ASHRAE 62-89 Analysis
Part Ill: Indoor Air Quality Procedure
ASHRAE Standard 62-89, Ventiatior
‘Standard for Acceptable indoor Ai
Quality, is widely viewed a8 the
minimum ventiaton stand to be met,
93 ‘cores. This isthe
wd of throe Engingers Newsletters
that attempt to interpret the standard
and offer suggestions for cmp
The purpose of ASHRAE Standard 62:
89 isto specify minimum ventilation
rates and define acceptable indoor air
‘quality 1o avoid adverse health effects
jo accompish this, the standard
presents a series of general
requirements for systems and
equipment Section 5.) then offers two
ternative procedures for providing
acceptable indoor air quaity (Section
80), The following analysis presented
to help designers and installers inorpre
the standord's diverse requirements, and
's based on our best judgment of the
‘meaning and purpose of the various
provisions. URimate responsibilty for
interpretation compliance, however,
rests with the individual designer and
installer
Section 50, Systems and Equipment,
and Section 6 1, Ventilation ate
Procedkire, were the subjects of
evious Engineers Newsletters, Section
2, Indoor Air Qualty Procedure, and
Section 6:3, Design Documentation
Procedures, are discussed in 1h issue
General Terms
Requirements (denoted by shall and
must) and suggestions (signaled by use
of the words should and may) are
presented throughout the standara
Conformance with the standard can onty
be claimed if all requrememts are met,
On the surface, it seems that
suggestions need nat be met for
compliance. However, ignoring
suggestions may not be prudent After
all, these suggestions retlect the
consensus of experis in the HVAC
industry and might, therefore, be viewed
as the minimum citer a prudent
designer would folow when designing a
vontiation system,
TON zee
ASHRAE 62-69 makes several
references to occupied space and
‘occupied zane, Within this discussion
the cocupied space refers to all
inhabited areas... usualy rooms.
within the bulging, The occupied zone
on the other hand, refers to a defined
region within the accupied space,
between planes 3 and 72 inches
‘above the floor and more than 2 feet
from the walls
The terms outdoor air and ventiation
2ir ae often used interchangeably.
However, as used here, autdoor ari
air from outside the buldng, whie
ventilation air isthe portion of supply ait
Used to maintain acceptable indoor ait
quality. Ventilation ar may be either
entiely outdoor air or a mixture o
outdoor air and cleaned, ececulated air
49}}0;]SmeyN SisoulBUuFigure 1: Typical Airflows for a Two-Space System
Outdoor ‘Supply
‘Supply = Outdoor + Rectculated
Recireulated a
Leakage
Central
Exhaust Rew Occupied
Space
y
4 Prim
< |
| i I
Local E Lace Local
Exhaust Makoup Exhaust
< o cup
Tote, FT Be
e
Exfitration Lr
Primary air the supply air delivered to Mote specifically, the Indoor Air Qualty
each occupied space For want of a Procedure sets concentration lit for
betor term, acta iris the amount of 10 contaminants, proscrbes subjective
primary ar that actualy reeches te analyst determina acceptabe odor e
Sccuped zone wun the occupied levels, and describes the use of tested
space. Bypass aris the portion at recicalated ait reduce the minimum
primary a that never reaches the outdoor aio rates presented in the
fSecipied zone Figure states Sanda
soveral of those defintons.
Key points presented in Section 6.2 are
Analysis of Section 6.2: arranged by topic and discussed below
Indoor Air Quality Procedure in a question-and answer format
To review, the Ventilation Rate
Procedure Section 61) presents Determining Indoor Air Quality
‘one way to achieve acceptable
indoor air qualty’; namely. supplying
leach occupied space with ventlation ait What contaminants are specified by the
of specific qualty and quantity. Outdoor standard, and what are the acceptable,
air usad to diste anticipated ‘concentraton levels of each? See
Contaminants to acceptable Figure 2
concentration levels
“Table 1 furnishes information on
In contrast, the Indoor Ait Quality acceptable contaminant levels in outéoor
Procedure (621 presents "an air {andl} also applies indoors for the
‘ternative performance method... for ‘same exposure times” (Section 6.2 1)
achieving acceptable air quality" by
‘quantitatively describing aoceptable “Table 3 contains lis for four other
indoor air quality It sets ints on the indaor contaminants” (Section 62.1)
‘concentration of known and specifiable
contaminants in an effort to achiave
acceptable indoor air qualiy in the
‘cccupied zone in a more direct way
than the Ventiation Rate Procedure ryTables 1 and 3 of the standard ist 11
acceptable indoor concentration levels
for 10.contaminants, presented hore in
Figure 2. By reference to the limits in
these tables, the indoor concentration of
the listed contaminants is required to be
bboiow the level sted
If concentration levels in Tables 1 and 3
(defined primaiy in Table C-1 and C-3)
‘are maintained, is the indoor ar quay
‘acceptabie? No, not necessanly
“Tables C-1 and C-3 do no inciude af
known contarnnanis that may be of
fsancern, and these concentration limits
may not, ipso facto, ensure acceptable
indoor air qualty with respect to other
omaminants” Section 62.1),
“To a certain extent, this observation
luncavels the indoor Air Qualty
Procedure as the performance-based
path to acceptable indoor air qual. It
implies that, even i the known and.
speciiable contaminants isted are
controled to the established
Concentration levels, indoor air quality
sbll may not be satistactary, In other
words, ifthe building system is designed
0 that listed concentration levels are
‘ot exceeded, acceptable indoor air
‘quality isnot assured, The building
‘designer has no clear, indisputable
{efintion of acceptable indoor air
‘quality, Acceptable IAQ is determined
by the contaminant loves listed, as well
138 by unknown levels of unknown
‘contaminants. Consequently, many
‘designers choose to use the Ventilation
Rate Procedure in which the
requirements are dearer and
‘compliance to those requirements is
more easily dernonstrated.
Figure 2: Summary of Tables 1 and 3
~ indoor Air Guay Standards
= ‘Acceptable Exposure
Long-Term Short-Term
ASHRAE
Contaminant Concenation | time | Concentration | Time | “able
gin] ppm | yeas | uaim® Tppm [hows |
Gaon Diode fraeio 1000) Con a
Caton Monoxide USA) aoooo] seo] 7 J
Catbon Monoxie USA) o000[ 900[ 8 [1
Chiordane (maximum) | 00006) Cont a
[ead 15] 025. i
Nivogen Dowd coo] 0085] 1.00 1
Onidants (ozone, USA wl oa] 7 [4
‘Ozone 1000] 005] Cone [3
Partevlie fora USA | 500) 1.00766] waft
Radon 4p.ci_| 100 Tf 3
Suifur Dowde USA | 800 | 0080, 100 ses oval pe [1Ifthe carbon dioxide concentration is
‘maintained below 1000 ppr, has
acceptable indoor ar quality been
achieved? No. To avoid unacceptable
‘dors, a carbon dioxide concentration
bbelow 1000 ppm is recommended,
“Carbon dioxide has been widely used
1 an indicator af indoor air qualy. A
limit of 1000 ppm CO; is recommended
‘0 satisfy comfort (odor criteria" Section
621)
While it observes that COp
‘measurements have been used t0
Incate acceptable ar quality, the
Standard does not require or suggest
that CO, concentration be used to
contra! ventilation rate. However, t does
recommend (or observe) that CO;
‘concentrations below 1000 pom are
likely to be accompanied by acceptable
‘cir levels
Can acceptable indoor air quality be
‘maintained by adjusting the outdoor
airflow rate to control the CO,
‘concentration level? No. if duton is nat
Used to control CO, level consideration
ff the concentration level of ether
contaminants i required,
"in the event CO, is controlled by any
‘method other than dilution, the effects
of the possible elevation of other
‘contarminants must be considered”
‘Section 62.1)
To implement the indoor Air Quality
Procedure, some building designers
‘specify measurement and conteol of
CO, concentration in the space. They
use gaseous filtering techmaues to
remove COp and measured CO;
Concentrations to modulate the outdoor
airflow rate Ifthe outdoor airflow rate is
less than the minimum rate specitieg in
Table 2, however, indoor air
Contaminants are no longer diluted as
required by the Ventlation Rate
Procedure. Therefore, the bulding
dosignor must consider that other
contaminant levels may be at high levels
and, presumably, must provide a means,
tw contro the concentration of these
contaminants as wel
Can aecoptable indoor air quality be
determined solely by sensing
contaminant levels? No. The qualty of
indoor air cannot aways be determined
by measuring cantaminant levels,
therefore, subjective evaluation of indoor
ar quality s required.
To some degree, adequacy of contro!
[of complex contaminant mixtures) must
‘est upon subjective evaluation” Section
621)
From the designer's viewpoint, this
requirement weakens the Indoor Ai
‘Qualty Procedure considerably. For
‘complex contaminant mixtures sully
Characterized by odors) the
‘ontarninant-related quaity of indoor at
cannot be measured, It must be
determined subjectively, based on the
ludgment of impartial abservers. The
building designer is required to design a
system that adequately controls
‘contaminants toa level that willbe
judged acceptable in subective
‘evaluation by impartial observers. So, a
positive subjective evaluation is a
system design requirement. But it can
only occur alter system installation and
buileing occupancy. tis unclear how 3
bbuiding can be occupied before the
systein design is completed.
If contaminant levels ara low enough
and @ subjective evaluation judges the
‘air qualty to be acceptabe, is te
building design in compliance wath the
1AQ Procedure? No, not necessarily
“tn the case of some adoviess biological
-a0r0s0'8, subjective evaluation is
inrelevant. Appicatin of generaly
acceptable technalogy, and vigilance
‘regarding adverse influences of reduced
ventiation, must therefore suffice”
(Section 6 21
This requirement further weakens the
Indoor Air Quality Procedure because it
provides litte conerete direction but
‘adds substantaly tothe designer's
‘burden of judgment with its attendant
responsibilty. Some contaminants can
noither be measured quanttatively nor
evaluated subjectvely. The building
signer is required to use acceptable
technology and vigilance when the
‘contaminants cannot be measured or
perceived. What is generally acceptable
technology at any given time? And, in
\what context must the designer be
Vigilant. on the alert... for the
adverse effects of reduced ventilation: In
‘general terms or an a job-by ob basis?
In summary, the Indoor Air Quality
Procedure explains that accopiable
indoor ait quality i determined by tee
criteria
1
Aoceptable concentrations of all known
and speciiable contaminants.
2
‘Acceptable subjective evaluation for a
‘other contaminants whch are not
known and specifable, but which can
bbe detected by impartal observers,
3
Reasonable appication of technology
‘and caution regarding the adverse
impact of reduced ventilation
Again, as a result of this loose definition
of acceptable indoor air quality, many
bulking designers chose the more
Clealy defined Ventilation Rate
ProcedureSubjective 1AQ Evaluation
Is a subjective IAQ evaluation requiced
for campliance via the IAQ Procedure?
Yes. If odor causing contaminants cannot
bbe measured objectively. a subjective
evaluation is required,
"lo the absence of objective means 10
assess the acceptably of such lodor
‘eausingl contaminants, the judgment of
scceptabity must necessarily derive
fom subjective evaluation af impartial
observers” (Sactan 6 22
‘Many odor-causing contaminants cannot
bbe measured in terms of concentration
levels or do not have an estabished
harmful concentration level, Therefore,
a designer using the 1AO Procedure
‘cannot comply with the standard
without @ successful subjective
‘evaluation of the completed system,
's a specific subjective IAQ evaluation
method required? No. A method
described in Appendix Cis suggested,
but not required
“One method that may be used for
‘measuring subjective response is
deseribed in Appendix C” (Section 622
The suggested method states that the
air qualty i acceptable"... 80,
percent of a panel of at least 20
Lniained observers deems the air to be
rot objectionable under representative
‘conditions of use and occupancy.” The
‘ebservations aro intended to detect
offensive odors only,
Ifthe system passes the subjective
evaluation, isthe air quality acceptable?
No.
“Caution should be used in any
subjective evaluation procedure to avoid
unacceptable concentrations of other
contaminants” (Section 62.2)
This suggestion warns the buiing
designer that an acceptable odor level
alone does not indicate satisfactory
indoor air quality. Unacceptable
‘concentrations of adorless contaminants
{such as carbon monoxide and radon!
‘can be present in a space, undetected
by a subjective evaluation for odors.
Air Cleaning
Can cleaned, recirculated air be used to
reduce the minimum outdoor ai rates in
Table 2? Yes, but the INO Procedure
‘must be used to avoid contaminant
‘accumulation in under-diuted spaces.
“Recirculation with ai-cleaning systems
Js also an effective means for contating
Contaminants viben using the Indoor Air
Quality Procedure... cleaned,
recirculated air is used to reduce the
outdoor airflow rate below the values
shown in Table 2, the Air Quaity
Procedure, 62, must be used” (Section
622 and Section 61.32.
To clean aie returning from the occupied
space, recrculate it as ventiaung air
and, thereby, reduce the minimum
outdoor airflow rate listed in Table 2; the
‘designer is required to use the Indoor
Air Quality Procedure. not the
entiation Rate Procedure. Some
contaminants, parteularly gaseous ones,
may not be adequately cleaned from the
recirculated ai stream, These
‘contaminants can accurnulate in the
‘occupied space, eventually reaching
Unacceptable concentration levels
Therefore, the acceptable indoor air
‘quality must be determined using the
IAQ Procedure. To avoid this necessity,
many bulding designers da not speciy
se of recirculated ai-ceaning solely 0
reduee the minimum outdoor airflow
rate
Is there a method for computing the
educed minimum outdoor airflow rate
when recirculated air used? Yes, The
Standard suggests the use of equations
presented in Appendix Eto calculate
reduced outdoor airflow rates.
“The allowable contaminant
‘concentration inthe accupied zone can
be used with the various system models
‘in Appendix Eto compute the required
‘outdoor airflow rate” (Section 62.3)
When applying the INQ Procedure, the
standard allows the building designer 10
use. equations from Append Eto
calculate requiced outdoor airtiow rates.
AA detailed analysis of Appendix E is
another full discussion in itself, tis
important to nate, however, that use of
these equations is not a smple matter
Several key variables are very dificult 10
determine. Far example, the
Contamination rate (polation generation
rate) for chemicals and furnishings
within the space are not readily
available, venation effectweness is
Uifieut to determine without testing and
fiterefficency for gaseous
contaminants may not be known. Also,
the calculations must be repeated for
‘each indivksal contaminant of caneern.5
. Throughout the standard, the building
Can recirculated ai aay be cleaned designe is require to docurnent design
sufficenty tobe used 10 reduce the _sgsumptions,eaculations and $9 on, so
cutdoor aston requrement? No. If any thatthe ventlaton system can be
Contaminant concentrations cannot be gperated and manned propery, AIS
tmainsined to acoeplable levels using awh proper desgn documentation, the
Gieaning and reduced outdoor airlow, impact of future changes tothe system
the desgne is requied 1 use the Table Or ts se, (og, number of conus in
rates the space indoovoudoor contaminant
‘sources, or space area) can be properly
evaluated, resuting ina more accurate
determination of system redesign
contaminants that are not
appreciably reduced by the ar-cleaning
‘system may be the controling facior in
design and prohibit the reduction of ar "4S
‘below that sot by the Ventiation Rate
Procedure” Section 6 2:9 Does the designer simpy record the
design, then file the documents away?
No. The standard suggests that design
‘documentation be delvered, presumably
to the building owner or operator, after
‘system instalation,
‘The building designer must be aware of
the cleansing capabilty of the air
Cleaning syster. Ifthe level ofall
‘contaminants in the occupied space
cannot be reduced to acceptable levels
by air cleaning, te designer must “Design eniteia and assumptions shal!
‘abandon the Indoor Air Quay bbe clocumented and should be made
Procedure and use the Ventilation Rate avaiable for operation ofthe system
Procedure instead within 2 reasonable time after
poe Installation” (Secton 63) e
Design Documentation The building designer must incude
Is the designer required to document design docurmentaion as part of the
‘ventilation related calculations? Yes. information delivered to the bulding
‘Crear docurnentation of the design ‘owner, Normal, transfer ofthe plans
assumptions is required. and specifications for the bulling
ecm
‘and contaminants" (Section 6.1.3.1). 's operated
“Design documentation shal leary
state which assumptions were used in
the design so that te lens of the
system in removing contaminants can
bo evaluated by others before the
systom is operated in a different mode
oF before new sources are introduced
into the space" (Section 60
The building designer must document
building design assumptions,
calculations, selections and so on. This is
design documentation wich isin
‘adoton to the trational buleing plans,
‘equipment schedules and specifications
Good design documentation is requited
te enable future changes to building
‘operation and usage without
Unexpected. and undesirable
indoor ar quality consequences, oFigure 3: Summary of Standard 62:89
TRANE™
Specificaly, what infoemation must be
‘documanted? Documentation
requirements and suggestions are
sprinkled throughout the standard
"Soe Sections 4 and 6, as well as 52
‘and 6.1.3 regarding assumptions that
‘should be detailed inthe
documentation” (Section 6.3)
‘The building designer is roquired or
advised to document the flowing:
Whenever the Ventilation Rate
Procedure is used, the design
documentation should clearly state that
this method was used and that the
design wil need to be reevaluated i at
{a fater time, space use changes eacur or
‘f unusual contaminants or unusually
strong sources of specific contaminants
‘are 10 be introduced into the space”
(Section 42:
“The design documentation shall stato
assumptions that were made in the
‘design with respect 10 ventilation rates
and air cistibuton’” (Section 6.2)
"Design documentation shot clearly
state which assumptions were used in
the design so thatthe imats of the
system i removing contaminants can
‘be evaluated by othors before the
systom is operated ina ctferent mode
(oF before new sources ara introduced
into the space" Section 6.0)
‘Design documentation shal specify all
sSignficant assumptions about occupants
{and contaminants" Section 6.1.3,
‘Summary
Section 62 of ASHRAE 62.89 attempts
to help the building designer by
imparting a method for direct control of
indoor air quaity. Unfortunately, i
presents only a shor lst of acceptable
‘contaminant levels; includes a
requirement fora post-design,
subjective evaluation for adors; and
‘seems fo require ongoing building
system vigilance on the part of the
designer after the buling is
designed and operating,
Inlight of these shortcomings, its our
View that the IAQ Procedure fais to
provide 3 welrdefined, enforceable path
to.complance with the standard. Unt it
is revised, this procedure is not likely to
be widely used by bulding desgners
This concludes our three-part analysis of
ASHRAE 62- 89. An overall summary of
ey requirements and suggestions is
Included in Figure 2
General Requirements
Design for good room air distribution
Document design assumptions and
caleulatons,
Locate outdoor air intakes properly,
Design for easy air system clearing
Provide local exhaust for stationary
Provide makeup air for indoor
combustion
Select fiters property,
Specify sloped drain pans with access
for cleaning
Follow either the Ventilation Rate
Procedure or the IAQ Procedure,
Procedure Requirements
Ventilation Rate Procedure
Evaluate the outdoor air qualty and
treat as necessary,
Provide the minimum outdoor airflow
fates of Table 2.
For muttpie-space systems, use
Equation 6-1 to find minimum outdoor
airlow:
100 Procedure
Control concentration level of 10,
contaminants,
For odors, conduct subjective
‘evaluation aftr building is completed
‘and occupied.
if recirculated air cannot be cleaned
sutficently, use Ventilation Rate
Procedure.
Additional Suggestions
Monitor outdoor aitfow,
Avoid intake of contaminated autdoor
Dehumiity (to ess than 60% RH),
Hurnaiy with steam, if necessary
(to more than 40% RH
Clean the supply air stream,
Use antimicrobial coatings where
appropriate to prevent microbial
growth,
Use the Ventlation Rate Procedure for
ew construction,
Use time-of day scheduling to minimize
ventilation needs.
Consider use ofthe IAQ Procedure for
busting buldings