You are on page 1of 5

CHW PLANT DESIGN

The Demise of the


Primary-Secondary Pumping Paradigm for
Chilled Water Plant Design
Accepting that low ∆T
chilled water plant
By WAYNE KIRSNER, PE, heating up the central plant
Kirsner, Pullin & Associates, building). The low ∆T at the
syndrome exists in
Atlanta, Ga. plant causes the operators to run almost all big
extra pumps and chillers to meet distributed chilled

I
’ve got some bad news—the the load, which, in addition to re-
20-odd-year experiment with ducing the plant’s cooling output water systems and
primary-secondary design of capacity, wastes energy. The sys- recognizing the need to
chilled water plants hasn’t tem may be keeping the campus
panned out. If you’ve designed a cool, but you know it’s inefficient seek design solutions
large distributed chilled water and idling a lot of chiller capac- that can cope with or
system and monitored the opera- ity.
tion of the central plant, you al- The problem described above prevent it
ready know about the problems: has come to be known as “low ∆T
the ∆T of the chilled water central plant syndrome.” To my
(CHW) returning to the campus knowledge, every large chilled
plant is below the design value water plant serving distributed at the NASA Johnson Space Cen-
for which the chillers and pumps loads is afflicted with it to some ter” (HPAC, February 1995)1 de-
were selected—in fact, it’s way degree. The article “Trouble- scribes a typical situation. A cen-
below; the secondary CHW flow shooting Chilled Water Problems tral plant originally designed for
doesn’t vary a hoot; and the ex- a 16 F ∆T between the chilled wa-
pensive variable-speed drive 1
Wayne Kirsner authored the Febru- ter return (CHR) and chilled wa-
(VSD) purchased to vary the flow ary 1995 article cited above as well as ter supply (CHS) could only de-
of the secondary pumps was the article “What Caused the Steam velop an 8 F ∆T because of low
great for test and balance but System Accident that Killed Jack CHR temperature from the cam-
hasn’t done much since (besides Smith?,” HPAC, July 1995. pus. This meant not only that
twice as much CHW as originally
intended had to be pumped
VSD
around the 5-mile campus piping
loop but also that the seven 2000-
ton chillers in the central plant
couldn’t be loaded much beyond
half their capacity. Thus, opera-
Chiller Chiller tors were usually forced to run
Crossover twice as many chillers to meet
decoupler the campus load, and the fric-
Constant-flow tional loss in the mains due to the
pumps excessive CHW flow made it

1 Archetypal primary-secondary
CHW plant design.

November 1996 HPAC Heating/Piping/AirConditioning 73


Chilled water plant design

tough to deliver sufficient CHW scheme that depends on system a severe upset, but it’s not far-
to hydraulically distant build- flow to gauge system load is virtu- fetched at all. Starting a second
ings. ally blind to load variation. chiller in a two-chiller plant,
The causes of low ∆T syndrome where identical chillers operate in
are not mysterious, but they are Problem #2 parallel, typically results in the
often pervasive and thus can be The primary loop is constant load to the active chiller being
hard to remedy. Low ∆T can be flow. Constant flow through halved. 2) In a constant-flow pri-
caused by dirty cooling coils, chillers is a highly desirable fea- mary loop designed to chill, say,
throttling valves with insuffi- ture of primary-secondary chilled 55 F CHR to 45 F CHS, a 50 per-
cient shutoff capability, reset water plant design, and most cent drop in load would manifest
CHS temperature, poorly con- chiller manufacturers still prefer itself in CHR temperature rising
trolled blending stations, and of and recommend it. I’ve been con- to 50 F. (This might occur because
course, CHW bypassing out in vinced, however, that most mod- approximately half the primary
the system. But most often, low ern chiller controls no longer re- flow of 45 F CHS is recirculating
system ∆T is the result of faulty quire constant flow to keep the through the crossover bridge to
controls and improperly adjusted chillers out of trouble. Let me ex- mix with the 55 F CHR from the
set points. This article, however, plain. system.) The 50 F CHR entering
is not about the causes of central When chiller vanes were con- the formerly fully loaded active
plant syndrome. It’s about ac- trolled by conventional pneu- chiller would initially be sub-
cepting that the problem exists in matic proportional controls, re- jected to the full cooling capacity
virtually every big distributed sponse time to changes in load of the chiller until its controls
chilled water system and then was necessarily slow and gradual could respond to decrease capac-
recognizing the need to seek de- to prevent overshoot and hunting ity. The chiller would thus tend to
sign solutions that can cope with as the chiller controls tried to drive the entering 50 F CHW
it, if not prevent it. achieve leaving CHS set point. down toward 40 F.
So why can’t a standard pri- Hence, chiller capacity controls Compare this upset condition to
mary-secondary chilled water de- would lag behind a sudden load a variable-flow configuration.
sign cope with low CHW ∆T? change. If the change was a drop Starting a second equal CHW
in load, the chiller would overcool pump could cut CHW flow through
Problem #1 the leaving CHW, dropping it be- the active chiller roughly in half.3
The primary-secondary control low set point until capacity con- The active chiller would initially
scheme is “blinded” by low ∆T trol vanes could react to reduce continue to try to apply its full out-
central plant syndrome. Fig. 1 de- chiller refrigerating capacity. If put capacity to half the mass flow,
picts what I would describe as the drop in load was sharp thereby doubling the ∆T of CHW
the archetypal primary-sec - enough, the chiller’s low evapora- passing through it—i.e., it would
ondary chilled water schematic tor temperature safety would tend to drive 55 F CHR down to 35
configuration. The primary fea- knock the chiller off line, requir- F. This is pretty close to freezing. If
ture of the configuration is the ing a manual reset to restart the the design ∆T was larger, the CHW
decoupled primary and sec - chiller. This is a situation to be would be driven down below freez-
ondary loops, which allow con- avoided. ing. In either case, a simple low
stant flow through the chillers Now consider the response of a evaporator temperature sensor
while permitting varying flow in chilled water plant designed for would likely cause the chiller to
the system to save pumping en- constant flow versus one designed trip off line to protect it from freez-
ergy. Chillers are staged on and for variable flow in the event that ing. The constant-flow chiller, in
off based on CHW flow through load across a fully loaded chiller comparison, whose leaving CHS
the crossover bridge (although suddenly dropped in half. (This is temperature dips only half as far,
the sensor may be elsewhere). would probably remain on line. For
The sole indicator of system load, this reason alone, one can easily
2
upon which control of the chillers For example, in a variable-flow understand why chiller manufac-
and pumps depends, is chilled plant, flow through the active chiller
water flow. will be cut roughly in two as the sec-
3
ond chiller’s pump instantly usurps Assuming immediate system control
In a plant with low ∆T syn-
half the flow. In a primary-secondary valve response and the absence of cen-
drome, CHW flow is no longer plant, approximately half the total tral plant syndrome. If control valve
much of an indicator of load. The primary CHW flow recirculates response were slow or the system were
amplitude of flow variation is just through the crossover bridge and, once afflicted with central plant syndrome,
a fraction of the amplitude of load the second chiller’s compressor has be- flow would not suddenly fall to half,
variation. Fundamentally then, a gun outputting CHW, mixes with sys- and thus the upset condition would be
primary-secondary control tem secondary CHR to halve its ∆T. far less traumatic.

74 HPAC Heating/Piping/AirConditioning Novemberr 1996


turers would prefer constant flow possibility of laminar flow individual chillers to load them
through chillers. through the evaporator due to low more fully. But with the primary-
So what’s changed to invalidate CHW flow is eliminated. This con- secondary configuration shown in
this argument? The low evapora- dition can easily be avoided, how- Fig. 1, this is not possible. Pri-
tor temperature control is more so- ever, in a variable primary flow mary-secondary systems can be
phisticated, for one. It’s no longer system. Burt Rishel of Systecon retrofitted, of course, in response
simply a low-temperature safety suggests the best way to do this is to low ∆T. New pumping capacity
cutout. The Trane Company’s mi- the old-fashioned way—with a by- can be added and flow through
croprocessor-based control, for ex- pass from CHS to CHR opened via chillers can be increased up to the
ample, integrates (i.e., sums) the a signal from a flow meter or dif- manufacturer’s recommended
number of degree-seconds (deg- ferential pressure controller maximum rate. Perhaps evapora-
sec) below the low evaporator tem- across the chiller. This might tors can even be converted from
perature set point. Don Epple- seem to replicate the expense of a three-pass to two-pass, reducing
heimer of Trane tells me that if primary-secondary crossover pressure drop through the
this sum remains below 50 deg-sec, bridge, but the difference is that chillers. But obviously, the con-
the control logic will not initiate a the recirculation pipe is sized to straints of the existing equipment
safety shutdown. This means: handle no more than about half a limit the flexibility to cope with
◆ Evaporator temperature may chiller’s design flow, and its func- the need to force more water
drop below freezing momentarily. tion is less likely to confuse the through the chillers. Further-
◆ The chiller’s capacity controls operator. more, retrofitting and adding
are allowed time to catch up with So the rationale for avoiding equipment to accommodate a
the load change. variable flow through chillers is, lower ∆T within the context of the
In fact, the sophistication of the in my opinion, no longer com- existing constant-flow design re-
control logic is such that Trane
feels confident in setting its low Flow meter
evaporator temperature set point
as low as 30 F.
The upshot of this improve-
ment, and to a lesser extent the By
Chiller Chiller
capacity control improvements, is
that chillers can survive a severe DP
upset condition in CHW flow
without tripping off line. In fact, VSD VSD
and this is really the proof of the
pudding, Mr. Eppleheimer says
that Trane routinely tests its
chillers to insure they can with- 2 Typical variable-flow CHW plant design.
stand a 50 percent drop in CHW
flow without tripping the low pelling. But even if constant flow sults in permanently locking in
evaporator temperature safety through chiller evaporators is no the higher CHW flow rate. A
cutout. (Other manufacturers longer essential for stable chiller retrofit of this kind effectively
have different control strategies operation, what’s wrong with it? throws in the towel on the quest to
for handling upsets in applied A constant-flow primary CHW find and fix the root causes of low
load. York’s chillers, for example, system with one nonvarying ∆T out in the system.
can accept an input that delays pump per chiller cannot respond So if not constant flow through
powering down of the chiller com- effectively to low ∆T syndrome. If the chillers, then what? A vari-
pressor upon a large drop in leav- CHR temperature returning from able-flow CHW pumping scheme
ing CHS temperature as long as the system is below design and can respond to low system ∆T if
the temperature does not fall be- cannot be raised, a central plant the pumps are selected for excess
low 36 F. Carrier’s low evaporator operator’s only option in respond- capacity. In fact, in my view, de-
temperature control overrides the ing to a call for more cooling ca- signers need to consider the de-
chiller capacity controller to close pacity is to energize more pumps sign ∆T for which they select the
compressor vanes should evapora- and more chillers.4 What would be continued on page 77
tor temperature approach 33 F. At preferable, of course, would be to
33 F, the safety shuts down the increase the CHW flow through 5
The maximum tube velocity recom-
machine.) mended in the ASHRAE Equipment
There is another benefit to con- 4
Assuming pumps are not ganged in a Handbook is 7 fps; most manufactur-
stant flow through chillers. The common header, of course. ers recommend 11 fps.

November 1996 HPAC Heating/Piping/AirConditioning 75


Chilled water plant design

continued from page 75


chillers as a target value and DP DP DP DP
then provide for the eventual-
ity that extra flow beyond the
design target may be re-
quired. In practice, this
VSD VSD VSD VSD
means: Chilled water plant CHS
◆ Selecting chiller evapo- Building 1 Building 2 Building 3 Building 4
rator tubes for tube velocities
not more than about 5.5 fps CHR
at design so that flow can be
increased up to twofold if nec-
essary.5
◆ Selecting pumps to over-
VSD VSD
pump the chillers. The
best scheme is to bank the
pumps and provide them 3 Distributed campus CHW pumping.
with VSDs. 6
With variable flow pumping most efficient pumping distribu- scheme. Distributed building
through the chillers, the crossover tion scheme. In Fig. 2, a single set pumps assume the function of
bridge and the secondary pumps of pumps handles the job of both the secondary pumps. Each
can be dispensed with, so a typical the primary and secondary pump is sized to deliver its build-
schematic layout for a simple pumps. But in a big system, a ing’s flow at just the head needed
building can look like Fig. 2. single set of pumps is not always to pump the building hydronic
Chillers are staged based on leav- desirable. If the pressure needed loads and draw the CHW
ing CHS temperature. When a to pump an entire campus is through the mains from the cen-
chiller can’t hold leaving CHS large, it’s advantageous to place tral plant. There are no decou-
temperature set point, a second a second set of pumps, and per- pling loops at the buildings, so no
chiller is energized. Pump speed haps even a third set, out in the CHW is bypassed. No balancing
is controlled by a differential pres- system to avoid imposing high valves are needed to eat up ex-
sure sensor situated across the pressure on the equipment close cess head since there is none.
hydronically farthest coil. A flow to the pumps’ discharge. Sec- Pump speeds are controlled by
meter and smart controller open a ondary pumping, as shown in VSDs receiving signals from dif-
bypass valve should flow through Fig. 1, can achieve this objective, ferential pressure switches at the
the chillers fall below the manu- but it’s not the most efficient end of the loop in each building.
facturer’s recommended mini- pumping scheme. That’s because Pumping horsepower saving
mum. the same head is imparted to all equals the sum:7
The advantages of this system CHW passing through the sec-
are: ondary pumps, whether it’s mak-
◆ It automatically responds to ing the short trip through the

i = 1, N − 1
CHW flow i ×
low ∆T by increasing flow through closest building or the longest ( Hbuilding N − Hbuilding i )/
chillers. trip through the hydraulically (3960 × η p )
◆ T h e r e ’ s o n l y o n e s e t o f most distant building. The extra
pumps. head imparted to CHW passing The primary pumps are VSD-
◆ Minimum chilled water flow through the closer buildings controlled, as before, and can op-
is pumped. must be wasted across balancing erate in series with the dis-
◆ T h e s y s t e m i s s i m p l e r ; valves and/or throttling valves at tributed pumps or be decoupled as
there’s no decoupling bridge. those buildings. Only the small shown in Fig. 3. If decoupled, the
fraction of the total CHW flow go- VSDs would be controlled to
Problem #3 ing to the most distant building maintain slightly positive flow
Secondary pumping is not the is produced without wasted en- from CHS to CHR in the crossover
ergy. bridge and not let flow through
6
Of course, oversizing the pumps and A better way to pump distant any chiller go below its minimum
balancing them down with a throt- loads is via distributed pumping, recommended value. Chillers are
tling valve is not an option unless you as illustrated in Fig. 3. Burt
routinely wear your shoes on the Rishel of Systecon gives credit to 7Assuming equal pump efficiencies for
wrong feet and when you tighten your Wilber Shuster of Cincinnati for building pumps and hypothetical sec-
belt, cut off your windpipe. first proposing this pumping ondary pumps.

November 1996 HPAC Heating/Piping/AirConditioning 77


Chilled water plant design

staged based on their ability to crossover bridges at the buildings, tors who run it.
maintain leaving CHS tempera- but if it does become a problem, The only unusual aspect of dis-
ture. the pumps and chillers can effec- tributed pumping is that it re-
The advantages of this system, tively deal with it. verses the typical pressure gradi-
besides minimizing pumping ◆ It reduces head pressure im- ent in the system. The CHS main
power, are: posed on equipment. is negative with respect to the
◆ It minimizes the potential for ◆ It’s simple and, more impor- pressure in the CHR main. Thus,
low system ∆T by eliminating tantly, looks simple to the opera- every load must be pumped.

In conclusion . . .
The traditional arguments for
desiring constant flow through
chiller evaporators no longer
carry much weight; most modern
microprocessor-based chiller con-
trols can effectively deal with up-
sets due to variable flow. More-
over, constant-flow primary
designs cannot respond to the
need to put more CHW through
chillers in the event that the dis-
tribution system returns low
CHW ∆T to the central plant.
A variable-flow design with
pumps either oversized and con-
trolled by VSDs or banked can re-
spond to low ∆T central plant
syndrome. Thus, for the same
reason that we as HVAC design-
ers provide freezestats upstream
of cooling coils, nonoverloading
motors to drive pumps and fans,
and tube pull space at chillers,
boilers, and air-handling units,
we need to design chilled water
plants that can anticipate the
possibility of low CHW ∆T and
respond to it. Therefore, I believe
it’s time to put primary-sec -
ondary pumping back into our
tool bag of applications to ad-
dress specific design situations
and adopt a new paradigm for
chilled water system design. HPAC

Bibliography
University of Wisconsin’s seminar
on Chilled Water Plant Design, orga-
nized by Harold Olsen.
Burt Rishel’s seminar speech, “Cur-
rent Trends in HVAC Water System
Design.”
Gil Avery’s article “Designing and
Commissioning of Variable Flow Hy-
dronic Systems,” ASHRAE Journal,
July 1993.
Al Utesch’s seminar speech at the
University of Wisconsin.

78 HPAC Heating/Piping/AirConditioning November 1996

You might also like