Professional Documents
Culture Documents
Pujo
Result
Compared to the original concept (Figure 7), the peak
cooling load was reduced by 35% in the optimized
concept (Figure 8).For the entire airport, a cooling
energy consumption of 191 GWh per year is estimated,
which means 513 kWh for each conditioned square
meter of floor area per year. This is a reduction of 226
kWh/m2 energy savings per year. Bearing in mind that
the airport has a total floor area of 550,000 m2, the
total annual savings are considerable.
Result
The simulations demonstrate that hydronic radiant
cooling using an evaporative supply water source in
conjunction with a dedicated outside air system has
significant potential for energy savings. As compared to
a well-optimized conventional VAV system in the
Denver, Sacramento, Los Angeles, and San Francisco
climates, with and without a waterside economizer or
free cooling and a nighttime precooling cycle,
estimated energy savings ranged from 54% to 71%.
Furthermore, the Radiant+DOAS was capable of
providing comparable and sometimes improved thermal
comfort
Result
High-temperature cooling and low-temperature heating is realized by the
radiant floor system in large spaces. The typical cooling capacity of the
radiant floor is 3040 W/m2 with a mean chilled water temperature of 18
C; when there is high-intensity solar radiation (e.g., 120170 W/m2), the
values increase significantly to 110140 W/m2. A heating capacity range
of 3070 W/m2 is provided by the radiant floor with a supplied hot water
temperature of 3540 C, which is sufficient to satisfy the heating
requirement.
The radiant floor cooling and heating system provides a comfortable
thermal environment for occupants, and the indoor air temperature and
humidity distribution throughout the entire space features apparent
stratification in cooling mode and relative uniformity in heating mode. In
contrast to the jet ventilation system in Terminal 2, there is potential for
reducing heat loss through the building envelope in the upper region.
Result
The potential energy saving of this strategy was estimated to be in
the range of 6 to 51% depending on design strategies and
operational scenarios of system. Comfortable and healthy indoor
environment is achievable for this design when a parallel air system
satisfies latent load and ventilation requirement of space. Low air
movement was the only reported comfort concern for this design
since locally acclimatized occupants in the tropics prefer higher air
movement compared to dry and temperate climates. Regarding the
parallel air system strategy, DOAS with ceiling supply-ceiling
exhaust is suggested to be the best choice to be coupled with high
temperature cooling system. In addition, incorporation of energy
recovery systems like membrane based air to air heat exchanger
into DOAS can improve the overall efficiency of this design.