is the first in the industry to
achieve third party verification through Intertek/ETL. Our channel-rated UTP solution
balances economy with Leviton performance. And shielded connectivity delivers the
signal isolation and data security essential in government, gaming, medical,
and financial installations.
TABLE OF CONTENTS
CH
1
CH
2
UNDERSTANDING CAT 6A
02
03
05
Standards
Leviton CAT 6A Expertise
Leviton CAT 6A Systems
HORIZONTAL CABLING
08
09
11
TELECOMMUNICATIONS ROOM
CH
3
CH
4
14
15
17
18
Patch Panels
Cable Management Products
Cable Assemblies
Managing Cords
WORK AREA
20 Cabling
21 Workstation
CH
5
CAT 6A TERMINATION
CH
6
CH
7
CH
8
CH
9
28
29
31
33
Tips
110-Style Patch Panels
UTP Connectors
Shielded Connectors
CAT 6A TESTING
36
37
Performance Tests
AXT Testing
39
43
GLOSSARY
1.
INTRODUCTION
Understanding CAT 6A
Equipment, design and planning, and installation practices for CAT 6A
projects are all significantly different from previous generation structured
cabling systems. Use this guide to gain a better understanding of these
unique requirements, which will in turn help you accurately bid jobs and
shorten installation time. The final result will be a high-performance
system that supports todays requirements and provides a smooth
migration path toward 10G network performance.
STANDARDS
INTRO
The Category 6A
(Augmented Category 6)
standard addresses the
performance demands
of 10 Gigabit Ethernet
(10GBASE-T). Several
organizations detail
aspects of the standard,
but all define 6A
performance as up to
500 MHz and a maximum
distance of 100 meters
(328 feet). CAT 6A is
backward compatible
with CAT 6, 5e, 5, and
3 performance and
applications.
Organization:
TIA (Telecommunications
Industry Association)
Organization:
ISO (International Standards
Organization)
Organization:
IEEE (Institute of Electrical and
Electronics Engineers)
Standard:
568-C.2 (replaces 568-B.2-10)
Standard:
11801; Class EA Specification
Standard:
802.3an
Defines:
Performance requirements for
CAT 6A channels, permanent
links, and components
Defines:
Class EA cabling and component
performance requirements
for customer premises. ISO
equivalent of CAT 6A; commonly
specified outside of North America
Defines:
Channel performance for
10GBASE-T Ethernet over
balanced twisted pair cables
leviton.com/cat6a | 800.722.2082
CH. 1
CH. 1
INTRO
INTRO
Specification Support
Contractor Program
leviton.com/cat6a | 800.722.2082
CH. 1
CH. 1
INTRO
Shielded System
INTRO
Shielded
Die-cast QuickPort connectors
SlimLine patch cords
QuickPort patch panels
leviton.com/cat6a | 800.722.2082
CH. 1
2.
HORIZONTAL CABLING
CAT 6
CAT 6A
2nd Generation
UTP
1st Gen
2nd Gen
shielded
1st Gen
Shielded
2nd Gen
1stshielded
Gen
2nd Gen
shielded
Cable Type
5e
6A Gen1
6A Gen2
6A Shielded
6A Max
Average OD
.185"
.230"
.330"
.300"
.290"
.354"
Maximum Horizontal
Cable Distance
TIA specifies 90 meters
(295 feet) as the maximum
permanent link length and
100 meters (328 feet) for
maximum channel length.
The standards do not specify
a minimum length, but 10
feet is recommended to avoid
return loss and NEXT issues
due to the higher signal
frequency. Leviton is the only
manufacturer to provide lifetime
warranty coverage on qualified
installations for a 10 foot
permanent link, critical in data
center applications.
leviton.com/cat6a | 800.722.2082
1st Generation
UTP
TECH TIP
HORIZ.
CABLING
Cable Reels
Cable Pulling
SPOTLIGHT
CH. 2
DON'T
CABLING
Bend Radius
Placement
Slack Loops
TIA recommends storing 10 feet of extra cable in
the telecom room and 12-18 inches above work area
installations for re-terminations and to accommodate
moves, adds, and changes. Use an extended or figure 8
loop configuration to alleviate cable stress. Cable slack in
bundled or excessive loops has been shown to degrade
cable performance and is associated with return loss
failures. Plan carefully to ensure there is sufficient space
and support for heavy CAT 6A cable slack loops.
Pulling Lubricants
To maintain CAT 6A performance, choose spray or wipe
lubricants specifically designed for data communications
cables. Using other lubricants can degrade performance;
the majority of insertion loss failures have been traced
back to the use of general purpose lubricants.
leviton.com/cat6a | 800.722.2082
HORIZ.
TECH TIP
CH. 2
10
TIA-569 recommends 25% fill at initial installation and up to 50% with unplanned additions.
If a single cable tray will also carry power cables, a physical barrier is required to comply with
the NEC. Finally, ensure tray support spacing is sufficient to prevent excessive sagging.
Consider solid bottom tray for higher density applications.
Conduit Fill
A maximum conduit fill ratio
of 40% is recommended
by TIA-569 standards to
accommodate cable bundle
bend radius requirements and
allow for future expansion.
HORIZ.
CABLING
Conduit**
CH. 2
5e
6A1
6A2
6AS
.290"
.185"
.230"
.330"
.300"
2" x 6"
111
72
35
42
45
4" x 8"
298
192
93
113
121
1116
722
350
424
454
11
1 1/4
19
14
1 1/2
25
19
11
12
6" x 20"
3/4
11
HORIZ.
CABLING
To determine the proper tray size based on 25% fill, use the
following calculation:
Instructions
Example
.09 x 100 = 9
9 x .785 = 7.065 sq in
7.065 x 4 = 28.26 sq in
At 25% fill, a 28 sq in area is needed, so a standard 4" x 8" tray would be adequate.
Note: For conduit, size for 40% fill by substituting 2.5 as the multiplier in Step 5
TECH TIP
Step
Firestopping
CAT 6A cables may require larger firewall penetrations. Always follow
applicable national code (e.g. NEC or CEC) or a superceding authorityhaving jurisdiction (AHJ) codes for firestopping requirements.
leviton.com/cat6a | 800.722.2082
CH. 2
12
PERMANENT LINK (90m)
CHANNEL (100m)
3.
TELECOMMUNICATIONS ROOM
PATCH PANELS
ROOM
Shielded
VertiGO Zero-U
QuickPort
C1 Ultra QuickPort
leviton.com/cat6a | 800.722.2082
TELECOM
110-Style
SPOTLIGHT
CH. 3
14
CH. 3
TELECOM
CABLE MANAGEMENT
ROOM
Vertical Management
8" High-Capacity Versi-Duct
5" Versi-Duct
CAT 6A Gen2
.330"
Average OD
CAT 6A Shielded
.300"
.290"
Fill Rate
25%
50%
25%
50%
25%
50%
45
90
55
110
59
118
145
290
177
354
190
380
15
CABLE MANAGEMENT
ROOM
Versi-Duct
Front only
Front and rear
1 and 2RU grey designer covers
Bend radius limiters
leviton.com/cat6a | 800.722.2082
TELECOM
Horizontal Management
SPOTLIGHT
CH. 3
16
TELECOM
CABLE ASSEMBLIES
ROOM
SPOTLIGHT
CH. 3
Managing CORDS
ROOM
Bend Radius
Color Coding
Enhance data center and telecom room organization by
color-coding connectors and patch cords. Choose from
several schemes, depending on application and system
management priorities:
A/B switch fabric for data center redundancy
Connectivity types such as WAN/corporate data, LAN,
engineering networks, voice, and more
Campus location
Company colors
leviton.com/cat6a | 800.722.2082
TELECOM
TECH TIP
CH. 3
18
4.
WORK AREA
leviton.com/cat6a | 800.722.2082
WORK
AREA
In-Wall Applications
SPOTLIGHT
CH. 4
20
Passive Raised-Floor Enclosure
WORKSTATION
WORK
AREA
TECH TIP
CH. 4
leviton.com/cat6a | 800.722.2082
WORKSTATION
WORK
AREA
SPOTLIGHT
CH. 4
22
Standard Commercial
Acenti
Decora
Angled
Excella
5.
Data centers are one of the most critical parts of any data network
and thus require the highest levels of performance and reliability.
Cabling for data centers differs from horizontal installations in
several ways: typical distances, network function, pathways and
spaces, and more. CAT 6A cabling may affect requirements for all
of these, but especially pathways and spaces. Careful planning and
proper specifications will help ensure a successful installation.
leviton.com/cat6a | 800.722.2082
DATA
CENTER
SPOTLIGHT
CH. 5
24
CH. 5
DATA
CENTER
Configuration options:
Cable type
Breakout and overall length (up to
90 meters)
Jack, plug, or open termination
Even or staggered plug alignment
Cable and jack color
Plenum or riser sleeve
25
leviton.com/cat6a | 800.722.2082
DATA
CENTER
Component-Rated Connectors
SPOTLIGHT
CH. 5
26
6.
CAT 6A TERMINATION
Termination steps for CAT 6A connectors are much the same as for CAT 6,
with the major exception of handling the cables larger OD. To compensate,
Leviton has designed several exclusive features into its new CAT 6A connectors
to speed termination. Read on for details of these features, other tips for
a seamless installation, and for termination instructions for our 110-style
panel, UTP connectors, and shielded connector.
SPOTLIGHT
Component-Rated CAT 6A
Channel-Rated CAT 6A
Shielded CAT 6A
leviton.com/cat6a | 800.722.2082
TERMINATION TIPS
TERMINATION
SPOTLIGHT
CH. 6
28
CH. 6
INSTRUCTIONS
TERMINATION
NOTE: If wires appear to be bridged over the IDC, rather than securely
seated into the slot, pull out the wires and reseat and repunch them
(Figure B).
Once the CAT 6A module has been terminated, snap the 3-port
retention cap to the back of the connector top and bottom sides.
The retention cap can also be broken into single pieces (Figure C).
After the panel has been fully terminated, attach the cable
management bar to the back of patch panel (Figure D).
29
CH. 6
TERMINATION
B.
C.
INSTRUCTIONS
"Bridged" Wire
D.
leviton.com/cat6a | 800.722.2082
A.
30
CH. 6
INSTRUCTIONS
TERMINATION
Remove about 3" of cable jacket and center spline (stiff plastic separator
inside CAT 6A cable).
Leave the cable jacket within 1/8" of the connector side, then route the wires
for termination using the selected wiring scheme (Figure B). Route cable
perpendicular to the IDC field. Ensure there is enough slack in the twisted
pairs, and do not place the cable jacket into the termination field.
Use your fingers to carefully seat wires into the IDC slots. Maintain wire pair
twisting to within 1/2" of the IDC. Set a 110-style impact tool to low and
position it perpendicular to the connector. Seat and trim the cable one pair at
a time to prevent crushing the inside pairs (Figure C).
Place the Cone of Silence over the terminated wires for secure connection
and guaranteed CAT 6A performance (Figure D).
T568A
Wire Colors
T568B
Wire Colors
White/Green
White/Orange
Green
Orange
White/Orange
White/Green
Blue
Blue
White/Blue
White/Blue
Orange
Green
White/Brown
White/Brown
Brown
Brown
31
CH. 6
TERMINATION
B.
C.
D.
eme
eXtrT 6A
CA
eme
eXtrT 6A
CA
eme
eXtrT 6A
CA
leviton.com/cat6a | 800.722.2082
INSTRUCTIONS
A.
32
CH. 6
INSTRUCTIONS
TERMINATION
Insert the wires from the stripped cable into the stuffer
cap through the hole (Figure A).
Ensure that the drain wire is wrapped around the cable and
shield. Tie-wrap the drain wire to the shield. Do not overtighten the tie wrap! It should be snug, but not so tight that
it crushes the wires (Figure E).
33
INSTRUCTIONS
TERMINATION
A.
B.
D.
E.
B
A
leviton.com/cat6a | 800.722.2082
CH. 6
C.
B
A
B
34
7.
CAT 6A TESTING
Field testing of CAT 6A installations is much like field testing for CAT 5e and
CAT 6. However, CAT 6A testing is performed out to the higher frequency of
500 MHz. In addition, CAT 6A adds several tests for alien crosstalk (AXT).
PERFORMANCE TESTS
CAT 6A
TESTING
Field Testing
Wire map
Length
Attenuation
Propagation delay
Delay skew
NEXT near-end crosstalk
PSNEXT power sum near-end crosstalk
FEXT far-end crosstalk
ELFEXT (ACRF) equal level far-end
crosstalk (attenuation-to-crosstalk ratio,
far-end)
PSELFEXT (PSACRF) power sum equal
level far-end crosstalk (power sum
attenuation-to-crosstalk ratio, far-end)
Use an industry-recognized
UL Level 4 field tester
capable of testing to 500
MHz. Contact the test
equipment manufacturer for
any necessary hardware or
software upgrades, including
AXT testing capabilities, for
testing CAT 6A installations.
Perform permanent link or
channel tests for all installed
drops. Upon completion,
provide the customer with all
test results.
leviton.com/cat6a | 800.722.2082
CH. 7
36
CH. 7
AXT TESTING
PSANEXT
PSAACRF
SPOTLIGHT
CAT 6A
TESTING
Independent (ETL) Test Results for Leviton Short Channel (30 ft.) CAT 6A System
leviton.com/cat6a | 800.722.2082
AXT TESTING
CAT 6A
TESTING
TECH TIP
CH. 7
38
8. PART NUMBERS
PART NO.
DESCRIPTION
PART NO.
6A586-U24
6910G-U24
6A586-U48
49255-H24
6A587-U24
6910G-D48
6910G-U48
49255-H48
49255-D72
49256-H24
49256-D48
49256-H48
49256-D72
4W256-H24
4W256-H48
4W256-D72
6A587-U48
C1255-H48
49280-QP0
49280-QP3
49280-QP6
leviton.com/cat6a | 800.722.2082
DESCRIPTION
FLAT
ANGLED
PART
NUMBERS
RECESSED
ANGLED
CH. 8
40
CH. 8
PART
NUMBERS
UTP
Shielded
CONNECTORS
CONNECTORS
PART NO.
DESCRIPTION
PART NO.
eXtreme 6A component-rated
6A10G-R6
CAT 6A shielded
6S10G-S6A
eXtreme 6A channel-rated
6110G-R6
PATCH CORDS
DESCRIPTION
UTP/SHIELDED
PATCH CORDS
eXtreme 6A component-rated SlimLine
6AS10-xx*
6AS10-xx*
PATCH PANELS
CROSS CONNECT
4S255-S24
4S255-S48
4S256-S24
4S256-S48
41D6A-1F4
Purple (P)
Blue (L)
Ivory (I)
Yellow (Y)
Orange (O)
Crimson (C)
Green (V)
Grey (G)
Black (E)
Brown (B)
Orange (O)
Red (R)
Blue (L)
Green (G)
Grey (S)
Black (E)
41
CABLE MANAGEMENT
FRONT ONLY
BLACK
COLORS
8980L-VFO
8980L-VFR
43105-005
43105-05*
8C80L-VFO
8C80L-VFR
43108-008
43108-08*
43112-012
43112-12*
DESCRIPTION
PART
NUMBERS
Center-mount bracket
89265-BKT
89265-SL1
43115-015
43115-15*
Cable retainer
89265-wr1
43115-075
43115-75*
4980L-VFO
4980L-VFR
43115-600
4940L-VFO
4940L-VFR
44115-15E
Center-mount bracket
49265-BKT
44115-15*
(no maroon)
4S115-75E
59265-5DC
492RU-HFO
492RU-HFR
491RU-HFO
491RU-HFR
49265-DC2
49265-DC1
Cable retainer
49265-WR1
* = Colors: Choose from any of the colors below. Maroon fasteners are plenum-rated.
Blue (L)
Yellow (Y)
See Levitons full product catalog for more VELCRO Brand utility fastener part numbers.
Leviton offers a wide variety of metal front and rear cable managers. Go online to Leviton.com
or see our full product catalog for the complete selection.
leviton.com/cat6a | 800.722.2082
CH. 8
42
9. GLOSSARY
leviton.com/cat6a | 800.722.2082
44
leviton.com/cat6a | 800.722.2082
47
leviton.com/cat6a | 800.722.2082
48
leviton.com/cat6a | 800.722.2082
50
REFERENCES
This guide has been developed consistent with all known applicable cabling practices as defined by the following:
TIA-568-C.0: Generic Telecommunications Cabling for Customer Premises (replaces applicable TIA 568-B standards)
TIA-568-C.1: Commercial Building Telecommunications Cabling Standard (replaces applicable TIA 568-B standards)
TIA-568-C.2: Telecommunications Cabling, Copper Component and Cabling Specifications (replaces applicable TIA 568-B standards)
TIA-569-B: Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-606-A: Administration Standard for The Telecommunications Infrastructure of Commercial Buildings
TIA-942: Telecommunications Infrastructure Standard for Data Centers
ANSI-J-STD-607-A: Commercial Building Grounding and Bonding Requirements for Telecommunications
IEEE 802.3: Ethernet-based LANs (multiple standards)
IEEE 1100: Recommended Practice for Powering and Grounding Electronic Equipment
Intertek/ETL: Applicable verifications
ISO 11801: Generic Cabling for Customer Premises (multiple standards)
National Electrical Safety Code (NESC): Published by IEEE
National Electric Code (NEC, NFPA 70): Published by NFPA
Telecommunications Distribution Methods Manual (TDMM): Published by BICSI
Underwriters Laboratories (UL): Applicable listings and ratings
Always follow superceding national, state, and local codes and regulations.
51
VertiGO
Copyright Leviton Manufacturing Co., Inc. 2010. All rights reserved. Any reproduction is forbidden
without express written permission. Information in this guide is provided to assist in understanding
CAT 6A structured cabling systems. All information contained herein is deemed accurate to the best
of the companys knowledge at time of publication and is subject to change without notice.
leviton.com/cat6a | 800.722.2082
52
leviton.com/networksolutions
Leviton Corporate Headquarters
T +971.4.886.4722 F +971.4.886.4723
E infolme@leviton.com
Latin America
T +52.55.5082.1040 F +52.55.5386.1797
E lsamarketing@leviton.com
China
T +852.2774.9876 F +852.2774.1741
E infochina@leviton.com
India / SAARC
T +91.124.4356300
E lev_india@leviton.com
Canada
T +1.514.954.1840 F +1.514.954.1853
E pcservice@leviton.com
South Korea
T +82.2.3273.9963 F +82.2.3273.9962
E infokorea@leviton.com
Europe
T +47.40.60.30.30 F +47.40.60.30.31
E infoeurope@leviton.com
L/9 - #2722