You are on page 1of 6

Loadbreak Apparatus

Connectors
Service Information
200 A 15 kV and 25 kV Class Elbow
Installation Instructions S500-10-1
Contents
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 LOCKING RING
MOLDED ON
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 INSULATED SLEEVE
Preparation of Concentric Neutral Cable . . . . . . . . .3 ENCAPSULATED
LOADBREAK
Elbow and Loadbreak Probe Installation . . . . . . . . . .4 SEMI-CONDUCTIVE INSERT
PROBE
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . .5
SEMI-CONDUCTING ARC
SHIELD FOLLOWER
GENERAL
The Cooper Power Systems Loadbreak Elbow Connector
is a fully-shielded and insulated plug-in termination for PULLING
connecting underground cable to transformers, switching EYE
cabinets and junctions equipped with loadbreak bushings.
The elbow connector and bushing insert comprise the COPPERTOP
essential components of all loadbreak connections. CONNECTOR
SEMI-CONDUCTIVE INSERT

WARNING: All associated apparatus must be TEST POINT


! de-energized during any hands-on installation
DRAIN WIRE TAB

or maintenance.
LOADBREAK BAND
INSULATION
ENCAPSULATED EPDM INSULATION
CAUTION: The 200 A Loadbreak Elbow CONDUCTIVE
! Connector is designed to be operated in INSERT ENDS
accordance with normal safe operating procedures.
These instructions are not intended to supersede or
replace existing safety and operating procedures. The
elbow connector should be installed and serviced only
by personnel familiar with good safety practices and Figure 1.
the handling of high-voltage electrical equipment. Line illustration of 200 A 25 kV Expanded Range
POSI-BREAK™ Elbow.

CAUTION: Optional Capacitive Test Point


! Operating Instructions: Use only voltage indi-
loadbreak operations. (See page 5 for operating
instructions.)
cating instruments specifically designed for test points.
Use of conventional voltage sensing devices may Complete elbow kit includes:
provide false “No Voltage” indications. ■ Elbow Body
The test point must be dry and free of contaminants ■ Coppertop Compression Connector
when checking for voltage. After indication is taken: ■ Loadbreak Probe
clean, dry, and lubricate the test point cap with ■ Probe Installation Tool
silicone grease and assemble to the test point. ■ Silicone Lubricant
■ Instruction Sheet
Always consider the termination to be energized
until the test point “No Voltage” indication is Tools/Accessories needed:
confirmed by other means. ■ Tape Measure
■ Wire Brush
■ Knife
INSTALLATION ■ Cable Stripping Tool
Cable stripping and scoring tools, available from various ■ Crimping Tool
tool manufacturers, are recommended for use when ■ Cable Cleaner
installing loadbreak elbows. After preparing the cable, ■ Cable Cutters
the elbow housing is pushed onto the cable. The load- ■ Emery Cloth
break probe is threaded into the coppertop connector ■ Hotstick
using the supplied installation tool or an approved ■ Personal Protection Equipment
equivalent. Use a hotstick to perform loadmake and

These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide
directions for meeting every contingency during installation, operation, or maintenance. When additional information is desired to
satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.

February 2005 • Supersedes 2/01 1


Printed in U.S.A.
200 A 15 and 25 kV Class Elbow Installation Instructions

!
SAFETY
!
SAFETY
FOR LIFE SAFETY FOR LIFE FOR LIFE

Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We
actively promote safe practices in the use and maintenance of our products through our service literature, instructional
training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design,
manufacture, marketing and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high-voltage lines and equipment and support our “Safety For Life” mission.

SAFETY INFORMATION
The instructions in this manual are not intended as a Safety Instructions
substitute for proper training or adequate experience in
the safe operation of the equipment described. Only Following are general caution and warning statements
competent technicians, who are familiar with this that apply to this equipment. Additional statements,
equipment should install, operate and service it. related to specific tasks and procedures, are located
A competent technician has these qualifications: throughout the manual.
■ Is thoroughly familiar with these instructions.
DANGER: Hazardous voltage. Contact with
■ Is trained in industry-accepted high- and low-voltage high voltage will cause death or severe
safe operating practices and procedures. personal injury. Follow all locally approved safety
■ Is trained and authorized to energize, de-energize,
procedures when working around high- and low-
voltage lines and equipment.
clear, and ground power distribution equipment.
■ Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield,
hard hat, rubber gloves, hotstick, etc. WARNING: Before installing, operating,
maintaining, or testing this equipment, carefully
Following is important safety information. For safe read and understand the contents of this manual.
installation and operation of this equipment, be sure to Improper operation, handling or maintenance can
read and understand all cautions and warnings. result in death, severe personal injury, and equipment
damage.

Hazard Statement Definitions


WARNING: This equipment is not intended to
This manual may contain four types of hazard protect human life. Follow all locally approved
statements: procedures and safety practices when installing or
operating this equipment. Failure to comply may
DANGER: Indicates an imminently hazardous result in death, severe personal injury and equipment
situation which, if not avoided, will result in damage.
death or serious injury.
WARNING: Indicates a potentially hazardous
situation which, if not avoided, could result In WARNING: Power distribution equipment must
death or serious injury. be selected for the intended application. It must
be installed and serviced by competent personnel
CAUTION: Indicates a potentially hazardous who have been trained and understand proper safety
situation which, if not avoided, may result in procedures. These instructions are written for such
minor or moderate injury. personnel and are not a substitute for adequate
training and experience in safety procedures. Failure
CAUTION: Indicates a potentially hazardous situation to properly select, install or maintain this equipment
which, if not avoided, may result in equipment can result in death, severe personal injury, and
damage only. equipment damage.

2
Step 1 Step 2 Step 3 Step 4

FIRST
CRIMP
PLACED
BELOW
2 1/8" KNURL
(54 mm) CONDUCTOR

1/8"
INSULATION
SHIELD BEVEL
(3 mm)
CLEAN
EXCESS
INHIBITOR
GREASE 6 7/8"
(175 mm)

8 1/2" INSULATION INSULATION


(216 mm) SHIELD SHIELD

BEND
NEUTRAL
WIRES
DOWN
AND OUT
OF THE
WAY

CABLE
JACKET

PREPARATION OF CONCENTRIC faces the apparatus bushing.


NEUTRAL CABLE Crimp the connector in place using a tool and die
NOTE: If concentric neutral cable is not being used, follow combination listed in Table 1. Start crimping just below
cable preparation directions in shield adapter kit. the knurled line and rotate each successive crimp to
prevent bowing. Do not overlap crimps. Place as many
Step 1 crimps on the connector as will fit.
Measure down from top of the cable 8 1/2". Clean excess inhibitor grease from coppertop connector
Remove cable jacket (if jacketed cable is used) to by wiping toward threaded eye.
expose neutral wires. Smooth any sharp edges on the crimp connector
Unwind neutral wires. surface.

Step 2 Step 4
Measure down from the top of the cable 2 1/8". Measure down from the top of the connector 6 7/8".
Remove the insulation and conductor shield to expose Remove the insulation shield. Take care not to nick or
the bare conductor. Take care not to nick the conductor. gouge insulation.
Place a 1/8" bevel on the insulation to ease elbow
Step 3 installation.
Clean the exposed conductor using a wire brush.
Step 5
NOTE: The probe (male contact) should be preassembled into
the threads of the compression connector prior to Apply a suitable jacket seal over the jacket and exposed
crimping to ensure proper thread engagement. neutral wires.
Place the coppertop (bimetal) connector on the If a Cooper Power Systems jacket seal is used, follow
conductor. Make sure the threaded hole in connector instructions supplied with the jacket seal kit.
3
S500-10-1

Step 5 Step 6

Step 7

COVER
TEST
POINT
WITH CAP

CLEAN CLEAN AND


AND LUBRICATE
LUBRICATE
CABLE
ENTRANCE ATTACH DRAIN
WIRE TO ELBOW
DRAIN WIRE TAB

JACKET
SEAL

ELBOW AND LOADBREAK PROBE Step 7


INSTALLATION By hand, thread loadbreak probe into threaded eye of
Step 6 coppertop connector. A thin layer of silicone lubricant
Clean insulation with a lint free cloth saturated with a applied to the back section of probe (not on threads) can
cleaning solution. Wipe insulation toward insulation aid in installation.
shield. NOTE: If installing a POSI-BREAK™ Elbow, be sure to use a
Apply a thin coating of supplied lubricant to the POSI-BREAK probe with black insulating sleeve.
insulation. When tight, use the provided installation tool to properly
Clean and lubricate the cable entrance of the elbow. torque the loadbreak probe. Proper torque is applied
when the tool achieves a 180° permanent set.
Place elbow on cable. With a twisting motion, push elbow NOTE: If a different installation tool is used it must apply a torque
onto cable until threaded eye of coppertop connector is of 100 to 120 lbf-in (11.0-13.5 N-m).
aligned with the elbow.
Clean and lubricate bushing and elbow interface areas
with a thin even coating of the silicone lubricant provided.
Attach a drain wire lead to the drain wire eye of the elbow.

4
S500-10-1

TABLE 1
Crimp Chart
CONNECTOR 5/8" DIAMETER 3/4" DIAMETER

CONDUCTOR SIZE NO. 4 THRU 2/0 STRANDED 3/0 - 4/0 STRANDED


TOOL Y34 Y35 OR Y39 MD6 Y34 Y35 OR Y39 MD6

BURNDY DIE A243 U243 UBG W243 WBG U247 U247 U467 W247

BG
A25AR U25ART U687 NOSE W687 A27AR U27ART

SOMERSET TOOL UT-3 UT-5 UT-15 UT-5 UT-15


(T AND B) DIE 5/8" TV 54 H TV 66
TOOL 0 H-1, H-2, H-3 0 H-1, H-2, H-3
KEARNEY 5/8"
DIE 620 9/16" 737 747 737 747
NOSE
TOOL 12A 12A
ALCOA
DIE B24 EA B39 EA
ANDERSON TOOL VC-5, VC-6 VC-5, VC-6
EEI – REFERENCE 8A 10A

CAUTION: The operator should always use Fault Close


! personal protective equipment (insulated 1. It is not recommended that operations be made on
gloves, hotstick and eye protection) whenever known faults.
operating the elbow. The operator should always
be in the best possible operating position, 2. If a fault is experienced, both the elbow connector
providing firm footing and enabling a secure grasp and the bushing must be replaced.
of the hotstick, while maintaining positive control Loadbreak Operation
of the elbow before, during and immediately after
operation. If there is any question regarding the 1. Securely fasten a hotstick to the pulling eye.
operator’s operating position, de-energize the 2. Without exerting any pulling force, slightly rotate
elbow before operation. The operator should not the connector clockwise to break surface friction
be looking directly at the connector during the between the elbow and bushing.
moment of circuit interruption or connection.
3. Withdraw the connector from the bushing with a
fast, firm, straight motion, being careful not to
OPERATING INSTRUCTIONS place the connector near a ground plane.
Do not connect two different phases of a multiple- 4. Place connector on an appropriate accessory
phase system. Before closing a single-phase loop, device, following the operating instructions for
make certain both ends of the loop are the same that accessory.
phase. 5. Place an insulated protective cap with drain wire
Loadmake Operation attached to system ground on any exposed
energized bushing using a hotstick.
1. Area must be clear of obstructions or contaminants
that would interfere with the operation of the
loadbreak elbow.
2. Securely fasten a hotstick to the pulling eye.
3. Place the loadbreak elbow over the bushing,
inserting the white arc follower of the probe into
the bushing approximately 2 1/2" until a slight
resistance is felt.
4. Immediately thrust the elbow onto the bushing
with a fast, firm, straight motion, with sufficient
force to latch the elbow to the bushing.
5. Push again on the elbow with the hotstick, and
then pull gently to make sure that it is secure.

5
200 A 15 and 25 kV Class Elbow Installation Instructions

(54 mm)
2 1/8"

(175 mm)
6 7/8"

©2005 Cooper Power Systems or its affiliates. 1045 Hickory Street


POSI-BREAK™ is a trademark of Cooper Power Systems or its affiliates. Pewaukee, WI 53072 USA
#5000050751 Rev. 06 www.cooperpower.com
6
MI
2/01

You might also like