Generator Stability Example (1)

Assume AB power system has equivalent H constant of 2000MJ/MVA at the base value
of S=100MVA. The system frequency deviation from 60Hz should be within 0.5Hz. AB
is also importing power from BC. Considering the possibility of losing the import power,
estimate the maximum import power from BC if the AB generators can not response
within 5 seconds.

Generator Stability Example (2)


The generator in the single line diagram below is initially operating in steady state
condition and delivering 0.9 per unit real power at 1.08 per unit terminal voltage when
circuit breaker B12 inadvertently opens. Use the equal area criterion to calculate the
maximum value of the generator power angle . Assume pu =1 in the swing equation.

B12

XTR = 0.1

X12 = 0.2

X23 = 0.2

X13 = 0.1
Xd = 0.3

B21

B11
B13

B22
3

Vbus = 1pu