VERTEX AIR TECHNOLOGIES PRIVATE LIMITED


(Re
definingStandards)

REV : 1
JOB : GLOBION INDIA PVT LTD.
BLOCK: BACTERIAL VACCINE
DATE : 10.09.2019
LOCATION : KARAKAPATLA , HYDERABAD
BASIS OF DESIGN

( FRSH AIR + PRE


CONSIDERED EQUIPMENT LOAD

+ INTERMEDIATE + BLEED AIR )


EQUIPMENT LOAD AS PER DQ

FRESH AIR QUANTITY AS PER

10% EXTRA OVER SUPPLY AIR

RECIRCULATION/ EXHAUST

HOT WATER COIL / HEATER


FRESH AIR QTY INCLUDING
EX FILTRATION AS PER DQ

HEPA POSITION IN ROOMS


DIVERSITY FACTOR AS DQ

IN FILTRATION AS PER DQ
FRESH AIR AS PER AC/Hr
OCCUPANCY AS PER DQ

FRESH AIR CHANGES/ Hr

COOLING COIL / ROWS


REQUIRED ROOM CFM
DESIGN AIR CHANGES
REHEAT AS PER DCPL

SUPPLY AIR BLOWER

AHU SELECTED CFM

RELATIVE HUMIDITY
AS PER HEAT LOAD
DEHUMIDIFIED CFM

FILTRATION LEVEL
STATIC PRESSURE
RETURN AIR CFM
LOCAL EXHAUST

BLOWER MODEL
SUPPLY AIR CFM

BLEED AIR CFM


RESULTANT T.R

AS PER MAC/Hr

TEMPERATURE

CLASS@ REST
OCCUPANCY
ROOM NAME

AS PER DQ

PER HOUR

REMARKS
EXHAUST

BLOWER
VOLUME
LENGTH

REHEAT
HEIGHT

IN AHU
FLOOR

BANKS
WIDTH

AREA
S.NO

AHU

# # # M M M² M M³ NOS KW % KW ACPH CFM CFM CFM CFM CFM CFM T.R KW KW CFM ACPH CFM CFM CFM CFM CFM CFM CFM SYSTEM TYPE MMWC 0
C % µm µm EUGMP CHW /DX HW/ HB -

1 CH-I GF 1.64 1.12 1.8 3.00 5.5 1 0.0 70 0.0 2 6 15 285 0 0 15 0.19 0.25 46 25 81 81 366

2 CH-II GF 1.72 1.12 1.9 3.00 5.8 1 0.0 70 0.0 2 7 15 128 128 0 15 0.19 0.97 48 25 85 85 85
10+5+3+H14 TERMINAL HEATER
AHU-BV-04 2500 RE-CIRCULATION 150 23±2 °C 55±5%
MIC HEPA H14
D CHW/6
BANK
PLUG TYPE
MEDIA WEIGHING &
3 COMPOUNDING
GF 2.84 2.98 8.5 3.00 25.4 2 7.5 70 5.3 2 30 30 128 128 0 30 2.28 0.26 1432 25 374 1432 1432

4 MEDIA STORE GF 2.09 1.42 3.0 3.00 8.9 1 0.0 70 0.0 2 10 15 0 128 0 15 0.22 0.22 73 25 131 131 3

15.2 45.6 5 7.5 5.3 0 75 2.89 0.00 1.70 1600 671 1729 1886 232 1961 2157
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYD OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS
Room. Name CH-I Season Summer DB 106
AHU NO AHU-BV-04 N NE E SE S SW W NW RH 28
WB 78
GLASS 0 0 0 0 0 0 0 0 TH 43.0
WALL 0 0 0 0 0 0 0 0 GR/LB 110.0
PARTITION 0 0 0 0 0 0 0 0

AREA 20 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.15 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.79 WALL 0.35
SH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 54.00 FALSE CEILING 0.2
TR 0.19 FLOOR 0.56
CFM 46

CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB


ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-I OUT SIDE 106 28 78
INSIDE 73 55 62

FLOOR AREA 20
DIFF. 33
VOLUME 194
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 6

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 22 = 0


EAST WALL 0 x 0.35 x 36 = 0
SOUTH WALL 0 x 0.35 x 34 = 0
WEST WALL 0 x 0.35 x 30 = 0
NORTH EAST WALL 0 x 0.34 x 28 = 0
SOUTH EAST WALL 0 x 0.34 x 36 = 0
SOUTH WEST WALL 0 x 0.34 x 32 = 0
NORTH WEST WALL 0 x 0.34 x 24 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 33 = 0
PARTITION 0 x 0.15 x 28 = 0
FLOOR 20 x 0.56 x 28 = 310
FALSE CEILING 20 x 0.2 x 28 = 111
ROOF 0 x 0.15 x 53 = 0
VENTILATION 15 x 33 x 0.054 = 27
PEOPLE 1 x 245 x 1 = 245
LIGHTS 20 x 1.5 x 3.41 = 101
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0.02 x 1 x 3410 = 68
SENSIBLE SUB TOTAL = 862 SENSI. HEAT RATIO
SAFETY = 43
SENSIBLE TOTAL = 905
DEHUMIDIFIED CFM
VENTILATION 15 x 39 x 0.0335 = 20
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 225 REFG. SUB TOTAL
SAFETY = 11 SAFETY
LATENT TOTAL = 236 TOTAL
SENSIBLE TOTAL = 905
TOTAL SPACE HEAT = 1141 TONNAGE
TH GR/LB

43 110
26.8 71

16.2 39

0.79
ADP 54.00

46

1141
1039
2179
109
2288

0.19
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name CH-I Season Monsoon DB 85


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 82
WB 81
GLASS 0 0 0 0 0 0 0 0 TH 47.0
WALL 0 0 0 0 0 0 0 0 GR/LB 166.0
PARTITION 0 0 0 0 0 0 0 0

AREA 20 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 0.7 GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.68 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 50.00 FALSE CEILING 0.2
TR 0.19 FLOOR 0.56
CFM 24
Reheat
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-I OUT SIDE 85 82 81
INSIDE 73 55 62

FLOOR AREA 20
DIFF. 12
VOLUME 194
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 6

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 1 = 0


EAST WALL 0 x 0.35 x 15 = 0
SOUTH WALL 0.00 x 0.35 x 13 = 0
WEST WALL 0 x 0.35 x 9 = 0
NORTH EAST WALL 0 x 0.34 x 7 = 0
SOUTH EAST WALL 0 x 0.34 x 15 = 0
SOUTH WEST WALL 0 x 0.34 x 11 = 0
NORTH WEST WALL 0 x 0.34 x 3 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 12 = 0
PARTITION 0 x 0.15 x 7 = 0
FLOOR 20 x 0.56 x 7 = 77
FALSE CEILING 20 x 0.2 x 7 = 28
ROOF 0 x 0.12 x 32 = 0
VENTILATION 15 x 12 x 0.054 = 10
PEOPLE 1 x 245 x 1 = 245
LIGHTS 20 x 1.5 x 3.41 = 101
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 78
SENSIBLE SUB TOTAL = 539 SENSI. HEAT RATIO
SAFETY = 27
SENSIBLE TOTAL = 566
DEHUMIDIFIED CFM
VENTILATION 15 x 95 x 0.0335 = 48
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 253 REFG. SUB TOTAL
SAFETY = 13 SAFETY
LATENT TOTAL = 265 TOTAL
SENSIBLE TOTAL = 566
TOTAL SPACE HEAT = 832 TONNAGE
TH GR/LB

47 166
26.8 71

20.2 95

SENSI. HEAT RATIO 0.68


ADP 50

DEHUMIDIFIED CFM 24

832
1295
2127
106
2233
0.19
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name CH-I Season Winter DB 55


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 60
WB 48
GLASS 0 0 0 0 0 0 0 0 TH 19.7
WALL 0 0 0 0 0 0 0 0 GR/LB 42.0
PARTITION 0 0 0 0 0 0 0 0

AREA 20 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 0.7 GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.22 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 54.00 FALSE CEILING 0.2
TR -0.02 FLOOR 0.56
CFM 3
Reheat 0
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-I OUT SIDE 55 60 48
INSIDE 73 55 62

FLOOR AREA 20
DIFF. -18
VOLUME 194
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 6

TOTAL CFM 15

NORTH WALL 0 x 0.35 x -29 = 0


EAST WALL 0 x 0.35 x -15 = 0
SOUTH WALL 0.00 x 0.35 x -17 = 0
WEST WALL 0 x 0.35 x -21 = 0
NORTH EAST WALL 0 x 0.34 x -23 = 0
SOUTH EAST WALL 0 x 0.34 x -15 = 0
SOUTH WEST WALL 0 x 0.34 x -19 = 0
NORTH WEST WALL 0 x 0.34 x -27 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x -18 = 0
PARTITION 0 x 0.15 x -23 = 0
FLOOR 20 x 0.56 x -23 = -255
FALSE CEILING 20 x 0.2 x -23 = -91
ROOF 0 x 0.12 x 2 = 0
VENTILATION 15 x -18 x 0.054 = -15
PEOPLE 1 x 245 x 1 = 245
LIGHTS 20 x 1.5 x 3.41 = 101
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 68
SENSIBLE SUB TOTAL = 54 SENSI. HEAT RATIO
SAFETY = 3
SENSIBLE TOTAL = 57
DEHUMIDIFIED CFM
VENTILATION 15 x -29 x 0.0335 = -15
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 190 REFG. SUB TOTAL
SAFETY = 10 SAFETY
LATENT TOTAL = 200 TOTAL
SENSIBLE TOTAL = 57
TOTAL SPACE HEAT = 257 TONNAGE
TH GR/LB

19.66 42
26.8 71

-7.14 -29

SENSI. HEAT RATIO 0.22


ADP 54

DEHUMIDIFIED CFM 3

257
-458
-201
-10
-211

-0.02
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYD OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS
Room. Name CH-II Season Summer DB 106
AHU NO AHU-BV-04 N NE E SE S SW W NW RH 28
WB 78
GLASS 0 0 0 0 0 0 0 0 TH 43.0
WALL 0 0 0 0 0 0 0 0 GR/LB 110.0
PARTITION 0 0 0 0 0 0 0 0

AREA 21 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.15 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.80 WALL 0.35
SH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 54.00 FALSE CEILING 0.2
TR 0.19 FLOOR 0.56
CFM 48

CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB


ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-II OUT SIDE 106 28 78
INSIDE 73 55 62

FLOOR AREA 21
DIFF. 33
VOLUME 204
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 7

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 22 = 0


EAST WALL 0 x 0.35 x 36 = 0
SOUTH WALL 0.00 x 0.35 x 34 = 0
WEST WALL 0 x 0.35 x 30 = 0
NORTH EAST WALL 0 x 0.34 x 28 = 0
SOUTH EAST WALL 0 x 0.34 x 36 = 0
SOUTH WEST WALL 0 x 0.34 x 32 = 0
NORTH WEST WALL 0 x 0.34 x 24 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 33 = 0
PARTITION 0 x 0.15 x 28 = 0
FLOOR 21 x 0.56 x 28 = 325
FALSE CEILING 21 x 0.2 x 28 = 116
ROOF 0 x 0.15 x 53 = 0
VENTILATION 15 x 33 x 0.054 = 27
PEOPLE 1 x 245 x 1 = 245
LIGHTS 21 x 1.5 x 3.41 = 106
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0.02 x 1 x 3410 = 78
SENSIBLE SUB TOTAL = 897 SENSI. HEAT RATIO
SAFETY = 45
SENSIBLE TOTAL = 942
DEHUMIDIFIED CFM
VENTILATION 15 x 39 x 0.0335 = 20
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 225 REFG. SUB TOTAL
SAFETY = 11 SAFETY
LATENT TOTAL = 236 TOTAL
SENSIBLE TOTAL = 942
TOTAL SPACE HEAT = 1178 TONNAGE
TH GR/LB

43 110
26.8 71

16.2 39

0.80
ADP 54

48

1178
1039
2217
111
2328

0.19
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name CH-II Season Monsoon DB 85


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 82
WB 81
GLASS 0 0 0 0 0 0 0 0 TH 47.0
WALL 0 0 0 0 0 0 0 0 GR/LB 166.0
PARTITION 0 0 0 0 0 0 0 0

AREA 21 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 0.7 GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.68 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 50.00 FALSE CEILING 0.2
TR 0.19 FLOOR 0.56
CFM 24
Reheat
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-II OUT SIDE 85 82 81
INSIDE 73 55 62

FLOOR AREA 21
DIFF. 12
VOLUME 204
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 7

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 1 = 0


EAST WALL 0 x 0.35 x 15 = 0
SOUTH WALL 0.00 x 0.35 x 13 = 0
WEST WALL 0 x 0.35 x 9 = 0
NORTH EAST WALL 0 x 0.34 x 7 = 0
SOUTH EAST WALL 0 x 0.34 x 15 = 0
SOUTH WEST WALL 0 x 0.34 x 11 = 0
NORTH WEST WALL 0 x 0.34 x 3 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 12 = 0
PARTITION 0 x 0.15 x 7 = 0
FLOOR 21 x 0.56 x 7 = 81
FALSE CEILING 21 x 0.2 x 7 = 29
ROOF 0 x 0.12 x 32 = 0
VENTILATION 15 x 12 x 0.054 = 10
PEOPLE 1 x 245 x 1 = 245
LIGHTS 21 x 1.5 x 3.41 = 106
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 78
SENSIBLE SUB TOTAL = 549 SENSI. HEAT RATIO
SAFETY = 27
SENSIBLE TOTAL = 577
DEHUMIDIFIED CFM
VENTILATION 15 x 95 x 0.0335 = 48
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 253 REFG. SUB TOTAL
SAFETY = 13 SAFETY
LATENT TOTAL = 265 TOTAL
SENSIBLE TOTAL = 577
TOTAL SPACE HEAT = 842 TONNAGE
TH GR/LB

47 166
26.8 71

20.2 95

SENSI. HEAT RATIO 0.68


ADP 50

DEHUMIDIFIED CFM 24

842
1295
2138
107
2245
0.19
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name CH-II Season Winter DB 55


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 60
WB 48
GLASS 0 0 0 0 0 0 0 0 TH 19.7
WALL 0 0 0 0 0 0 0 0 GR/LB 42.0
PARTITION 0 0 0 0 0 0 0 0

AREA 21 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.02 KW TH 26.8
DIVERSITY FACTOR 0.7 GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.22 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 57.00 FALSE CEILING 0.2
TR -0.02 FLOOR 0.56
CFM 3
Reheat 0
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM CH-II OUT SIDE 55 60 48
INSIDE 73 55 62

FLOOR AREA 21
DIFF. -18
VOLUME 204
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 3 7

TOTAL CFM 15

NORTH WALL 0 x 0.35 x -29 = 0


EAST WALL 0 x 0.35 x -15 = 0
SOUTH WALL 0.00 x 0.35 x -17 = 0
WEST WALL 0 x 0.35 x -21 = 0
NORTH EAST WALL 0 x 0.34 x -23 = 0
SOUTH EAST WALL 0 x 0.34 x -15 = 0
SOUTH WEST WALL 0 x 0.34 x -19 = 0
NORTH WEST WALL 0 x 0.34 x -27 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x -18 = 0
PARTITION 0 x 0.15 x -23 = 0
FLOOR 21 x 0.56 x -23 = -267
FALSE CEILING 21 x 0.2 x -23 = -95
ROOF 0 x 0.12 x 2 = 0
VENTILATION 15 x -18 x 0.054 = -15
PEOPLE 1 x 245 x 1 = 245
LIGHTS 21 x 1.5 x 3.41 = 106
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 78
SENSIBLE SUB TOTAL = 53 SENSI. HEAT RATIO
SAFETY = 3
SENSIBLE TOTAL = 55
DEHUMIDIFIED CFM
VENTILATION 15 x -29 x 0.0335 = -15
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 190 REFG. SUB TOTAL
SAFETY = 10 SAFETY
LATENT TOTAL = 200 TOTAL
SENSIBLE TOTAL = 55
TOTAL SPACE HEAT = 255 TONNAGE
TH GR/LB

19.66 42
26.8 71

-7.14 -29

SENSI. HEAT RATIO 0.22


ADP 57

DEHUMIDIFIED CFM 3

255
-458
-203
-10
-213

-0.02
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYD OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS
Room. Name MEDIA WEIGHING & COMPOUNSeason Summer DB 106
AHU NO AHU-BV-04 N NE E SE S SW W NW RH 28
WB 78
GLASS 0 0 0 0 0 0 0 0 TH 43.0
WALL 0 0 0 0 0 0 0 0 GR/LB 110.0
PARTITION 0 0 0 0 0 0 0 0

AREA 91 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 2 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 7.5 KW AHU 0.70 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.15 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.98 WALL 0.35
SH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 57.00 FALSE CEILING 0.2
TR 2.28 FLOOR 0.56
CFM 1432

CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB


ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA WEIGHING & COMPOUNDING OUT SIDE 106 28 78
INSIDE 73 55 62

FLOOR AREA 91
DIFF. 33
VOLUME 896
BYPASS FACTOR 0.05

PEOPLE 2 15 30
EXHAUST 0
NO. OF A/CHANGES 2.0 15 30

TOTAL CFM 30

NORTH WALL 0 x 0.35 x 22 = 0


EAST WALL 0 x 0.35 x 36 = 0
SOUTH WALL 0 x 0.35 x 34 = 0
WEST WALL 0 x 0.35 x 30 = 0
NORTH EAST WALL 0 x 0.34 x 28 = 0
SOUTH EAST WALL 0 x 0.34 x 36 = 0
SOUTH WEST WALL 0 x 0.34 x 32 = 0
NORTH WEST WALL 0 x 0.34 x 24 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 33 = 0
PARTITION 0 x 0.15 x 28 = 0
FLOOR 91 x 0.56 x 28 = 1428
FALSE CEILING 91 x 0.2 x 28 = 510
ROOF 0 x 0.15 x 53 = 0
VENTILATION 30 x 33 x 0.054 = 53
PEOPLE 2 x 245 x 1 = 490
LIGHTS 91 x 1.5 x 3.41 = 466
EQUIPMENT (Kw) 8 x 0.7 x 3410 = 17903
AHU MOTOR (Kw) 0.70 x 1 x 3410 = 2387
SENSIBLE SUB TOTAL = 23237 SENSI. HEAT RATIO
SAFETY = 267
SENSIBLE TOTAL = 23503
DEHUMIDIFIED CFM
VENTILATION 30 x 39 x 0.0335 = 39
PEOPLE 2 x 205 x 1 = 410 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 449 REFG. SUB TOTAL
SAFETY = 22 SAFETY
LATENT TOTAL = 472 TOTAL
SENSIBLE TOTAL = 23503
TOTAL SPACE HEAT = 23975 TONNAGE
TH GR/LB

43 110
26.8 71

16.2 39

0.98
ADP 57

1432

23975
2078
26053
1303
27355

2.28
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name MEDIA WEIGHING & COM Season Monsoon DB 85


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 82
WB 81
GLASS 0 0 0 0 0 0 0 0 TH 47.0
WALL 0 0 0 0 0 0 0 0 GR/LB 166.0
PARTITION 0 0 0 0 0 0 0 0

AREA 91 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 2 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 7.5 KW AHU 0.70 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.98 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 57.00 FALSE CEILING 0.2
TR 2.19 FLOOR 0.56
CFM 1337
Reheat
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA WEIGHING & COMPOUNDING OUT SIDE 85 82 81
INSIDE 73 55 62

FLOOR AREA 91
DIFF. 12
VOLUME 896
BYPASS FACTOR 0.05

PEOPLE 2 15 30
EXHAUST 0
NO. OF A/CHANGES 2.0 15 30

TOTAL CFM 30

NORTH WALL 0 x 0.35 x 1 = 0


EAST WALL 0 x 0.35 x 15 = 0
SOUTH WALL 0.00 x 0.35 x 13 = 0
WEST WALL 0 x 0.35 x 9 = 0
NORTH EAST WALL 0 x 0.34 x 7 = 0
SOUTH EAST WALL 0 x 0.34 x 15 = 0
SOUTH WEST WALL 0 x 0.34 x 11 = 0
NORTH WEST WALL 0 x 0.34 x 3 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 12 = 0
PARTITION 0 x 0.15 x 7 = 0
FLOOR 91 x 0.56 x 7 = 357
FALSE CEILING 91 x 0.2 x 7 = 127
ROOF 0 x 0.12 x 32 = 0
VENTILATION 30 x 12 x 0.054 = 19
PEOPLE 2 x 245 x 1 = 490
LIGHTS 91 x 1.5 x 3.41 = 466
EQUIPMENT (Kw) 8 x 0.7 x 3410 = 17903
AHU MOTOR (Kw) 1 x 1 x 3410 = 2387
SENSIBLE SUB TOTAL = 21749 SENSI. HEAT RATIO
SAFETY = 192
SENSIBLE TOTAL = 21942
DEHUMIDIFIED CFM
VENTILATION 30 x 95 x 0.0335 = 95
PEOPLE 2 x 205 x 1 = 410 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 505 REFG. SUB TOTAL
SAFETY = 25 SAFETY
LATENT TOTAL = 531 TOTAL
SENSIBLE TOTAL = 21942
TOTAL SPACE HEAT = 22472 TONNAGE
TH GR/LB

47 166
26.8 71

20.2 95

SENSI. HEAT RATIO 0.98


ADP 57

DEHUMIDIFIED CFM 1337

22472
2591
25063
1253
26316
2.19
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name MEDIA WEIGHING & COM Season Winter DB 55


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 60
WB 48
GLASS 0 0 0 0 0 0 0 0 TH 19.7
WALL 0 0 0 0 0 0 0 0 GR/LB 42.0
PARTITION 0 0 0 0 0 0 0 0

AREA 91 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 2 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 7.5 KW AHU 0.70 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.98 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 56.00 FALSE CEILING 0.2
TR 1.68 FLOOR 0.56
CFM 1130
Reheat 0
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA WEIGHING & COMPOUNDING OUT SIDE 55 60 48
INSIDE 73 55 62

FLOOR AREA 91
DIFF. -18
VOLUME 896
BYPASS FACTOR 0.05

PEOPLE 2 15 30
EXHAUST 0
NO. OF A/CHANGES 2.0 15 30

TOTAL CFM 30

NORTH WALL 0 x 0.35 x -29 = 0


EAST WALL 0 x 0.35 x -15 = 0
SOUTH WALL 0.00 x 0.35 x -17 = 0
WEST WALL 0 x 0.35 x -21 = 0
NORTH EAST WALL 0 x 0.34 x -23 = 0
SOUTH EAST WALL 0 x 0.34 x -15 = 0
SOUTH WEST WALL 0 x 0.34 x -19 = 0
NORTH WEST WALL 0 x 0.34 x -27 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x -18 = 0
PARTITION 0 x 0.15 x -23 = 0
FLOOR 91 x 0.56 x -23 = -1173
FALSE CEILING 91 x 0.2 x -23 = -419
ROOF 0 x 0.12 x 2 = 0
VENTILATION 30 x -18 x 0.054 = -29
PEOPLE 2 x 245 x 1 = 490
LIGHTS 91 x 1.5 x 3.41 = 466
EQUIPMENT (Kw) 8 x 0.7 x 3410 = 17903
AHU MOTOR (Kw) 1 x 1 x 3410 = 2387
SENSIBLE SUB TOTAL = 19624 SENSI. HEAT RATIO
SAFETY = 86
SENSIBLE TOTAL = 19710
DEHUMIDIFIED CFM
VENTILATION 30 x -29 x 0.0335 = -29
PEOPLE 2 x 205 x 1 = 410 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 381 REFG. SUB TOTAL
SAFETY = 19 SAFETY
LATENT TOTAL = 400 TOTAL
SENSIBLE TOTAL = 19710
TOTAL SPACE HEAT = 20110 TONNAGE
TH GR/LB

19.66 42
26.8 71

-7.14 -29

SENSI. HEAT RATIO 0.98


ADP 56

DEHUMIDIFIED CFM 1130

20110
-916
19195
960
20154
1.68
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYD OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS
Room. Name MEDIA STORE Season Summer DB 106
AHU NO AHU-BV-04 N NE E SE S SW W NW RH 28
WB 78
GLASS 0 0 0 0 0 0 0 0 TH 43.0
WALL 0 0 0 0 0 0 0 0 GR/LB 110.0
PARTITION 0 0 0 0 0 0 0 0

AREA 32 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.03 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.15 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.84 WALL 0.35
SH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 56.00 FALSE CEILING 0.2
TR 0.22 FLOOR 0.56
CFM 73

CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB


ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA STORE OUT SIDE 106 28 78
INSIDE 73 55 62

FLOOR AREA 32
DIFF. 33
VOLUME 314
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 5 10

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 22 = 0


EAST WALL 0 x 0.35 x 36 = 0
SOUTH WALL 0.00 x 0.35 x 34 = 0
WEST WALL 0 x 0.35 x 30 = 0
NORTH EAST WALL 0 x 0.34 x 28 = 0
SOUTH EAST WALL 0 x 0.34 x 36 = 0
SOUTH WEST WALL 0 x 0.34 x 32 = 0
NORTH WEST WALL 0 x 0.34 x 24 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 33 = 0
PARTITION 0 x 0.15 x 28 = 0
FLOOR 32 x 0.56 x 28 = 501
FALSE CEILING 32 x 0.2 x 28 = 179
ROOF 0 x 0.15 x 53 = 0
VENTILATION 15 x 33 x 0.054 = 27
PEOPLE 1 x 245 x 1 = 245
LIGHTS 32 x 1.5 x 3.41 = 163
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0.03 x 1 x 3410 = 102
SENSIBLE SUB TOTAL = 1217 SENSI. HEAT RATIO
SAFETY = 61
SENSIBLE TOTAL = 1278
DEHUMIDIFIED CFM
VENTILATION 15 x 39 x 0.0335 = 20
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 225 REFG. SUB TOTAL
SAFETY = 11 SAFETY
LATENT TOTAL = 236 TOTAL
SENSIBLE TOTAL = 1278
TOTAL SPACE HEAT = 1514 TONNAGE
TH GR/LB

43 110
26.8 71

16.2 39

0.84
ADP 56

73

1514
1039
2552
128
2680

0.22
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name MEDIA STORE Season Monsoon DB 85


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 82
WB 81
GLASS 0 0 0 0 0 0 0 0 TH 47.0
WALL 0 0 0 0 0 0 0 0 GR/LB 166.0
PARTITION 0 0 0 0 0 0 0 0

AREA 32 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.03 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR 0.73 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 52.00 FALSE CEILING 0.2
TR 0.20 FLOOR 0.56
CFM 34
Reheat
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA STORE OUT SIDE 85 82 81
INSIDE 73 55 62

FLOOR AREA 32
DIFF. 12
VOLUME 314
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 5 10

TOTAL CFM 15

NORTH WALL 0 x 0.35 x 1 = 0


EAST WALL 0 x 0.35 x 15 = 0
SOUTH WALL 0.00 x 0.35 x 13 = 0
WEST WALL 0 x 0.35 x 9 = 0
NORTH EAST WALL 0 x 0.34 x 7 = 0
SOUTH EAST WALL 0 x 0.34 x 15 = 0
SOUTH WEST WALL 0 x 0.34 x 11 = 0
NORTH WEST WALL 0 x 0.34 x 3 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x 12 = 0
PARTITION 0 x 0.15 x 7 = 0
FLOOR 32 x 0.56 x 7 = 125
FALSE CEILING 32 x 0.2 x 7 = 45
ROOF 0 x 0.12 x 32 = 0
VENTILATION 15 x 12 x 0.054 = 10
PEOPLE 1 x 245 x 1 = 245
LIGHTS 32 x 1.5 x 3.41 = 163
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 102
SENSIBLE SUB TOTAL = 690 SENSI. HEAT RATIO
SAFETY = 35
SENSIBLE TOTAL = 725
DEHUMIDIFIED CFM
VENTILATION 15 x 95 x 0.0335 = 48
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 253 REFG. SUB TOTAL
SAFETY = 13 SAFETY
LATENT TOTAL = 265 TOTAL
SENSIBLE TOTAL = 725
TOTAL SPACE HEAT = 990 TONNAGE
TH GR/LB

47 166
26.8 71

20.2 95

SENSI. HEAT RATIO 0.73


ADP 52

DEHUMIDIFIED CFM 34

990
1295
2285
114
2400
0.20
Customer: M/S. BACTERIAL VACCINE Address : KARAKAPATLA , HYDERABA OUTSIDE DESIGN
Room. No Date : 10.09.2019 CONDITIONS

Room. Name MEDIA STORE Season Winter DB 55


AHU NO AHU-BV-04 N NE E SE S SW W NW RH 60
WB 48
GLASS 0 0 0 0 0 0 0 0 TH 19.7
WALL 0 0 0 0 0 0 0 0 GR/LB 42.0
PARTITION 0 0 0 0 0 0 0 0

AREA 32 Sft
INSIDE DESIGN
FALSE CEILING HT. 9.84 Ft CONDITIONS
NO OF AIR CHANGES 2 PER HR. DB 73
NO. OF PEOPLE 1 RH 55
LIGHTING LOAD 1.5 W/S. FT WB 62
EQUIPMENT LOAD 0.0 KW AHU 0.03 KW TH 26.8
DIVERSITY FACTOR 70% GR/LB 71
EXHAUST 0
FLOOR GAIN 1 (1 if fl. gain exists else 0)
ROOF(0)/FALSECEILING(1) 1 0.12 (0.12 or 0.5 if roof) FACTORS
CAND(1)/IN CANDI 1 SHR -0.48 WALL 0.35
RH PER PERSON 245 GLASS 0.56
LH PER PERSON 205 ALL GLASS 1.13
BPF 0.05 PARTITION 0.15
CFM/PERSON 15 Selected ADP 56.00 FALSE CEILING 0.2
TR -0.03 FLOOR 0.56
CFM -4
Reheat 0
CUSTOMER M/S. BACTERIAL VACCINE DB %RH WB
ADDRESS KARAKAPATLA , HYDERABAD
ROOM MEDIA STORE OUT SIDE 55 60 48
INSIDE 73 55 62

FLOOR AREA 32
DIFF. -18
VOLUME 314
BYPASS FACTOR 0.05

PEOPLE 1 15 15
EXHAUST 0
NO. OF A/CHANGES 2.0 5 10

TOTAL CFM 15

NORTH WALL 0 x 0.35 x -29 = 0


EAST WALL 0 x 0.35 x -15 = 0
SOUTH WALL 0.00 x 0.35 x -17 = 0
WEST WALL 0 x 0.35 x -21 = 0
NORTH EAST WALL 0 x 0.34 x -23 = 0
SOUTH EAST WALL 0 x 0.34 x -15 = 0
SOUTH WEST WALL 0 x 0.34 x -19 = 0
NORTH WEST WALL 0 x 0.34 x -27 = 0
NORTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH EAST GLASS 0 x 0.56 x 12 = 0
SOUTH WEST GLASS 0 x 0.56 x 85 = 0
NORTH WEST GLASS 0 x 0.56 x 138 = 0
NORTH GLASS 0 x 0.56 x 23 = 0
EAST GLASS 0 x 0.56 x 12 = 0
SOUTH GLASS 0 x 0.56 x 12 = 0
WEST GLASS 0 x 0.56 x 163 = 0
ALL GLASS 0 x 1.13 x -18 = 0
PARTITION 0 x 0.15 x -23 = 0
FLOOR 32 x 0.56 x -23 = -411
FALSE CEILING 32 x 0.2 x -23 = -147
ROOF 0 x 0.12 x 2 = 0
VENTILATION 15 x -18 x 0.054 = -15
PEOPLE 1 x 245 x 1 = 245
LIGHTS 32 x 1.5 x 3.41 = 163
EQUIPMENT (Kw) 0 x 0.7 x 3410 = 0
AHU MOTOR (Kw) 0 x 1 x 3410 = 102
SENSIBLE SUB TOTAL = -62 SENSI. HEAT RATIO
SAFETY = -3
SENSIBLE TOTAL = -65
DEHUMIDIFIED CFM
VENTILATION 15 x -29 x 0.0335 = -15
PEOPLE 1 x 205 x 1 = 205 TOTAL SPACE HEAT
VENT. HEAT
LATENT SUB TOTAL = 190 REFG. SUB TOTAL
SAFETY = 10 SAFETY
LATENT TOTAL = 200 TOTAL
SENSIBLE TOTAL = -65
TOTAL SPACE HEAT = 135 TONNAGE
TH GR/LB

19.66 42
26.8 71

-7.14 -29

SENSI. HEAT RATIO -0.48


ADP 56

DEHUMIDIFIED CFM -4

135
-458
-323
-16
-339

-0.03