Professional Documents
Culture Documents
Main
Range of product Xantrex GT
Device short name GT100-208
Product or component Grid-tie solar inverter
type
Network number of Three phase
phases
Nominal output power 100 kW AC
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Output voltage 208 V +10 % -12 % AC three phase
Output current 278 A AC
Peak output current 1100 A 8 ms
Network frequency 60 Hz +0.5 Hz -0.7 Hz (output)
Cos phi > 0.99 above 20 % rated power
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Harmonic distortion < 3 % at rated power
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Input voltage 300 - 600 V DC
300 - 480 V DC MPPT
<= 600 V DC open circuit
Input current 347 A DC
Utility backfeed current 0A
Overcurrent protection 400 A (output)
Efficiency 95 % CEC
Power consumption in W < 100 W night time
Feature available Standard integrated AC and DC disconnects
Standard ground fault protection
Standard integrated isolation transformer
Optional RS485/Modbus or Ethernet communications interface kit
Optional integrated sub-array combiner with 100A, 150A or 200A circuits
Display type VFD
Display capacity 4 lines
Enclosure material Steel
Surface finish Powder coated
Zinc primed
Type of cooling Forced convection (depending on temperature)
Device mounting Floor mounted
Height 1862 mm
Width 1702 mm
Depth 1171 mm
Product weight 1361 kg