The column is an important structure element because the failure of column will have direct
impact to other structure components, so that the ruin of structural column is an important thing to
be observed. The research use experimental method. The aim of this research is to get improving of
strength and ductility in column specimen which is given the FRP strengthener (Fiber Reinforced
Polymer) compared with original column. There are 3 specimens used. They are C-1 (original
column), C-1G (column with GFRP strengthener 1 layer) and C-1C (column with CFRP strengthener
1 layer). From the research got the increasing Pmax toward original column is 33,52% and 54,97%,
the increasing of dmax is 6,65% and 81,18%, also the increasing of Mmax is 32,41% and 55,36% each
for C-1G and C-1C. Ductility indexes taken on three positions are plastic hinge zone, a half high of
column effective and as high as column effective. From analyze result got the increasing of
displacement ductility toward C-1 for C-1G is -34,20%, -28,46% and -12,74% and C-1C is 64,48%,
108,74% and 118,68%, each for plastic hinge zone, a half high of column effective and as high as
column effective. In column C-1G happened the decreasing of ductility value because there has been
destruction in column head when the test was running.
Key words : Experimental method, FRP, RC, Strengthener column
Abstrak
Kolom merupakan elemen struktur penting karena kegagalan kolom akan berpengaruh langsung
terhadap komponen struktur lainnya , sehingga kehancuran kolom struktural merupakan hal yang
penting untuk dicermati . Penelitian ini menggunakan metode eksperimen . Tujuan dari penelitian ini
adalah untuk mendapatkan meningkatkan kekuatan dan daktilitas dalam spesimen kolom yang diberi
FRP penguat ( Fiber Reinforced Polymer ) dibandingkan dengan kolom awal . Ada 3 spesimen yang
digunakan . Mereka adalah C - 1 ( kolom asli) , C - 1G ( kolom dengan GFRP penguat 1 lapisan ) dan C
- 1C ( kolom dengan CFRP penguat 1 lapisan ) . Dari penelitian mendapat peningkatan Pmax menuju
kolom awal adalah 33,52 % dan 54,97 % , peningkatan dmax adalah 6,65 % dan 81,18 % , juga
meningkatnya Mmax adalah 32,41 % dan 55 , 36 % masing-masing untuk C - 1G dan C - 1C . Indeks
daktilitas diambil pada tiga posisi yang zona sendi plastis , setengah tinggi kolom yang efektif dan
setinggi kolom yang efektif . Dari hasil analisis mendapat peningkatan daktilitas terhadap - C 1 untuk
C - 1G adalah -34,20 % , -28,46 % dan -12,74 % dan C - 1C adalah 64,48 % , 108,74 % dan 118,68 % ,
masing-masing untuk zona sendi plastis , setengah tinggi kolom yang efektif dan setinggi kolom yang
efektif . Dalam kolom C - 1G terjadi penurunan nilai daktilitas karena sudah ada kerusakan di kepala
kolom saat tes berjalan .
Kata kunci : metode eksperimental , FRP , RC , kolom Strengthener
PENDAHULUAN
Struktur kolom merupakan elemen struktur
yang rentan terhadap kegagalan ketika menerima
149
Gambar 1. Serat yang digunakan: (a)Tyfo SEH System Uni-directional glass composite; (b).Tyfo
SCH System Uni-directional carbon composite (Brosur Tyfo Fibrwrap System)
Kolom
Perkuatan Struktur
150
Versi online:
1
METODE PENELITIAN
Tempat Penelitian
Rancangan Penelitian
Penelitian ini dilakukan di dua tempat.
Pembuatan benda uji dilakukan di Laboratorium
Bahan Konstruksi dan Laboratorium Struktur
Jurusan Teknik Sipil Universitas Brawijaya, Malang.
Untuk uji tarik FRP dan pengujian struktur dilakukan
di Balai Bahan Bangunan dan Balai Struktur
Benda uji yang digunakan ada 3 buah yaitu C1 sebagai kolom kontrol, C-1G yaitu kolom perkuatan
1 lapis GFRP dan C-1C yaitu kolom perkuatan 1
lapis CFRP. Dengan spesifikasi benda uji seperti
dalam tabel 1.
No
Benda
uji
1
Benda
uji
kolom
C-1
Kuat
tekan
beton,
Mpa
20,34
C-1G
20,34
350
350
1100
C-1C
20,34
350
350
1100
Tulangan
Trans
10 - 200
Fu,
MPa
-
Tebal
/ lapis
(mm)
-
Jumlah
Lapisan
-
8D19
10 - 200
575
1.3
8D19
10 - 200
876
1.0
B
(mm)
350
H
(mm)
350
L
(mm)
1100
Long
8D19
Setting up
Pelaksanaan pengujian dilakukan dengan
menempatkan benda uji kolom berdiri tegak pada 2
buah rangka baja (loading frame) yang diletakkan
di atas lantai kerja yang dikunci pada ujung-ujung
balok tumpuan dengan baut. Untuk mendapatkan
151
152
Versi online:
1
153
Versi online:
1
155
Prosentase peningkatan md C-1G terhadap C1 adalah -34,20%, -28,46% dan -12,74% dan
peningkatan md C-1C terhadap C-1 adalah
64,48%, 108,74% dan 118,68% untuk zona
sendi plastis, setengah tinggi kolom dan setinggi
efektif kolom.
Versi online:
1
Saran
DAFTAR PUSTAKA
ACI 440.2R-02. Guide for the Design and
Construction of Externally Bonded FRP
Systems for Strengthening Concrete
Structures. ACI Committee 440, 2002
ACI 440.3R-04. Guide Test Methods for FiberReinforced Polymers (FRPs) for Reinforcing
or Strengthening Concrete Structures. ACI
Committee 440, 2004
ACI 374.1-05. Acceptance Criteria for Moment
Frames Based on Structural Testing and
Commentary. ACI Committee 374, 2005
Al-Sulayfani, B and Al-Taee, H. Modeling of
Stress-Strain Relationship for Fibrous
Concrete
Under
Cyclic
Loads
Eng.Tech.Vol.26, No1, 2008, pp. 45-53
Balaguru, P, Nanni, A and Giancaspro, J. FRP
Composites for Reinforced and Prestressed
Concrete Structures Taylor & Francis Group,
New York, 2009
Bank, Lawrence. Structural Design with FRP
Materials John Wiley & Sons, INC, Canada,
2006
Benzaid, R, Chikh NE and Mesbah H. Behaviour
Of Square Concrete Column Confined With
GFRP Composite Warp, Journal Of Civil
Engineering And Management, 2008