Professional Documents
Culture Documents
The Demise of The Primary-Secondary Pumping Paradigm For: Chilled Water Plant Design
The Demise of The Primary-Secondary Pumping Paradigm For: Chilled Water Plant Design
I
’ve got some bad news—the the load, which, in addition to re-
20-odd-year experiment with ducing the plant’s cooling output water systems and
primary-secondary design of capacity, wastes energy. The sys- recognizing the need to
chilled water plants hasn’t tem may be keeping the campus
panned out. If you’ve designed a cool, but you know it’s inefficient seek design solutions
large distributed chilled water and idling a lot of chiller capac- that can cope with or
system and monitored the opera- ity.
tion of the central plant, you al- The problem described above prevent it
ready know about the problems: has come to be known as “low ∆T
the ∆T of the chilled water central plant syndrome.” To my
(CHW) returning to the campus knowledge, every large chilled
plant is below the design value water plant serving distributed at the NASA Johnson Space Cen-
for which the chillers and pumps loads is afflicted with it to some ter” (HPAC, February 1995)1 de-
were selected—in fact, it’s way degree. The article “Trouble- scribes a typical situation. A cen-
below; the secondary CHW flow shooting Chilled Water Problems tral plant originally designed for
doesn’t vary a hoot; and the ex- a 16 F ∆T between the chilled wa-
pensive variable-speed drive 1
Wayne Kirsner authored the Febru- ter return (CHR) and chilled wa-
(VSD) purchased to vary the flow ary 1995 article cited above as well as ter supply (CHS) could only de-
of the secondary pumps was the article “What Caused the Steam velop an 8 F ∆T because of low
great for test and balance but System Accident that Killed Jack CHR temperature from the cam-
hasn’t done much since (besides Smith?,” HPAC, July 1995. pus. This meant not only that
twice as much CHW as originally
intended had to be pumped
VSD
around the 5-mile campus piping
loop but also that the seven 2000-
ton chillers in the central plant
couldn’t be loaded much beyond
half their capacity. Thus, opera-
Chiller Chiller tors were usually forced to run
Crossover twice as many chillers to meet
decoupler the campus load, and the fric-
Constant-flow tional loss in the mains due to the
pumps excessive CHW flow made it
1 Archetypal primary-secondary
CHW plant design.
tough to deliver sufficient CHW scheme that depends on system a severe upset, but it’s not far-
to hydraulically distant build- flow to gauge system load is virtu- fetched at all. Starting a second
ings. ally blind to load variation. chiller in a two-chiller plant,
The causes of low ∆T syndrome where identical chillers operate in
are not mysterious, but they are Problem #2 parallel, typically results in the
often pervasive and thus can be The primary loop is constant load to the active chiller being
hard to remedy. Low ∆T can be flow. Constant flow through halved. 2) In a constant-flow pri-
caused by dirty cooling coils, chillers is a highly desirable fea- mary loop designed to chill, say,
throttling valves with insuffi- ture of primary-secondary chilled 55 F CHR to 45 F CHS, a 50 per-
cient shutoff capability, reset water plant design, and most cent drop in load would manifest
CHS temperature, poorly con- chiller manufacturers still prefer itself in CHR temperature rising
trolled blending stations, and of and recommend it. I’ve been con- to 50 F. (This might occur because
course, CHW bypassing out in vinced, however, that most mod- approximately half the primary
the system. But most often, low ern chiller controls no longer re- flow of 45 F CHS is recirculating
system ∆T is the result of faulty quire constant flow to keep the through the crossover bridge to
controls and improperly adjusted chillers out of trouble. Let me ex- mix with the 55 F CHR from the
set points. This article, however, plain. system.) The 50 F CHR entering
is not about the causes of central When chiller vanes were con- the formerly fully loaded active
plant syndrome. It’s about ac- trolled by conventional pneu- chiller would initially be sub-
cepting that the problem exists in matic proportional controls, re- jected to the full cooling capacity
virtually every big distributed sponse time to changes in load of the chiller until its controls
chilled water system and then was necessarily slow and gradual could respond to decrease capac-
recognizing the need to seek de- to prevent overshoot and hunting ity. The chiller would thus tend to
sign solutions that can cope with as the chiller controls tried to drive the entering 50 F CHW
it, if not prevent it. achieve leaving CHS set point. down toward 40 F.
So why can’t a standard pri- Hence, chiller capacity controls Compare this upset condition to
mary-secondary chilled water de- would lag behind a sudden load a variable-flow configuration.
sign cope with low CHW ∆T? change. If the change was a drop Starting a second equal CHW
in load, the chiller would overcool pump could cut CHW flow through
Problem #1 the leaving CHW, dropping it be- the active chiller roughly in half.3
The primary-secondary control low set point until capacity con- The active chiller would initially
scheme is “blinded” by low ∆T trol vanes could react to reduce continue to try to apply its full out-
central plant syndrome. Fig. 1 de- chiller refrigerating capacity. If put capacity to half the mass flow,
picts what I would describe as the drop in load was sharp thereby doubling the ∆T of CHW
the archetypal primary-sec - enough, the chiller’s low evapora- passing through it—i.e., it would
ondary chilled water schematic tor temperature safety would tend to drive 55 F CHR down to 35
configuration. The primary fea- knock the chiller off line, requir- F. This is pretty close to freezing. If
ture of the configuration is the ing a manual reset to restart the the design ∆T was larger, the CHW
decoupled primary and sec - chiller. This is a situation to be would be driven down below freez-
ondary loops, which allow con- avoided. ing. In either case, a simple low
stant flow through the chillers Now consider the response of a evaporator temperature sensor
while permitting varying flow in chilled water plant designed for would likely cause the chiller to
the system to save pumping en- constant flow versus one designed trip off line to protect it from freez-
ergy. Chillers are staged on and for variable flow in the event that ing. The constant-flow chiller, in
off based on CHW flow through load across a fully loaded chiller comparison, whose leaving CHS
the crossover bridge (although suddenly dropped in half. (This is temperature dips only half as far,
the sensor may be elsewhere). would probably remain on line. For
The sole indicator of system load, this reason alone, one can easily
2
upon which control of the chillers For example, in a variable-flow understand why chiller manufac-
and pumps depends, is chilled plant, flow through the active chiller
water flow. will be cut roughly in two as the sec-
3
ond chiller’s pump instantly usurps Assuming immediate system control
In a plant with low ∆T syn-
half the flow. In a primary-secondary valve response and the absence of cen-
drome, CHW flow is no longer plant, approximately half the total tral plant syndrome. If control valve
much of an indicator of load. The primary CHW flow recirculates response were slow or the system were
amplitude of flow variation is just through the crossover bridge and, once afflicted with central plant syndrome,
a fraction of the amplitude of load the second chiller’s compressor has be- flow would not suddenly fall to half,
variation. Fundamentally then, a gun outputting CHW, mixes with sys- and thus the upset condition would be
primary-secondary control tem secondary CHR to halve its ∆T. far less traumatic.
staged based on their ability to crossover bridges at the buildings, tors who run it.
maintain leaving CHS tempera- but if it does become a problem, The only unusual aspect of dis-
ture. the pumps and chillers can effec- tributed pumping is that it re-
The advantages of this system, tively deal with it. verses the typical pressure gradi-
besides minimizing pumping ◆ It reduces head pressure im- ent in the system. The CHS main
power, are: posed on equipment. is negative with respect to the
◆ It minimizes the potential for ◆ It’s simple and, more impor- pressure in the CHR main. Thus,
low system ∆T by eliminating tantly, looks simple to the opera- every load must be pumped.
In conclusion . . .
The traditional arguments for
desiring constant flow through
chiller evaporators no longer
carry much weight; most modern
microprocessor-based chiller con-
trols can effectively deal with up-
sets due to variable flow. More-
over, constant-flow primary
designs cannot respond to the
need to put more CHW through
chillers in the event that the dis-
tribution system returns low
CHW ∆T to the central plant.
A variable-flow design with
pumps either oversized and con-
trolled by VSDs or banked can re-
spond to low ∆T central plant
syndrome. Thus, for the same
reason that we as HVAC design-
ers provide freezestats upstream
of cooling coils, nonoverloading
motors to drive pumps and fans,
and tube pull space at chillers,
boilers, and air-handling units,
we need to design chilled water
plants that can anticipate the
possibility of low CHW ∆T and
respond to it. Therefore, I believe
it’s time to put primary-sec -
ondary pumping back into our
tool bag of applications to ad-
dress specific design situations
and adopt a new paradigm for
chilled water system design. HPAC
Bibliography
University of Wisconsin’s seminar
on Chilled Water Plant Design, orga-
nized by Harold Olsen.
Burt Rishel’s seminar speech, “Cur-
rent Trends in HVAC Water System
Design.”
Gil Avery’s article “Designing and
Commissioning of Variable Flow Hy-
dronic Systems,” ASHRAE Journal,
July 1993.
Al Utesch’s seminar speech at the
University of Wisconsin.