Product Documentation: Liebert HPM
Product Documentation: Liebert HPM
Business-Critical Continuity
Liebert HPM
6-205 kW Indoor Room Cooling Units
PRODUCT DOCUMENTATION
Introduction
Liebert HPM
Liebert HPM is the new serie of air conditioners developed by Emerson Network Power to
allow maximum flexibility of application in technological environments, from data processing
centers to manned control rooms and electronic centers for telecommunication. This series includes
units with a rated cooling capacity ranging from 6 to 205 kW.
Complete environmental control and reliability are paramount to ensure faultless operation of
computer rooms, telecom installations, data centres and technical applications. Emerson
Network Power products have traditionally set the industry standards. But today's world requires
more than just environmental control and reliability; it requires increasingly higher levels of overall
performances. While still offering unmatched environmental control and reliability, the new Liebert
HPM range raises the bar of performance in Precision Air Conditioning setting new standards in
terms of Energy Efficiency, Compactness and Sound emissions.
The new Liebert HPM range is available in a number of airflow versions: with upflow, downflow and
displacement airflow patterns across a full range of cooling modes: direct expansion, chilled water,
freecooling, dual fluid and constant (for an ultra high temperature and humidity control and air
filtration).
UNDER
OVER
Contents
Contents
Emerson
Network
Model Configuration
Operating Range
AirFlow Characteristics
Technical Specifications
Filter Section
Microprocessor Controls
10
Humidair Humidifier
11
Dimensional Data /
Connections
12
13
Hydraulic Circuits
Power
0-0
Energy Efficiency
EC Fan (Plug-in Electronically Commutated Fan),
EC fan Light, EC fan Full
Liebert HPM units are supplied with an exclusive fan type, this
enables you to greatly increase the unit's efficiency and
therefore significantly reduce operating costs.
EC fans [Electronically Commutated DC motors] have the
added advantage of higher fan shaft motor efficiency: from
45% of 1- phase motors, to 65% of 3-phase motors and to
85-90% of EC fans. As an example, a chilled water Liebert
HPM requires about 50% lower power input with this option,
respect the market average value.
Additional benefits are that, on start up, the Liebert HPM peak inrush current is lower than the
operating current. This means the EC fan option features a true soft start. Also compared to AC fan
supplied by the frequency converter, the advantages are evident and the input power is clearly
inferior: from 13 to 38% as a function of the working point.
The internal electronics of the EC fan are integrated into Emerson Network Power' controls.
The EC fan design allows a new approach in regulating environmental parameters within HPAC
applications. To name a few:
constant air volume
constant external static pressure
sound emission optimization
power input optimization
cooling capacity regulation (on request)
This enables each system to be optimized for the installation.
These features are available from standard Liebert HPM units supplied with the EC fan option and
we can summarized that with two words: versatility and efficiency.
EC Fan Light
EC fans Light are plugin, electronically commutated fans optional on Liebert HPM units. EC motor
is comparable to the DC brushless motor, except that the magnetic field is produced by permanent
magnets in the rotor; the commutation is done electronically and therefore without wear.
This kind of fan presents several technical and economical benefits:
Large energy costs saving (efficiency of motor up to 90%)
Less part numbers
Optimized low noise fan design
Variable speed control system via linear interface 010V DC, through iCOM
Available External static pressure up to 350 Pa
No need of autotransformer
Soft start
Liebert HPM-PD-273153 - 01.10.2012
1-1
EC Fan Full
Liebert HPM fitted with EC Fan full allows a perfect coupling in terms of airflow for each of the sites
needs. A full 0,1V adaptation can be done through iCOM control.
Furthermore on the units where it is allowed a full set of speed controls is available:
Parallel mode: reducing fans speed according to the room temperature decreasing it
proportionally the cooling capacity.
ECO mode: keep the minimum allowed fan speed for the longest part of the proportional band,
increasing in advance the cooling control device.
Delta mode: keep constant a temperature difference between 2 sensors installed where the
application needs.
Liebert HPM with EC Fan full is offering the full advantages of EC fan technology, adding to the
benefits in terms of noise, availability and efficiency the most advanced solutions in terms of control.
Easy maintenance
All components are easily accessible from the front of the room unit. The service compartment
facilitates checking and setting of refrigeration circuit, without changing aeraulic conditions.
The access to the fan is executed with the greatest care for easier interventions (maintenance and/or
fan replacement).
One very important feature, for example, is the possibility to check the total pressure drop of the high
pressure piping using the schrader connections available in the front part of the machine.
1-2
Model Configuration
Model Configuration
Digit Nomenclature
The unit is fully defined by seventeen digits.
9 10 11 12 13 14 15 16 17
S 06 U C
Digit 1
range
S Small
M Medium
L Large
Digit 5
Version
Digit 4
Air distribution
U
O
D
G
Digit 2 and 3
Size:
Downflow
Upflow
Displacement
Frontal Upflow
Digit 6 - Fan
1
2
0
1
2
3
EC fan Full
EC fan Light
None
Electric heating
Digit 9 - Humidification
0
V
None
Electrode humidifier
None
Hot water coil
G4
F5
G4; with Clogged Filter Pressure Switch
F5; with Clogged Filter Pressure Switch
Digit 14 -Paint
0
1
2
Digit 15 -Free
Digit 16 -Packing
For S06, S08, and S11xx units
F
PLP and Pallet
G
PLP and Wooden Crate
M Seaworthy
For all other units
P
PLP and Pallet
C
PLP and Wooden Crate
S
Seaworthy
2-1
Model Configuration
Air Distribution (4 Digit)
All units are available in the four configurations shown below.
U / UNDER
Downflow
D / DISPLACEMENT
Frontal air discharge at floor level
G / GRILLE
Frontal upflow with front air return
2-2
O / OVER
S06 model
Model Configuration
Version C
Chilled water units
Chilled water circuit
The unit is provided with a 3-way modulating valve (1), complete with incremental motor for the
control of water flow to the coil (2); the opening or closing signals, generated by the electronic
controler, manage the valve actuator movement in order to maintain the desired conditions. The
room air is cooled passing through the coil (2) (air/water heat exchanger), moved by the motor fan
(3).
The iCom Control (or CDL Graphic Display / opt.) controls all parameters. It is possible to adjust,
for instance: set points, proportional or proportional+integral temperature, integrating factor and
valve characteristics. It is also possible to manually adjust the valve with a suitable wrench.
SxxUC
MxxUC
LxxUC
Units
Chilled Water
(from Customer)
2-3
Model Configuration
Version R
Redundant chilled water units
Double chilled water circuit
The unit is equipped with two independent chilled water circuits interlaced to one single coil, each
circuit is equipped with 3-way/2-way control valve (x), complete with incremental motors for the
water flow control of each circuit. These units can be connected to chilled water circuits coming from
two independent sources. In case the first circuit failure, the second one can substitute the need for
cooling capacity and provide the necessary back up.
According to the setting of the controller the actuators can be managed in three different ways:
parallel mode: both valves are managed by the same input signal-always have the same
position;
cascade mode: in this case the first valve is managed until 70% of temperature proportional band
(cooling band) is reached then also second valve will start to open second circuit;
circuit redundancy mode: by external input you can choose which circuit (valve) will be duty and
which will be closed, only enabled circuit will have the valve driven according to the temperature
proportional band.
Both circuits provide the same cooling capacity.
MxxUR
LxxUR
Units
Chilled Water
(from Customer)
2-4
MxxOR
Units
1
Chilled Water
(from Customer)
Model Configuration
Displacement D
Top air inlet, Front air discharge
The Packaged Indoor Liebert HPM Displacement units, inject air next to the floor at low speed and
take it in again from above, in the room upper part. The injected air generates a fresh air front hitting
and moving the existing room air. The heat sources, on their turn, originate hot air ascensional
currents to the room upper part due to natural convection. The hot air, limited and stratified above,
is then taken in again by the conditioner.
The air diffusion limits the mixing between injected air mass and existing air, causing a useful
temperature stratification in the room.
The Displacement system is suitable for industrial rooms and for telecom unmanned sites with very
high specific load [kW/m2].
The main advantages are:
a better efficiency (more than 10%) of the cooling process 1, acting on air with temperature higher
than the room average value;
better efficiency of the ventilation process, needing lower exit speeds;
lower installation costs: the false floor is not request as per Under units.
lower operating costs: due to better efficiencies.
Redundant (xR) units are not available in displacement execution. With R models you can satisfy
displacement effect requirement only using downflow execution + basemodule with frontal air
discharge.
28C
2-5
Operating Range
Operating Range
Liebert HPM units are provided for operating within the following working ranges (the limits concern
new units on which correct installation have already been made):
All versions
Room air conditions
Hot water circuit
Storage conditions
from:
to:
inlet water temperature
water pressure
from:
to:
For C units
Chilled water circuit
inlet water temperature
min. 55C
water pressure
max. 16 bar
Max. differential pressures on the modulating valve (2 or 3 ways)
- Max. differential pressure through the closed valve: Dpcv
- Max. differential pressure across the valve for modulating service: Dpms
S models
Dpcv (kPa)
Dpms (kPa)
350
300
300
300
300
300
350
300
300
300
300
300
Dpcv (kPa)
Dpms (kPa)
175
175
75
75
175
175
75
75
Dpcv (kPa)
Dpms (kPa)
145
145
145
145
145
145
125
125
200
200
200
200
200
200
125
125
S06xC
S08xC
S11xC
S15xC
S18xC
S29xC
M models
M44xC
M55xC
M66xC
M77xC
L models
L90xC
L10xC
L12xC
L14xC
L15xC
L16xC
L18xC
L20xC
M models
M24U/OR
M45U/OR
M60U/OR
L models
L85UR
L11UR
L13UR
3-1
Dpcv (kPa)
Dpms (kPa)
300
175
175
300
175
175
Dpcv (kPa)
Dpms (kPa)
525
300
300
525
300
300
Technical Data
TechnicalData
MODELS
Power supply voltage (V 10%)
V/Ph/Hz
230/1/50
S08
S11
S15
S18
S29
M44
M55
M66
M77
14220
400/3/50
PERFORMANCE (1)
m3/h
1395
2200
2800
4500
5200
6150
8150
12740
13650
ESP (Under)
Pa
20
20
20
20
20
20
20
20
20
20
Pa
300
240
85
300
300
250
150
280
210
140
ESP (Over)
Pa
50
50
50
50
50
50
50
50
50
50
Pa
300
240
114
300
300
250
150
280
210
140
kW
0.12
0.17
0.35
0.70
0.96
1.51
1.54
2x 1.08
2x 1.44
2x 1.54
83.5
air flow
kW
6.2
9.2
12.6
17.5
22.4
28.8
43.6
58.6
68.8
kW
5.6
8.5
11.2
16.7
20.3
25.0
34.7
49.7
56.2
64.8
0.90
0.92
0.89
0.95
0.91
0.87
0.80
0.85
0.82
0.78
water flow
l/s
0.30
0.44
0.60
0.83
1.07
1.38
2.08
2.79
3.28
3.99
kPa
91
33
45
120
91
121
109
101
75
93
55.4
kW
4.1
6.4
8.8
12.3
15.8
20.1
29.6
40.6
47.1
kW
4.1
6.4
8.8
12.3
15.8
20.1
29.6
40.6
47.1
54.1
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
water flow
l/s
0.20
0.31
0.42
0.59
0.75
0.96
1.41
1.94
2.25
2.65
kPa
43
17
23
64
47
62
53
51
37
43
quantity
no.
poles
no.
3.01
2.93
2.93
4.0
4.0
4.0
4.0
8.0
8.0
8.0
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
dB(A)
53.6
50.3
53.6
48.6
51.8
50.0
50.5
53.8
55.8
57.2
dB(A)
55.7
51.4
55.7
51.9
55.5
54.3
54.6
53.2
55.0
56.4
m2
0.28
0.47
0.47
0.63
0.63
0.63
0.85
1.67
1.67
1.67
RP
RP
RP
RP 1
RP 1
RP 1
RP 1
RP 1
RP 1
RP 1
dm3
3.5
6.7
8.6
9.8
12.5
15.1
22.4
28.8
38.4
45.2
width
mm
750
750
750
750
750
750
1000
1750
1750
1750
depth
mm
400
500
500
750
750
750
850
850
850
850
height
mm
1950
1950
1950
1950
1950
1950
1950
1950
1950
1950
footprint
m2
0.30
0.38
0.38
0.56
0.56
0.56
0.85
1.49
1.49
1.49
net
kg
135
150
165
190
210
230
330
480
550
600
kg
140
157
172
200
220
240
340
490
560
610
Copper/alluminium
WEIGHTS
(1) AT THE FOLLOWING STANDARD CONDITIONS: ambient conditions 24C db; 50% R.H.(17C wb). The air flow of the units refers to the
standard configuration with G4 class filter.
Note 1: Cooling capacities are gross. To obtain the net cooling capacities the fan power input must be substracted.
Note 2: Performance with EC Fan Full, when available.
(2) Max. external static pressure for the indicated air flow
(3) Measured at 1.5 m height and 2 m front distance, in free field, at standard operating conditionswith working fan(s).
4-1
Technical Data
LxxU C series
L90
MODELS
Power supply voltage (V 10%)
L10
V/Ph/Hz
L12
L14
L15
25400
400/3/50
PERFORMANCE (1)
m3/h
19060
20400
23100
24500
ESP (Under)
Pa
20
20
20
20
20
Pa
300
280
300
240
180
kW
3.20
3.84
4.27
5.73
6.84
kW
90.7
103.4
117.9
144.0
158.9
kW
76.8
83.9
97.4
111.7
120.7
0.85
0.81
0.83
0.78
0.76
water flow
l/s
4.33
4.93
5.62
6.87
7.58
kPa
71
70
101
124
137
kW
61.4
69.3
78.5
93.1
100.6
kW
61.4
69.3
78.5
92.1
97.0
1.0
1.0
1.0
0.99
0.96
air flow
water flow
l/s
2.93
3.31
3.75
4.45
4.81
kPa
35
33
47
55
59
quantity
no.
poles
no.
2x 5.0
2x 5.0
3x 5.0
3x 5.0
3x 5.0
2x 0.1
2x 0.1
3x 0.1
3x 0.1
3x 0.1
dB(A)
58.8
59.8
63.7
63.3
65.4
m2
2x 1.74
2x 1.74
2x 2.24
2x 2.24
2x 2.24
R2
R2
R 2
R 2
R 2
dm3
56.6
70.8
72.5
90.5
106.0
width
mm
2050
2050
2550
2550
2550
depth
mm
890
890
890
890
890
height
mm
1950
1950
1950
1950
1950
footprint
m2
1.82
1.82
2.27
2.27
2.27
Copper/alluminium
WEIGHTS
net
kg
620
630
830
800
810
kg
635
645
845
815
825
(1) AT THE FOLLOWING STANDARD CONDITIONS: ambient conditions 24C db; 50% R.H.(17C wb). The air flow of the units refers to the
standard configuration with G4 class filter.
Note 1:Cooling capacities are gross. To obtain the net cooling capaicities the fan heat load must be substracted.
Note 2: Performance with EC fan Full, when available.
(2) Max. external static pressure for the indicated air flow
(3) Measured at 1.5 m height and 2 m front distance, in free field, at standard operating conditionswith working fan(s).
4-2
Technical Data
LxxU C series
MODELS
Power supply voltage (V 10%)
L16UC
L18UC
L20UC
V/Ph/Hz
400/3/50
400/3/50
400/3/50
35650
PERFORMANCE (1)
m3/h
29600
35410
ESP
Pa
20
20
20
Pa
100
100
100
kW
8.1
10.6
10.6
air flow
kW
153.9
182.2
204.5
kW
134.6
159.9
172.3
0.87
0.88
0.84
water flow
l/s
7.35
8.69
9.75
kPa
115
141
150
kW
112.1
133.1
144.8
kW
112.1
133.1
144.8
1.0
1.0
1.0
water flow
l/s
5.35
6.36
6.92
kPa
63
79
79
quantity
no.
poles
no.
3x 5.0
4x 5.0
4x 5.0
EC fan FLA
EC fan LRA
3x 0.1
4x 0.1
4x 0.1
dB(A)
66.4
68.5
68.6
m2
5.38
6.00
7.20
R 2
R 2
R 2
dm3
131.0
142.0
169.0
width
mm
2550
3350
3350
depth
mm
890
890
890
height
mm
2150
1950
2150
footprint
m2
2.27
2.98
2.98
net
kg
940
1000
1085
kg
960
1020
1105
Copper/alluminium
WEIGHTS
(1) AT THE FOLLOWING STANDARD CONDITIONS: ambient conditions 24C db; 45% R.H. The air flow of the units refers to the standard
configuration with G4 class filter.
Note 1:Cooling capacities are gross. To obtain the net cooling capaicities the fan heat load must be substracted.
Note 2: Performance with EC fan Full, when available.
(2) Max. external static pressure for the indicated air flow
(3) Measured at 1.5 m height and 2 m front distance, in free field, at standard operating conditions.
4-3
Technical Data
Options (further information: Chap. 8)
MODELS
Power supply voltage (V 10%)
V/Ph/Hz
S06
S08
S11
S15
S18
S29
M44
M55
M66
M77
230/1/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Electrical heating
FLA
total power / steps
8.5
6.5
6.5
8.6
8.6
8.6
11.0
22.0
22.0
22.0
kW/no.
1.50/1
4.50/3
4.50/3
5.85/3
5.85/3
5.85/3
7.5/1
15.0/2
15.0/2
15.0/2
6.5
4.6
4.6
9.0
9.0
9.0
9.0
13.0
13.0
13.0
kW
1.5
3.0
3.0
5.8
5.8
5.8
5.8
9.0
9.0
9.0
kW
2.4
4.8
5.6
8.4
9.2
10.2
14.3
32.8
34.3
35.1
kW
3.1
6.2
7.3
11.4
12.6
14.0
19.3
41.7
44.2
46.3
Humidifier
FLA
Nominal power
Heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out
80/65C)
Re-heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out
80/65C)
MODELS
Power supply voltage (V 10%)
V/Ph/Hz
L90
L10
L12
L14
L15
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Electrical heating
FLA
total power / steps
26.0
26.0
26.0
26.0
26.0
kW/no.
18.0/3
18.0/3
18.0/3
18.0/3
18.0/3
13.0
13.0
13.0
13.0
13.0
kW
9.0
9.0
9.0
9.0
9.0
kW
21.6
22.5
27.7
28.7
29.3
kW
26.4
27.8
34.1
37.5
38.7
Humidifier
FLA
Nominal power
Heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out 80/65C)
Re-heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out 80/65C)
MODELS
Power supply voltage (V 10%)
L16UC
L18UC
L20UC
V/Ph/Hz
400/3/50
400/3/50
400/3/50
Electrical heating
FLA
total power / steps
26
26
26
kW/no.
18.0/3
18.0/3
18.0/3
13.0
13.0
13.0
kW
9.0
9.0
9.0
kW
28.8
41.1
37.3
kW
37.7
53.9
49.2
Humidifier
FLA
Nominal power
Heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out 80/65C)
Re-heating mode
Hot water coil
heating capacity
(at 24C, 50%, water in/out 80/65C)
4-4
Technical Data
Tab. 4b - Chilled water unit Displacement air distribution, S-MxxD C series
MODELS
S06D
power supply voltage (V 10%)
V/Ph/Hz
230/1/50
PERFORMANCE (1)
air flow
m3/s
1190
external static pressure ESP
0
EC Fan Full absorbed power
kW
0.07
inlet water temperature: 7C - outlet water temperature: 12C
total cooling capacity
kW
5.6
sensible cooling capacity
kW
4.8
SHR (sensible/total ratio)
0.86
water flow
l/s
0.27
water side pressure drop
kPa
74
inlet water temperature: 10C - outlet water temperature: 15C
total cooling capacity
kW
3.6
sensible cooling capacity
kW
3.6
SHR (sensible/total ratio)
1.00
water flow
l/s
0.18
water side pressure drop
kPa
34
FAN
type
quantity
no.
1
poles
no.
4
FLA std. fan
3.01
LRA std. Fan
0.1
sound pressure level (3)
dB(A)
55.6
CHILLED WATER COIL
pipes/fins
frontal surface
CHILLED WATER CONNECTIONS
water connections ISO 7/1
CHILLED WATER CONTENT
Total chilled water internal volume
DIMENSIONS
width
depth
height
footprint
WEIGHTS
net
gross (standard packing see Fig. 12j)
m2
0.28
S08D
400/3/50
S11D
400/3/50
S15D
400/3/50
S18D
400/3/50
S29D
400/3/50
M44D
400/3/50
1980
0
0.16
2575
0
0.30
4050
0
0.61
4590
0
0.70
5445
0
1.45
7780
0
1.45
8.5
7.7
0.91
0.41
29
11.9
10.4
0.87
0.57
41
16.2
15.2
0.94
0.77
106
20.6
18.3
0.89
0.98
78
26.5
22.6
0.85
1.26
104
42.1
33.4
0.79
2.01
102
5.9
5.9
1.00
0.28
15
8.2
8.2
1.00
0.39
20
11.3
11.3
1.00
0.54
55
14.3
14.3
1.00
0.69
40
18.3
18.3
1.00
0.87
52
28.5
28.5
1.00
1.36
50
1
4
2.93
0.1
55.9
1
4
4.0
0.1
60.3
1
4
4.0
0.1
60.3
0.47
Copper/treated alluminium
0.47
0.63
0.63
0.63
0.85
RP
RP
RP 1
RP 1
RP 1
dm3
3.5
6.7
8.6
9.8
12.5
15.1
22.4
mm
mm
mm
m2
750
400
1950
0.30
750
500
1950
0.38
750
500
1950
0.38
750
750
1950
0.56
750
750
1950
0.56
750
750
1950
0.56
1000
850
1950
0.85
kg
kg
135
140
150
157
165
172
190
200
210
220
230
240
330
340
(1) AT THE FOLLOWING STANDARD CONDITIONS: ambient conditions 24C db; 50% R.H.(17C wb). The air flow of the units refers to the
standard configuration with G4 class filter.
Note 1:Cooling capacities are gross. To obtain the net cooling capaicities the fan heat load must be substracted.
Note 2: Performance with EC Fan Full, when available.
(2) Max. external static pressure for the indicated air flow
(3) Measured at 1.5 m height and 2 m front distance, in free field, at standard operating conditionswith working fan.
S06D
S08D
S11D
S15D
S18D
S29D
M44D
V/Ph/Hz
230/1/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
A
kW/no.
6.5
1.50/1
6.5
4.50/3
6.5
4.50/3
8.4
5.85/3
8.4
5.85/3
8.4
5.85/3
11.0
7.5/1
kW
2.1
4.5
5.3
7.6
8.3
9.3
14.0
kW
2.8
5.7
6.9
10.6
11.6
13.0
18.9
4-5
Technical Data
Tab. 4c - Double chilled water circuit, unit MxxU/O and LxxU, R series (Redundant series)
M24
MODELS
power supply voltage (V 10%)
M45
M60
V/Ph/Hz
L85
L11
L13
32700
400/3/50
PERFORMANCE (1)
m3/s
7050
11500
13900
17150
23900
ESP (Under)
Pa
20
20
20
20
20
20
Pa
150
270
80
240
260
170
ESP (Over)
Pa
50
50
50
Pa
150
270
80
kW
1.54
2.25
2 x 1.96
2 x 1.93
3 x 1.9
4 x 2.3
kW
24.2
46.9
60.7
80.3
99.7
118.6
kW
24.0
43.1
54.0
68.3
89.1
118.6
0.99
0.92
0.89
0.85
0.89
water flow
l/s
1.15
2.24
2.89
3.83
4.76
5.66
kPa
84
75
98
99
91
98
kW
17.9
33.4
43.3
54.7
69.0
93.6
kW
17.9
33.4
43.3
54.7
69.0
93.6
water flow
l/s
0.86
1.59
2.07
2.61
3.29
4.48
kPa
48
40
52
48
46
63
quantity
no.
poles
no.
4.0
5.0
2 x 3.6
2 x 5.0
3 x 5.0
4 x 5.0
air flow
FLA EC fan
LRA EC fan
0.1
0.1
2 x 0.1
2 x 0.1
3 x 0.1
4 x 0.1
dB(A)
49.4
62.4
59.2
64.1
66.2
69.3
dB(A)
51.4
63.4
60.2
m2
0.79
1.48
1.51
3.2
4.2
5.7
RP 1
RP 1
RP 1
R 2)
R2
R 2
dm3
2 x 9.5
2 x 19
2 x 20
2 x 38
2 x 50
2 x 66
width
mm
1000
1750
1750
2050
2550
3350
depth
mm
850
850
850
890
890
890
height
mm
1950
1950
1950
1950
1950
1950
footprint
m2
0.85
1.49
1.49
1.82
2.27
2.98
Copper/alluminium
WEIGHTS
net
kg
335
520
610
650
865
1020
kg
345
530
620
665
880
1040
(1) AT THE FOLLOWING STANDARD CONDITIONS: ambient conditions 24C db; 50% R.H. (24C db; 45% R.H. for unit L13).
The air flow of the units refers to the standard configuration with G4 class filter.
Note 1:Cooling capacities are gross. To obtain the net cooling capacities the fan heat load must be substracted.
Note 2:Cooling capacities refer to only one hydraulic circuit running.
(2) Max. external static pressure for the indicated air flow.
(3) Measured at 1.5 m height and 2 m front distance, in free field, at standard operating conditionswith working fan(s).
4-6
Technical Data
Options (further information: Chap. 8)
MODEL
power supply voltage (standard)
V/Ph/Hz
M24
M45
M60
L85
L11
L13
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Electrical heating
FLA
total power / steps
11.0
22.0
22.0
26.0
26.0
kW/no.
7.5/1
15.0/2
15.0/2
18.0/3
18.0/3
26
18.0/3
Humidifier
FLA
Nominal power
9.0
13.0
13.0
13.0
13.0
13.0
kW
5.8
9.0
9.0
9.0
9.0
9.0
kW
13.3
30.8
33.5
19.4
27.4
39.2
kW
17.1
38.9
42.8
24.8
34.3
48.4
Heating mode
Hot-water coil
heating capacity
(@24C, 50%R.H., water in/out 80/65C)
Re-heating mode
Hot-water coil
heating capacity
(@24C, 50%R.H., water in/out 80/65C)
4-7
Airflow characteristics
Airflow characteristics
The graphs give the available and allowed external static pressure against airflow at different motor
supply voltages and different signal for EC Fan for all units, with G4 air filter, standard configuration.
Pa
300
300
10 V
8V
7,5 V
8,5 V
7V
250
6,5 V
HPM S06
ESP
1395 m3/h
HPM S08
ESP
250
2200 m3/h
8V
7,5 V
6V
200
200
7V
5,5 V
6,5 V
150
150
5V
100
6V
100
4,5V
5,5 V
5V
50
50
4,5V
4V
4V
0
1320
0
843
943
1043
1143
1243
1343
1443
1543
1643
1743
1420
1520
1620
1720
1820
1920
2020
2120
2220
2320
2420
2520
2620
2720
m3/h
m3/h
Pa
300
Pa
300
8V
8.5V
9.5V
9V
10V
HPM S15
ESP
7.5V
4520 m3/h
10 V
HPM S11
ESP
250
8,5 V
8V
250
7V
200
200
7,5 V
6.5V
7V
150
150
6,5 V
6V
2800 m3/h
100
100
6V
5.5V
5,5 V
50
50
5V
5V
0
1680
1780
1880
1980
2080
2180
2280
2380
2480
2580
2680
2780
2880
2980
3080
0
2750
m3/h
300
3250
3750
4250
4750
m3/h
5250
300
8V
8.5V
Pa
9V
9.5V
10V
5200 m3/h
9.5V
9V
8.5V
Pa
HPM S18
ESP
10V
HPM S29
ESP
5460 m3/h
250
250
7.5V
200
8V
200
7V
7.5V
150
150
6.5V
7V
6V
100
100
6.5V
5.5V
50
50
6V
5V
0
3250
5 --- 1
3750
4250
4750
5250
5750
6250
m3/h
0
3700
4200
4700
5200
5700
6200
6700 m3/h
Airflow characteristics
300
300
9V
8.5V
Pa
9.5V
10V
HPM M44
ESP
8150 m3/h
8.5V
Pa
9V
9.5V
10V
HPM M55
ESP
8V
12740 m3/h
250
250
8V
7.5V
200
200
7V
7.5V
150
150
6.5V
7V
100
100
6V
6.5V
50
50
5.5V
0
5250
5750
6250
6750
7250
7750
8250
8750
0
8400
m3/h 9250
300
9400
10400
11400
12400
13400
14400
15400
m3/h
300
8.5V
9V
9.5V
9V
10V
Pa
13650 m3/h
8V
14220 m3/h
250
250
7.5V
200
10V
9.5V
Pa
HPM M66
ESP
HPM M77
ESP
8.5V
200
8V
7V
150
150
7.5V
6.5V
100
100
7V
6V
50
50
6.5V
5.5V
0
8400
9400
10400
11400
8.5V
9V
12400
300
8V
13400
14400
10500
10V
11500
12500
9V
9.5V
8.5V
Pa
HPM L90
ESP
19060 m3/h
7.5V
m3/h
13500
14500
m3/h
15500
300
9.5V
Pa
250
15400
0
9500
10V
HPM L10
ESP
8V
20400 m3/h
250
7.5V
200
200
7V
150
150
7V
6.5V
100
100
6.5V
6V
50
50
6V
5.5V
0
12500
14500
16500
18500
20500
22500
24500
0
13500
m3/h
300
15500
17500
19500
21500
23500
m3/h 25500
300
8.5V
Pa
10V
9.5V
9V
8.5V
HPM L12
ESP
8V
23100 m3/h
250
9V
9.5V
10V
Pa
8V
HPM L14
ESP
24500 m3/h
250
7.5V
200
200
7.5V
7V
150
150
7V
100
100
6.5V
6.5V
50
6V
50
6V
6V
0
16200
18200
20200
22200
24200
26200
28200
0
16200
18200
20200
22200
24200
26200
28200
m3/h
5 --- 2
Airflow characteristics
300
300
9V
10V
9.5V
Pa
HPM L15
ESP
8.5V
25400 m3/h
250
9.5V
9V
Pa
10V
HPM L16
ESP
29600 m3/h
250
8.5V
8V
200
200
150
150
8V
7.5V
100
100
7V
7.5V
50
50
6.5V
7V
0
18000
20000
300
22000
9.5V
24000
26000
0
21500
m3/h
28000
23500
300
Pa
10V
9V
9.5V
HPM L18
ESP
Pa
35400 m3/h
250
25500
27500
29500
31500
m3/h
10V
9V
35650 m3/h
HPM L20
ESP
250
200
200
8.5V
8.5V
150
150
8V
8V
100
50
100
7.5V
7.5V
50
0
26500
28500
30500
32500
34500
36500
0
26500
m3/h 38500
28500
30500
32500
34500
m3/h 38500
36500
300
10V
9.5V
9V
8.5V
Pa
HPM M24
ESP
7050 m3/h
9V
9.5V
10V
Pa
HPM M45
ESP
8V
11500 m3/h
250
250
8.5V
200
200
7.5V
8V
150
150
7V
7.5V
100
100
6.5V
7V
50
50
0
5000
5500
6000
6500
7000
0
8000
m3/h 8000
7500
9000
10000
11000
12000
m3/h 14000
13000
300
300
13900 m3/h
HPM M60
ESP
10V
9.5V
9V
10V
Pa
HPM L85
ESP
Pa
17150 m3/h
8.5V
250
250
9.5V
200
200
8V
9V
150
150
7.5V
8.5V
100
100
7V
50
50
8V
0
11000
5 --- 3
11500
12000
12500
13000
13500
14000
14500
m3/h 15000
0
13000
14000
15000
16000
17000
18000
19000
20000
m3/h21000
Airflow characteristics
300
300
8.5V
9.5V
9V
9V
8.5V
10V
Pa
23900 m3/h
9.5V
10V
Pa
HPM L11
ESP
32700 m3/h
HPM L13
ESP
250
250
8V
8V
200
200
7.5V
7.5V
150
150
7V
100
100
7V
6.5V
50
50
6.5V
6V
0
17000
19000
21000
23000
25000
27000
m3/h
0
22000
24000
26000
28000
30000
32000
34000
5 --- 4
Liebert HPM units have been designed with particular care for sound and vibration problems. The
complete mechanical insulation of the ventilating section, combined with the special study of the
aeraulic circuit as a consequence of accurate researches made in our thermodynamical laboratories
and the oversizing of the components crossed by air offer the highest ventilation efficiency with the
lowest sound emission.
1.5 m
2m
6-1
Mode
Level
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
63
125
250
500
1000
2000
4000
8000
Sound Level
[dB(A)]
50.3
61.7
45.7
63.8
45.2
69.1
62.9
41.8
67.1
48.2
64.0
43.2
58.1
48.9
58.7
49.5
61.1
51.5
62.3
57.4
77.9
68.5
78.9
69.5
82.8
73.4
82.4
73.0
84.5
75.1
85.5
76.1
87.6
78.2
87.7
78.3
50.3
61.7
45.7
63.8
45.2
69.1
62.9
41.8
67.1
48.2
64.0
43.2
58.1
48.9
58.7
49.5
61.1
51.5
62.3
56.4
75.3
61.5
76.3
62.5
80.2
66.4
79.8
66.0
81.9
68.1
82.9
69.1
85.0
71.2
85.1
71.3
54.9
63.5
57.4
65.7
60.3
71.0
69.2
47.8
73.4
52.6
71.9
49.2
66.0
47.5
66.6
52.5
69.0
54.5
70.2
56.3
84.7
62.1
85.7
63.1
89.6
67.0
89.2
66.6
91.3
68.7
92.3
69.7
94.4
71.8
94.5
71.9
56.3
63.2
54.0
65.4
57.3
70.7
69.6
54.9
73.8
54.8
75.3
53.9
69.4
51.4
70.0
52.9
72.4
54.9
73.6
59.9
82.6
64.8
83.6
65.8
87.5
69.7
87.1
69.3
89.2
71.4
90.2
72.4
92.3
74.5
92.4
74.6
51.6
60.0
47.4
62.2
49.9
67.5
66.4
44.5
70.6
49.0
67.6
45.8
61.7
47.5
62.3
50.9
64.7
52.9
65.9
52.0
73.6
54.3
74.6
55.3
78.5
59.2
78.1
58.8
80.2
60.9
81.2
61.9
83.3
64.0
83.4
64.1
46.7
56.0
43.1
58.1
45.8
63.4
62.1
38.8
66.3
45.4
65.8
43.8
59.9
44.5
60.5
49.8
62.9
51.8
64.1
51.9
69.1
47.0
70.1
48.0
74.0
51.9
73.6
51.5
75.7
53.6
76.7
54.6
78.8
56.7
78.9
56.8
44.9
54.2
38.7
56.4
42.2
61.7
59.3
36.2
63.5
42.7
63.7
41.4
57.8
43.5
58.4
45.0
60.8
47.0
62.0
49.6
68.3
49.0
69.3
50.0
73.2
53.9
72.8
53.5
74.9
55.6
75.9
56.6
78.0
58.7
78.1
58.8
37.1
51.7
30.9
53.8
34.4
59.1
55.2
29.7
59.4
36.5
59.0
34.5
53.1
36.2
53.7
38.4
56.1
40.4
57.3
41.8
58.3
38.8
59.3
39.8
63.2
43.7
62.8
43.3
64.9
45.4
65.9
46.4
68.0
48.5
68.1
48.6
26.1
45.3
23.7
47.4
26.1
52.7
50.7
23.1
54.9
33.4
56.3
31.4
50.4
33.9
51.0
31.7
53.4
33.7
54.6
37.3
50.6
31.1
51.6
32.1
55.5
36.0
55.1
35.6
57.2
37.7
58.2
38.7
60.3
40.8
60.4
40.9
53.6
62.5
50.3
64.7
53.2
70.0
68.3
48.6
72.5
51.8
72.1
50.0
66.2
50.5
66.8
53.8
69.2
55.8
70.4
57.2
77.9
58.8
78.9
59.8
82.8
63.7
82.4
63.3
84.5
65.4
85.5
66.4
87.6
68.5
87.7
68.6
Mode
Level
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
63
125
250
500
1000
2000
4000
8000
Sound Level
[dB(A)]
56.1
71.8
51.8
67.0
56.6
71.1
61.1
52.3
65.9
55.9
63.4
54.6
57.8
56.5
57.1
57.2
58.7
59.0
60.3
58.4
56.1
71.8
51.8
67.0
56.6
71.1
61.1
52.3
65.9
55.9
63.4
54.6
57.8
56.5
57.1
52.1
58.7
53.9
60.3
53.9
60.3
74.6
56.0
69.9
60.8
74.0
67.4
56.5
72.2
60.1
71.3
58.8
65.7
56.0
65.0
56.1
66.6
57.9
68.2
57.9
55.7
74.3
51.4
69.6
56.2
73.7
67.8
51.9
72.6
55.5
74.7
54.8
69.1
55.8
68.4
51.7
70.0
53.5
71.6
55.6
54.6
71.1
50.3
66.4
55.1
70.5
64.6
50.8
69.4
54.4
67.0
52.1
61.4
54.2
60.7
50.5
62.3
52.3
63.9
53.2
49.6
68.1
45.3
63.3
50.1
67.4
60.3
45.8
65.1
49.4
65.2
48.7
59.6
48.0
58.9
49.2
60.5
51.0
62.1
52.6
45.8
66.3
41.5
61.6
46.3
65.7
57.5
42.0
62.3
45.6
63.1
45.3
57.5
43.8
56.8
43.7
58.4
45.5
60.0
47.0
39.2
63.8
34.9
59.0
39.7
63.1
53.4
35.4
58.2
39.0
58.4
39.2
52.8
36.2
52.1
37.2
53.7
39.0
55.3
40.8
29.5
58.4
25.2
53.6
30.0
57.7
47.9
25.7
52.7
29.3
54.7
29.4
49.1
27.0
48.4
33.1
50.0
34.9
51.6
36.1
55.7
74.2
51.4
69.5
56.2
73.6
66.5
51.9
71.3
55.5
71.4
54.3
65.8
54.6
65.1
53.2
66.7
55.0
68.3
56.4
Mode
Level
31.5
63
125
250
500
1000
2000
4000
8000
Sound
Level
[dB(A)]
(1)
SPL
58.1
58.1
60.8
54.2
51.5
52.2
46.4
36.4
29.6
55.6
(4)
PWL
64.4
64.4
66.3
66.0
62.8
58.7
57.0
54.4
48.0
65.3
(1)
SPL
58.4
58.4
6131
54.5
51.8
52.5
46.7
36.7
29.9
55.9
(4)
PWL
61.9
61.9
63.7
63.4
60.2
56.1
54.4
51.9
45.5
62.7
(1)
SPL
59.4
59.4
62.1
55.5
52.8
53.5
47.7
37.7
30.9
56.9
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
67.2
61.4
58.7
67.7
63.2
65.0
62.8
65.0
62.8
67.2
61.4
58.7
67.7
63.2
65.0
62.8
65.0
62.8
69.1
67.7
61.4
69.8
65.9
72.9
65.5
72.9
65.5
68.8
68.1
54.8
71.4
59.3
76.3
58.9
76.3
58.9
65.6
64.9
52.1
69.5
56.6
68.6
56.2
68.6
56.2
61.5
60.6
52.8
63.3
57.3
66.8
56.9
66.8
56.9
59.8
57.8
47.0
60.2
51.5
64.7
51.1
64.7
51.1
57.2
53.7
37.0
55.4
41.5
60.0
41.1
60.0
41.1
50.8
49.2
30.2
50.0
34.7
57.3
34.3
57.3
34.3
68.1
66.8
56.2
70.2
60.7
73.1
60.3
73.1
60.3
Tab. 6d --- C version, Grille and Constant top frontal flow configurations
MODEL
S06GC
Mode
Level
31.5
63
125
250
500
1000
2000
4000
8000
Sound
Level
[dB(A)]
(1)
SPL
59.1
59.1
63.3
58.7
57.6
52.6
48.8
42.2
32.5
58.7
(4)
PWL
63.7
63.7
65.5
65.2
62.0
58.0
56.2
53.7
48.3
64.5
LEGENDA
The sound levels global and for each octave band are expressed in dB with a tolerance of ( ---0/+2) dB.
(1) At 2 m in front of the unit and 1 m height, in free field conditions (20 Pa for Under, 50 Pa for Over and 0 Pa for Displacement available
external static pressure).
(4) On discharge side.
Level
SPL sound pressure level
PWLsound power level
6 --- 2
Mode
Level
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
(1)
(4)
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
SPL
PWL
31.5
63
125
250
500
1000
2000
4000
8000
Sound
Level
[dB(A)]
57.0
47.8
67.7
58.1
64.3
59.4
83.2
73.8
85.3
75.9
88.4
79.0
57.0
47.8
67.7
58.1
64.3
58.4
80.6
66.8
82.7
68.9
85.8
72.0
64.9
46.4
75.6
61.1
72.2
58.3
90.0
67.4
92.1
69.5
95.2
72.6
68.3
50.3
79.0
61.5
75.6
61.9
87.9
70.1
90.0
72.2
93.1
75.3
60.6
46.4
71.3
59.5
67.9
54.0
78.9
59.6
81.0
61.7
84.1
64.8
58.8
43.4
69.5
58.4
66.1
53.9
74.4
52.3
76.5
54.4
79.6
57.5
56.7
42.4
67.4
53.6
64.0
51.6
73.6
54.3
75.7
56.4
78.8
59.5
52.0
35.1
62.7
47.0
59.3
43.8
63.6
44.1
65.7
46.2
68.8
49.3
49.3
32.8
60.0
40.3
56.6
39.3
55.9
36.4
58.0
38.5
61.1
41.6
65.1
49.4
75.8
62.4
72.4
59.2
83.2
64.1
85.3
66.2
88.4
69.3
Mode
Level
(1)
(4)
(1)
(4)
(1)
(4)
SPL
PWL
SPL
PWL
SPL
PWL
31.5
63
125
250
500
1000
2000
4000
8000
Sound
Level
[dB(A)]
54.6
53.3
67.1
67.4
64.1
62.2
54.6
53.3
67.1
62.3
64.1
57.7
62.5
52.8
75.0
66.3
72.0
61.7
65.9
52.6
78.4
61.9
75.4
59.4
58.2
51.0
70.7
60.7
67.7
57.0
56.4
44.8
68.9
59.4
65.9
56.4
54.3
40.6
66.8
53.9
63.8
50.8
49.6
33.0
62.1
47.4
59.1
44.6
45.9
23.8
58.4
43.3
55.4
39.9
62.6
51.4
75.1
63.4
72.1
60.2
LEGENDA
The sound levels global and for each octave band are expressed in dB with a tolerance of (-0/+2) dB.
(1) At 2 m in front of the unit and 1 m height, in free field conditions (20 Pa for Under, 50 Pa for Over and 0 Pa for Displacement available
external static pressure).
(4) On discharge side.
Level
SPL sound pressure level
PWLsound power level
6-3
1 row
2 rows
Dimensions
Free Section
[mm]
[mm]
1 row
Cartridge Number
2 rows
400 x 100
400 x 100
400 x 100
400 x 100
10
400 x 100
11
22
400 x 100
12
24
400 x 100
12
24
400 x 100
16
32
400 x 100
22
44
Tab. 6h - Attenuation in dB
row no.
63
125
15
26
28
27
14
12
27
49
53
49
23
1
2
8000
Pressure drops (Pa) for each module at different air flows (m3/s)
0.2
0.3
0.4
0.5
0.6
1
11
18
26
1m
F
1.5 m
2m
Unit Configuration
Under
Over
Position
Plenum Height
Cartridge Rows
Number
600 mm
-4.0 dB
-7.0 dB
1200 mm
-5.0 dB
-8.0 dB
600 mm
-7.5 dB
-12.0 dB
1200 mm
-9.5 dB
-14.0 dB
6-4
Technical Specifications
TechnicalSpecifications
7-1
Technical Specifications
There an ON-OFF type electronic temperature controller, a safety thermostat with manual reset, a
miniature circuit breaker for short-circuit protection and harness protection from possible
accidental contact.
When electrical heating is installed, the dehumidification system can be also activated and humidity
sensor and indicator provided, if especially ordered (see "humidification and dehumidification
system" for the dehumidification function). Electric heating can be installed combined with hot gas
or hot water heating.
Hot Water Coil (for heating and reheating mode and dehumidification system)
The hot water heating coil is made of copper pipes and aluminium fins, with one row, test pressure
30 bar and includes an exhaust valve. A three-way on-off valve directly driven by the
microprocessor controller is supplied as standard.
A hot water thermostat (provided by the customer) is installed to indicate the presence of hot water
at the correct temperature. When hot water heating is installed, the dehumidification system can also
activated and a humidity sensor and indicator provided, if especially ordered (see "humidification
and dehumidification system" for the dehumidification function).
Tab. 7a - Features of hot water reheat system at nominal airflow
MODELS
U/O C
S06
S08
S11
S15
S18
S29
M44
M55
M66
M77
no.
1
2
2
1
1
1
1
1
m2
0.17
0.15
0.15
0.37
0.37
0.37
0.47
0.47
indoor temp. 24_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
3.1
6.2
7.3
11.3
12.5
13.9
19.3
41.7
water flow
l/s
0.05
0.10
0.12
0.18
0.20
0.23 0.315 0.681
coil side pressure drops
kPa
1
1
1
1
1
1
1
3
total pressure drops
kPa
2
2
2
4
5
3
5
22
indoor temp. 20_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
3.1
6.2
7.3
11.4
12.6
14.1
19.8
42.4
water flow
l/s
0.05
0.10
0.12
0.19
0.21
0.23 0.322 0.692
coil side pressure drops
kPa
1
1
1
1
1
1
1
3
total pressure drops
kPa
2
2
2
5
5
3
5
23
1
1.07
1
1.07
44.2
0.721
4
26
46.3
0.756
4
28
45.0
0.734
4
27
47.1
0.768
4
29
rows
surface
MODELS
UC
rows
surface
L90
L10
L12
L14
L15
L16
no.
1
1
1
1
1
1
m2
0.99
0.99
1.29
1.29
1.29
1.29
indoor temp. 24_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
27.6
28.9
35.6
37.5
38.7
37.7
water flow
l/s
0.450
0.471
0.581
0.611
0.631
0.720
coil side pressure drops
kPa
3
3
6
7
7
7
total pressure drops
kPa
6
6
12
13
14
23
indoor temp. 20_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
27.9
29.3
35.9
38.0
39.1
38.2
water flow
l/s
0.455
0.478
0.586
0.619
0.637
0.623
coil side pressure drops
kPa
3
3
6
7
7
7
total pressure drops
kPa
7
7
12
14
14
23
L18
L20
1
1.75
1
1.75
53.8
0.880
17
49
49.3
0.800
15
42
54.5
0.899
17
50
49.6
0.810
15
42
7-2
Technical Specifications
MODELS
U/O R
M24
M45
M60
rows
surface
no.
1
1
m2
0.45
1.00
indoor temp. 24_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
17.7
39.4
water flow
l/s
0.288
0.643
coil side pressure drops
kPa
1
3
total pressure drops
kPa
5
23
indoor temp. 20_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
17.4
39.8
water flow
l/s
0.283
0.649
coil side pressure drops
kPa
1
3
total pressure drops
kPa
5
24
MODELS
UR
L85
L11
1
1.00
43.7
0.712
3
29
44.3
0.722
3
29
L13
rows
surface
no.
1
1
m2
0.91
1.21
indoor temp. 24_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
24.8
34.3
water flow
l/s
0.403
0.559
coil side pressure drops
kPa
2
6
total pressure drops
kPa
10
22
indoor temp. 20_C, 50% R.H.; water inlet/outlet temperature 80/65_C; chilled water 7/12_C
power (re-heating)
kW
25.1
39.7
water flow
l/s
0.409
0.565
coil side pressure drops
kPa
2
6
total pressure drops
kPa
8
22
1
1.69
48.6
0.793
14
46
49.2
0.802
14
47
7-3
HW + H1
HW + H2
=
HW + H1
Reheating + Heater
Reheating + Heater
Technical Specifications
Tab. 7c - Features of hot water heating system at nominal airflow
MODELS
U/O C
rows
front surface
power (heating)
water flow
coil side pressure drops
total pressure drops
power (heating)
water flow
coil side pressure drops
total pressure drops
S06
M44
M55
M66
M77
no.
1
2
2
1
1
1
1
m2
0.17 0.15 0.15 0.37 0.37 0.37
0.47
indoor temp. 24_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
2.3
4.8
5.6
8.2
9.0
10.0
14.3
l/s
0.04 0.08 0.09 0.13 0.16 0.16
0.234
kPa
1
1
1
1
1
1
1
kPa
2
2
2
3
3
2
3
indoor temp. 20_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
2.6
5.3
6.2
9.4
10.2 11.3
15.9
l/s
0.04 0.09 0.10 0.15 0.17 0.19
0.260
kPa
1
1
1
1
1
1
1
kPa
2
2
2
3
4
2
4
1
0.47
1
1.07
1
1.07
32.8
0.535
2
14
34.3
0.559
2
15
35.1
0.572
2
16
35.8
0.585
2
16
37.5
0.611
3
19
38.4
0.626
3
19
MODELS
UC
rows
front surface
power (heating)
water flow
coil side pressure drops
total pressure drops
power (heating)
water flow
coil side pressure drops
total pressure drops
L90
power (heating)
water flow
coil side pressure drops
total pressure drops
power (heating)
water flow
coil side pressure drops
total pressure drops
power (heating)
water flow
coil side pressure drops
total pressure drops
power (heating)
water flow
coil side pressure drops
total pressure drops
L10
M24
S15
L12
S18
S29
L14
L15
M45
no.
1
1
m2
0.45
1.00
indoor temp. 24_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
13.7
31.9
l/s
0.223
0.508
kPa
1
2
kPa
3
15
indoor temp. 20_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
15.3
34.1
l/s
0.249
0.508
kPa
1
2
kPa
4
18
MODELS
UR
rows
front surface
S11
no.
1
1
1
1
1
m2
0.99
0.99
1.29
1.29
1.29
indoor temp. 24_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
21.6
22.5
27.7
28.7
29.3
l/s
0.353
0.367
0.452
0.467
0.477
kPa
2
2
4
4
4
kPa
4
4
7
8
8
indoor temp. 20_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
23.6
24.6
30.2
31.2
31.9
l/s
0.385
0.401
0.493
0.509
0.520
kPa
2
3
5
5
5
kPa
5
6
9
9
10
MODELS
U/O R
rows
front surface
S08
L85
L11
no.
1
1
m2
0.91
1.21
indoor temp. 24_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
19.4
27.4
l/s
0.316
0.446
kPa
2
4
kPa
7
14
indoor temp. 20_C, 50% R.H. water inlet/outlet temperature 80/65_C
kW
21.2
29.9
l/s
0.345
0.487
kPa
2
4
kPa
8
16
L16
L18
L20
1
1.29
1
1.75
1
1.75
28.8
0.470
4
13
41.4
0.680
11
30
37.3
0.610
9
24
31.4
0.510
5
16
45.1
0.740
12
35
40.6
0.660
10
28
M60
1
1.00
34.3
0.558
2
18
37.5
0.611
3
22
L13
1
1.69
39.2
0.638
10
31
42.7
0.695
11
35
7-4
Technical Specifications
Electric board
The electric board is housed in the front part in a space insulated against the air
flow and protected by a plastic crankcase, so as to avoid tampering by
non-authorized personnel and to protect the electric board parts supplied with
a voltage higher than 24 V.
The electric board complies with the norm 204-1 IEC.
The air conditioners have been provided for operating at 400 V/3/50 Hz+N+G (as alternative
execution, the version with 230V/3/50Hz + G can be supplied in the majority of cases).
Magnetothermal switches are supplied as protection of every electric component. A single-phase
transformer has been provided for supplying power to the secondary circuit at 24 V.
A main switch with door-locking handle is installed in series on the safety crankcase to prevent it
from being removed when the switch is in the operating position.
There will be an automatic start-up after a possible stop due to power supply lack.
Additional terminals for remote start-up and carry of some operating conditions (fans and
compressors) or connection of additional devices (Liquistat, Firestat, Smokestat, clogged filters) are
set in series on the terminal board of the electric board. On the terminal board there is also a clean
contact for the remote signalling of the general alarm.
Control system
Very simple user interface.
Immediately intelligible utilization of the control unit system with
LCD.
Net connectivity of several units.
Possible utilization of the iCom CDL with graphic display.
Fig. 7
7-5
iCom Medium
Filter section
Standard filters
Filter section
Removable filters installed inside the unit before of fan and heat
exchanger.
Filtration from G4 to F5 (CN EN779 --- respectively corresponding
to EU4 and EU5 accoding to Eurovent EU4/5).
The folded structure of the filters gives high filtration efficiency and
low pressure drop.
The filter media used consists of synthetic fibre cells. The frame is
made of cardboard.
The additional pressure drop in comparison with G4 sdt filters are
indicated in Tab. 8c.
Eurovent 4/9
EN 779
EN 1882
[less than]
EU1
EU2
EU3
EU4
EU5
EU6
EU7
EU8
EU9
G1
G2
G3
G4
F5
F6
F7
F8
F9
60%
65%
80%
90%
95%
99%
99%
99%
99%
65%
80%
90%
95%
98%
*
**
[less than]
20%
20%
20%
20%
40%
60%
80%
90%
95%
30%
60%
80%
90%
95%
Minimum Efficiency
Reporting Value
[ASHRAE 52.2---1999]
1--- 4
4
5
6--- 7--- 8
8--- 9--- 10
10--- 11--- 12--- 13
13--- 14
14--- 15
15
Achieved filtering performance in accordance to gravimetric test method on a specific sample of dust.
Achieved filtering performance in accordance to a light transmission test methods, with natural atmospheric dust.
8 --- 1
Filter section
Tab. 8b --- Approximate efficiency versus particle size for typical air filters
EFFICIENCY %
HPM S08-11
p F5
140
100
130
90
120
80
110
100
70
90
50
80
Pa
Pa
60
Sxx U/D
60
40
50
40
30
Sxx O/G/K/L
30
20
Sxx O/K
20
10
10
0
800
Sxx U/D
70
0
1650
900
1000
1100
1200
1300
1400
1500
1600
1850
2050
2250
2450
1700
2650
2850
3050
3250
m3/h
m3/h
HPM M44 UC
M24 UR
F5 filter pressure drop
200
180
190
180
170
170
160
160
150
150
130
Pa
Pa
140
120
140
110
130
100
90
120
80
70
3600
4100
4600
5100
5600
6100
m 3/h
8 --- 2
6600
7100
7600
8100
8600
110
5700
5950
6200
6450
6700
6950
7200
7450
7700
7950
8200
m 3/h
Filter section
HPM M55-66-77 OC
M45-60 OR
F5 filter pressure drop
HPM M55-66-77 UC
M45-60 UR
F5 filter pressure drop
160
170
150
160
140
150
130
140
Pa
Pa
120
110
130
120
100
90
110
80
100
70
8300
9300
10300
11300
12300
13300
90
8300
14300
m 3/h
10300
11300
12300
13300
14300
m 3/h
190
9300
190
180
180
F5
F5
170
170
Pa
160
Pa
160
150
150
140
140
130
120
130
19000
21000
23000
m 3/h
25000
27000
16000
17000
18000
19000
20000
21000
m 3/h
190
[Pa]
180
HPM L18-20 UC
L13 UR
F5
170
160
150
140
130
28000
30000
32000
34000
[m /h]
36000
130
160
110
140
Pa
Pa
90
120
100
70
80
50
30
1000
60
3000
3500
4000
4500
5000
5500
6000
6500
7000
1250
1500
1750
2000
2250
2500
2750
m /h
m /h
8 --- 3
Filter section
Tab. 8e --- Additional pressure drop Filters F7
HPM S06-08-11 U/OC
P F7
160
200
140
180
120
Pa
160
Pa
100
140
120
80
100
60
80
40
900
1100
1300
1500
1700
1900
2100
2300
2500
2700
60
3000
m /h
3500
4000
4500
5000
m /h
5500
6000
6500
7000
190
200
170
150
180
160
110
Pa
Pa
130
90
140
70
50
120
30
700
900
1100
1300
1500
1700
1900
2100
2300
2500
2700
100
m /h
3600
4000
4400
4800
5200
5600
6000
m /h
200
F7
220
[Pa
180
HPM L18-20 UC
L13 UR
200
F7
F6
160
F6
180
Pa
140
160
120
140
100
19000
21000
23000
25000
27000
120
28000
30000
32000
34000
36000
3
[m /h]
m 3/h
180
200
190
170
F9
F9
180
160
170
150
160
F7
140
130
Pa
Pa
F7
150
140
F6
120
F6
130
120
110
110
100
100
90
90
80
80
70
70
5700
8 --- 4
5950
6200
6450
6700
6950
7200
m3/h
7450
7700
7950
8200
60
8300
9300
10300
11300 m 3/h
12300
13300
14300
Filter section
HPM L90
L90 ----L10
UC
Himod
L10UC
L85 UR
240
F9
220
F7
200
Pa
180
F6
160
140
120
16000
17000
18000
19000
20000
21000
m 3/h
8 --- 5
Microprocessor Controls
MicroprocessorControls
iCom Control
Fig. 9.a
Liebert HPM models are controlled by iCom
Medium (Fig. 9.a).
The Main Board is housed in the electrical
panel and it is connected to the remote
display, to be installed in the container/room
(connection cable is included).
D The user interface is the 3-digit back-lit display showing
parameter values and relevant symbols/codes in a tree
menu. It features navigation push-buttons and status
leds.
D Both high and low priority alarms activate a visual
indicator and buzzer.
D Input for Remote On-Off and volt-free contacts for
simple remote monitoring of low and high priority alarms:
high/low room temperature, high/low refrigerant
pressure, fan/control failure are available.
D LAN management: functions provided as standard include stand-by (in case of failure or
overload of the unit in operation, the second one starts automatically), automatic rotation, and
cascade (division of the load among several units, through split of the proportional band).
D All settings are protected through a 3-Level password system.
D Automatic restart is provided after a power failure.
9-1
iCom Medium
4Mbit + 512kbit
32Mbit
128Mbit
Coldfire 32Mbit
3 x 0-10V,0-5V,4..20mA (selectable) + 2 PTC/NTC + 3 NTC
9 x opto-coupled
2 x 0-10V
7 triacs output and 2 relay output
2 RJ45 sockets (for unit in LAN, remote display)
1 RJ45 socket
2 RJ12 sockets
1 RJ9 socket for RS485 (direct connection to proprietary supervision)
Microprocessor Controls
CDL Graphic Display (option)
Featuring a 24h graphic record of controlled parameters as well as
the last 200 events occurred. A back-up battery keeps the data
stored in the memory (graphic data record, alarms).
D Large graphic display (320 x 240 pixel)
D System Window: system operation status at a glance
D Self-explanatory Icons: they are used for the Menu-Layout of
the CDL iCom
D Online Help: Every single parameter has its own multi-page
explanation (Evolution)
D Status Report of the latest 200 event-messages of the
unit/system
D Four different Graphic Data Records (Evolution)
D Timer Mode (electronic timer included in the Software)
D Semi or Full Manual Mode software management including all safety devices
D 4-Level Passwords system to protect all the settings
D Ergonomic design for use also as portable device (start-up and "flying connections" by service
personnel)
D Multi-language menu with on-the-fly language selection
9-2
10
Humidair humidifier
Humidairhumidifier
Humidification
The humidification system is provided by a HUMIDAIR electronic humidifier. The
dehumidification function, which is supplied as standard when the humidifier option is installed,
acts by reducing the fan speed with consequent reduction of the air flow and at the same time
completely opening the chilled water three-way valve.
Humidifier features
The steam is mixed with the delivery air of the evaporating coil by means of a suitable distributor.
The iCom Control controller can determine when the cylinder has to be changed. Replacing the
cylinder is extremely easy and quick. A self-adaptive flow control system is fitted as standard and
controls the current passing through the cylinder water.
10 - 1
Humidair humidifier
Tab. 10a - Humidair specifications
MAX.
CYLINDER
WATER
VOLUME
MAX.
SUPPLY WATER
QUANTITY
MAX. DRAIN
WATER
QUANTITY
[kW]
[l]
[l/min.]
[l/min.]
1.5
1.7
0.6
4.0
4.6
3.0
3.3
0.6
4.0
1.3...4.5
8.0
3.0
3.3
0.6
4.0
2.7...9.0
9.0
5.8
5.5
0.6
4.0
KUECLE
2.7...9.0
15.6
5.8
5.5
0.6
4.0
M55...77
M45-60R
KUECLD
3.9...13.0
13.0
9.0
5.5
0.6
4.0
M55...77
M45-60R
KUECLE
3.9...13.0
22.5
9.0
5.5
0.6
4.0
L90...20
L85-11-13R
KUECLD
3.9...13.0
13.0
9.0
5.5
0.6
4.0
L90...20
KUECLE
3.9...13.0
22.5
9.0
5.5
0.6
4.0
ABSORBED
CURRENT
POWER
MAX. CYLIN
DER WATER
VOLUME
MAX. SUPPLY
WATER
QUANTITY
MAX. DRAIN
WATER
QUANTITY
ABSORBED
CURRENT
POWER
[kg/h] *
[A]
0.6...2.0
6.5
1.3...4.5
KUECLD
S15...29
M44
M24R
SETTING
HPM MODEL
HUMIDAIR
MODEL
MAIN POWER
SUPPLIES
(V 10%)
S06
KUECLA
S08...11
KUECLB
S08...11
KUECLC
S15...29
M44
M24R
HUMIDAIR
MODEL
MAIN POWER
SUPPLIES
(V 10%)
SETTING
[kg/h] *
[A]
[kW]
[l]
[l/min.]
[l/min.]
S06 D
KUECLA
0.6...2.0
6.5
1.5
1.7
0.6
4.0
S08...11 D
KUECLB
1.3...2.0
2.0
1.3
3.3
0.6
4.0
S08...11 D
KUECLC
1.3...2.0
3.6
1.3
3.3
0.6
4.0
S15...29 D
M44 D
KUECLD
2.7...4.5
4.6
3.0
5.5
0.6
4.0
S15...29 D
M44 D
KUECLE
2.7...4.5
8.0
3.0
5.5
0.6
4.0
For humidifier current (FLA) and rated power refer to electrical features in air conditioner manual.
(*) Unit is factory-set to produce about 70% of the maximum value (see iCom Control manual).
10 - 2
11
1950
1950
1950
Plenum
1950
1950
200
200
200
Base module
Models
A (mm)
S06C
S08-11C
S15-18-29C
M24R, M44C
M45-60R, M55-66-77C
L85-11R,
L90-10-12-14-15C
400
11 - 1
Plenum simple
500
750
-
600-900-1200
500-600-700800-900
600
600-900-1200
600-700-800-900
1950
2150
Plenum
2150
Models
Plenum simple
L16C
600-900-1200
600-700-800-900
L13R, L18-20C
600-900
600-900
600-900
11 - 2
11 - 3
MODELS
S06C
S08C
S11C
S15C
S18C
S29C
M44C
M55C
M66C
M77C
L90C
L10C
L12C
L14C
L15C
L16C
L18C
L20C
WEIGHTS (kg)
135
150
165
190
210
230
330
480
550
600
620
630
830
840
850
940
1000
1085
M24R
335
M45R
540
M60R
610
L85R
640
L11R
865
L13R
1020
Silencing cartridges
Horizontal input/output
grille
OR
High efficiency filters
Extension hood
Base frame
Fig. 11.k
Fig. 11.l
11 - 4
Fig. 11.n
WALL
BASE FRAME
ACCESSORY
FRONT
UNIT
D
E
FRONT UNIT
MODELS
S06C
S08-11C
S15-18-29C
M24R-44C
M45R-55C
60R-66C-77C
11 - 5
without
base frame
with base
frame
690
750
930
1000
1680
1750
L85R-90C
10C
1960
2050
L11R-12C
14C-15C
2460
2550
L13R-18C
20C
3260
3350
without
base frame
with base
frame
320
390
420
490
670
740
without
base frame
with base
frame
F
380
740
480
730
990
770
840
50
805
10
300
500
1740
800
2040
895
2540
805
830
895
885
3340
The air conditioners are usually packed on a wooden pallet (1), with shockproof angle pieces in
pressed cardboard (2, 3, 4)/polystyrene (5), panels in cardboard (6)/polystyrene (7) and flexible
polythene film (8).
Tab. 11b - Packing depth (A)
MODELS
S06C
S08-11C
S15-18-29C
M24R-44C
M45R-55C-60R-66C-77C
L85R-90C-10C
L11R-12C-14C-15C
L16C
L13R-18C
L20C
Dimensions (mm)
A
480
830
2080
580
830
2080
830
830
2080
930
1080
2110
930
1830
2110
970
2130
2110
970
2630
2110
970
2630
2310
970
3430
2110
970
3430
2310
11 - 6
no. 4 holes O 48
HF
HD
OCW
ICW
400
EC CD
+OHW
OHW
(over)
IHW
(under)
130
215
215
(under)
70
55
55
55
310
90
590
115
75
85
750
UNIT FRONT
Unit Connection
ICW
OCW
IHW
OHW
CD
HF
HD
EC
11 - 7
Dimensions
Rp
Rp
200
OD 16 mm
OD 16 mm
ID 20 mm
ID 22 mm
Hole O 48 mm
200
180
420
70
150
IHW
OHW
500
265
no. 4 holes O 48
EC CD HF HD
ICW
165
175
OCW
70
55
55
55
260
140
115
750
UNIT FRONT
Unit Connection
ICW
OCW
IHW
OHW
CD
HF
HD
EC
Dimensions
Rp
Rp
200
OD 16 mm
OD 16 mm
ID 20 mm
ID 22 mm
Hole O 48 mm
200
11 - 8
(over)
IHW
(over)
750
OHW
no. 4 holes O 48
OCW
ICW
EC CD HF HD
300
OHW IHW
165
120
250
(under) (under)
50
70
55
55
55
295
120
115
100
750
UNIT FRONT
Unit Connection
ICW
OCW
IHW
OHW
CD
HF
HD
EC
11 - 9
Dimensions
Rp 1
Rp 1
200
OD 18 mm
OD 18 mm
ID 20 mm
ID 22 mm
Hole O 48 mm
200
850
850
CD
705
no. 4 holes O 48
OCW
330
HF
ICW
344
IHW
280
300
264
HD
190
OHW
150
EC
80
0
70
230
100
480
180
432
620
662
755
1000
Precut holes
UNIT FRONT
Unit Connection
ICW
OCW
IHW
OHW
CD
HF
HD
EC
Dimensions
Rp 1
Rp 1
260
OD 18 mm
OD 18 mm
ID 20 mm
ID 22 mm
Hole O 48 mm
260
11 - 10
Double Circuit
850
850
CD
705
no. 4 holes O 48
OCW1 ICW1
330
HF
344
IHW
280
300
264
HD
190
OHW
150
223
187
OCW2 ICW2
EC
80
0
70
100
230
180
480
620
432
662
755
1000
Precut holes
UNIT FRONT
ICW 1
OCW 1
ICW 2
OCW 2
IHW
OHW
CD
HF
HD
EC
11 - 11
Unit Connection
Chilled water inlet 1 ISO 7/1
Chilled water outlet 1 ISO 7/1
Chilled water inlet 2 ISO 7/1
Chilled water outlet 2 ISO 7/1
Hot water inlet (opt.)
Hot water outlet (opt.)
Condensate drain
Humidifier feed (opt.) ISO 7/1
Humidifier drain (opt.)
Electrical power supply
Dimensions
Rp 1
Rp 1
Rp 1
Rp 1
OD 18 mm
OD 18 mm
ID 20 mm
R
ID 22 mm
Hole O 48 mm
1650 1750
1710
850
CD
705
no. 5 holes O 48
330
HF
280
IHW
293
OCW
HD
190
150
ICW
230
OHW
150
EC
70
0
0
0
70
100 180
800 870
1430
1750
Precut holes
UNIT FRONT
Models
Unit Connection
Dimensions
Rp 1
Rp 1
Rp 1
Rp 1
110
OD 22 mm
OHW
OD 22 mm
Mxx
CD
Condensate drain
ID 20 mm
Mxx
HF
Mxx
HD
ID 22 mm
Mxx
EC
Hole O 48 mm
M55
ICW
M66-77
ICW
M55
OCW
M66-77
OCW
Mxx
IHW
Mxx
110
110
110
11 - 12
Double Circuit
1650 1750
1710
850
CD
705
no. 5 holes O 48
HF
280
OCW1
IHW
ICW1
293
HD
190
150
230
OHW
150
EC
70
0
0
0
70
100 180
800 870
555
695
1430
1750
Precut holes
UNIT FRONT
ICW 2
OCW 2
Dimensions
Rp 1
Rp 1
Rp 1
Rp 1
Unit Connection
ICW 1
OCW 1
IHW
OD 22 mm
OHW
OD 22 mm
CD
Condensate drain
ID 20 mm
HF
HD
ID 22 mm
EC
Hole O 48 mm
11 - 13
890
Wire mesh
safety
screen (*)
IHW
60
115
CD
EC
CD in addition for
L18-20 only
185
685
80
CD
99
OHW
109
80
119
94
HD/HF
140
OCW
ICW
60
75
675
60
2050 (L 9010)
2550 (L 12141516)
3350 (L 1820)
UNIT FRONT
(*)
This must be cut in order to allow access for the pipes and cables
Models
Unit Connection
Dimensions
R2
R2
R2
R2
200
OD 22 mm
OD 22 mm
CD
ID 20 mm
Lxx
HF
Lxx
HD
ID 22 mm
Lxx
EC
Hole O 80 mm
L90-10
ICW
L12...20
ICW
L90-10
OCW
L12...20
OCW
Lxx
IHW
Lxx
OHW
Lxx
200
350
350
11 - 14
Double Circuit
115
890
185
OCW 2
CD
CD in addition for
L13 only
185
685
80
119
OHW
EC
60
240
HD/HF
CD
115
IHW
OCW 1
109
80
119
94
ICW 1
ICW 2
100
Wire mesh
safety
screen (*)
60
75
675 (L85)
60
750 (L1113)
2050 (L85)
2550 (L11)
3350 (L13)
UNIT FRONT
(*)
This must be cut in order to allow access for the pipes and cables
Models
11 - 15
Unit Connection
L85-11
ICW 1
L13
ICW 1
L85-11
OCW 1
L13
OCW 1
L85-11
ICW 2
L13
ICW 2
L85-11
OCW 2
L13
OCW 2
Dimensions
R2
R2
R2
R2
R2
R2
R2
R2
OD 22 mm
HD
EC
Hole O 80 mm
Lxx
IHW
Lxx
OHW
Lxx
CD
Lxx
HF
Lxx
Lxx
OD 22 mm
ID 20 mm
R
ID 22 mm
12
Special Cartridges
See Chap. 7
Humidifier
See Chap. 10
Base modules
See Chap. 11
Base frames
See Chap. 11
Special packing
See Chap. 11
12 - 1
[l/s]
0.083
0.167
0.250
0.333
[kPa]
20
19
18
14
12 - 2
13
Hydraulic Circuits
HydraulicCircuits
Fig. 13.1 -
SUPPLY LIMIT
SUPPLY LIMIT
POS.
Components
POS.
Components
13 - 1
Hydraulic Circuits
Fig. 13.2 -
5
1
5
5
1
SUPPLY LIMIT
4
SUPPLY LIMIT
HOT WATER OUTLET
POS.
Components
POS.
Components
13 - 2
Hydraulic Circuits
Fig. 13.3 -
5
1
5
5
1
AB
6
AB
6
SUPPLY LIMIT
SUPPLY LIMIT
HOT WATER OUTLET
POS.
Components
POS.
Components
Calibrated orifice
13 - 3
Double Circuit
Hydraulic Circuits
Fig. 13.4 -
1
5
3
SUPPLY LIMIT
A
B
2
AB
A
B
AB
4
CHILLED WATER OUTLET
SUPPLY LIMIT
POS.
Components
POS.
Components
13 - 4
Double Circuit
Hydraulic Circuits
Fig. 13.5 -
1
3
SUPPLY LIMIT
A
2
B
CHILLED WATER INLET
AB
A
B
AB
4
CHILLED WATER OUTLET
SUPPLY LIMIT
6
HOT WATER INTET
POS.
Components
POS.
Components
13 - 5
The Manufacturer hereby declares that this product conforms to the European Union directives:
Le Fabricant dclare que ce produit est conforme aux directives Europennes:
El Fabricante declara que este producto es conforme a las directivas Europeas:
O Fabricante declara que este produto est em conformidade com as directivas Europeias:
Tillverkare frskrar hrmed att denna produkt verensstmmer med Europeiska Uniones direktiv:
De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is:
tten,
ett tm tuote tytt seuraavien EU--- direktiivien vaatimukset:
Since the Liebert HIROSSVaimistaja
Companyvakuuttaa
has a policy
of continuous
product improvement, it reserves
the erklrer
right to change
Produsent
herveddesign
at detteand
produktet er i samsvar med EU--- direktiver:
specifications without previous notice.
Fabrikant erklrer herved, at dette produkt opfylder kravene i EU direktiverne:
j m m m j j j ..:
Issued by T.D.Service
Der Hersteller erklrt hiermit, dass dieses Produkt den Anforderungen der Europischen Richtlinien gerecht wird:
Locations
Emerson Network Power - Headquarters EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 5841 257
marketing.emea@emersonnetworkpower.com
Emerson Network Power - Service EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 9719 045
service.emea@emersonnetworkpower.com
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Tel: +1 6148880246
Asia
29/F The Orient Square Building
F. Ortigas Jr. Road, Ortigas Centre
Pasig City 1605 Philippines
Tel: +63 2 620 3600
Fax: +63 2 730 9572
Embedded Computing
Outside Plant
Connectivity
Embedded Power
Services
DC Power
Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power Iogo are trademarks and service marks of Emerson Electric Co. 2008 Emerson Electric Co.