Professional Documents
Culture Documents
GENERATOR
Presented By:
NIAZ AKHTAR
GTE-ELECT.
Contents
Types of Controls associated with Generator
Operating modes of Generator
Excitation System Basics
Types of Excitation System
Automatic Voltage Regulator
PRISMIC A10 AVR and types
Protections Associated with AVR
Synchronous Generator Controller
Two types of controls associated with
synchronous generator:
1. AVR/ Excitation system Control
(Voltage, Power factor and MVAr are Controlled by AVR)
2. Governor/Turbine Control
(Speed, Frequency and MW output is controlled by
Governor)
Generator Operating Modes
Operating Modes of
Generator
Isochronous Vs Droop
Sharing of Load
GENERATOR LOADING IN VARYING LOAD
LARGE GRID DISTRIBUTION
Excitation System of Generator
Excitation
The injection of dc in the field winding to produce magnetic field is
called excitation.
Purpose of Excitation
The purpose of excitation system is to monitors line voltage and
current constantly and produce proper excitation voltage
necessary to maintain terminal voltage constant under all
conditions of generator operation (no load, full load etc).
At no load, the excitation system should only supply that much
amount of volts necessary to maintain the terminal voltage of
generator constant. when a sudden load is applied to a generator,
it’s terminal voltage decreases slightly, therefore an efficient
excitation system senses the voltage dip and increase the
excitation volts immediately and thus maintains the terminal
voltage.
Excitation System of Generator
Excitation System
The system which controls the excitation in order to maintain
constant terminal voltage under normal operating conditions,
to vary the generation of reactive power and to maintain
voltage under fault conditions.
Protection
System and
Limiting
Power System
Stability
Voltage
Stability
Control
System for
MW,
Frequency
Control
System for
MVAr, p.f
PRISMIC A10 AVR
The PRISMIC A10 Excitation Controller is designed to control the
excitation of a brushless generator. It is a microprocessor-based
device that incorporates a wide range of features. The A10 is
normally supplied on a mounting plate that contains the auxiliary
equipment such as field suppression contactor, field suppression
resistor etc.
Region 1
Output power is limited by stator current
Region 3
Output power is limited by Core heating
Region 2
Output power is limited by Field Current
Under Excitation Limiter
The minimum excitation limiter (MEL) is unique in
that it is not a protective relay, but rather a control
function integral to the automatic voltage regulator
(AVR) circuitry. It acts to limit VAR flow into the
generator. During normal operation, the AVR
maintains generator voltage at a preset value. When
system conditions attempt to produce VAR flow into
the generator in excess of the MEL set point, the MEL
activates, overriding the AVR set point to increase
terminal voltage which reduces the VAR in-flow. The
voltage increase continues until VAR flow is reduced
below the MEL setting.
Limits on Leading VAR Operation
Two limits are imposed on Under Excitation
Limiter
line of the QCC function built in the AVR. For each of the
AVR’s, the final voltage reference is on a straight line starting
at the set point and drooping with the measured MVAr’s (Q).
At full MVAr of the generator, the line has drooped with 4%.
Reactive Droop Characteristics
Interesting Behavior of GTG AVR by
changing load on One of GTG
GTG-A GTG-B
S=√(P2+Q2) p.f=P/S
THANK YOU
Voltage Rise above 11 KV
Background
On March 14 when GTG-A was running alone at 14 MW
for first time at our complex. GTG-A terminal voltage
raised to 11.2 KV and they were not coming down to 11.0
KV by decreasing excitation while AVR-B was selected.
Following indications were observed on AVR-B:
LED#1 “AUTO/MANUAL” blinks (with 2 consecutive
pulses).
LED#2 “UE LIM” blinks (with on pulse),
frequently.
Remedy
To find the cause the problem was
communicated to Mr. Cock Huizer and
different facts were cleared.
There was a problem with the measurement of
the excitation current. All reading of this
current measured were too low. e.g.
Sample Calculations
11.1KV, 547.3A, 0.84PF, 8.81MW, 5.74MVAR,
Excitation Voltage & Current: 22V & 1.2A
MVA = sqrt(8.81^2 + 5.74^2) = 10.51 MVA
pf = 8.81 MW /10.51 = 0.84
P-rated = 0.8 x 26.25 MVA = 21 MW ==> 8.81 MW =
42%
When we look at the V-curve of the generator, we
find for 42% power and p.f. = 0.85 an excitation
current of 3.8 A.
So the conclusion was that meter on GEP panel
showing wrong value of current.
V-Curve of Synchronous Generator
Cause of UE LIM blinking
Cause No 1. False connection of current transformer
When a generator is running in parallel with the (infinite bus) public grid and the excitation is too low,
there will be a leading current.
The under excitation limiter and under excitation monitor in fact look if the leading current does not
pass a set limit. The set point of this limit is 0,21 A In our case this current is measured on the
secondary side of the 2000:1 ratio CT. Therefore 0,21 A setting equals 420 A generator current.
Although we are running with one generator not connected to the public grid, the UE limiter and
monitor are apparently still enabled.
In our system if we suppose the load p.f will have been about 0,82 lagging. At 14 MW and a p.f of 0,82
lagging, the lagging current would be:
14MW at cosPhi = 0,82 gives 17,07 MVA and with S^2 = P^2 + Q^2 we find Q = 9,77 MVAr ,
which gives a lagging current of 512 A.
This current should never give activity of the UE limiter. Unless the sign of the measured current on
the AVR is reversed and the AVR sees the actual lagging current as leading current. The value of 512A
is above the threshold of 420 A.
The result of the activity of the limiter is increasing the excitation (trying to stop the too low
excitation). The limiter will take over from the setting of the operator. So far it looks like the behavior
can be explained from a false connection of current transformer =50+LSC-T6.2.
But the same secondary current of current transformer =50+LSC-T6.2 flows through both AVR-A and
AVR-B. The idea was that perhaps on AVR-A the short circuit on terminals A1:D30 to D31 was not
removed, and AVR-A would have a measured current of 0 Amps.
Results after communication with HMI
Software
S. No. Measurement AVR-A Remarks AVR-B Remarks
Description
1 Line Volt 111.35V 111.35V
7 VA 17.8VA 18VA
GTG-A was running with AVR-A selected 4MW and Volts =11KV, Ampere = 248A, Power Factor = 0.83pf.
Analysis of values shown on HMI
AVR-A is showing a lagging power factor as it should be with the
actual load on the generator.
AVR-A and AVR-B are showing very similar line Amps, and line
Volts, but the power factor of AVR-B is leading and different.
There is only one CT to measure the current for both AVR's. so
the only possibility for a wrong connection would be a reversal.
In that case the power factor would change from lagging to
leading, but with the same value.
As the value also changed, there must be a wrong connection in
the three phase voltage measurement.
The terminals E214 E234 & E254 are not in correct sequence and
they are connected as E214 E254 & E234 .So they should be
corrected.
Correction of signals of V.T going to AVR-
B
Complete loop was checked for phase correction
instead of changing only the terminals at AVR-B.
On checking it was found that terminals not only
at AVR-B are wrong but also in LSS (Line Side
Cubicle Secondary) terminals are in reverse
order but still the phase sequence going to AVR-
B is wrong because of which it was sensing
incorrectly and showing leading p.f. )
In fact voltage sequence going to AVR-A is RYB
whereas it was YRB for AVR-B.
Results shown by HMI Software after
correction
S. No. Measurement AVR-A Remarks AVR-B Remarks
Description
1 Line Volt 111.00V 110.9V
7 VA 19.8VA 20.0VA
GTG-A was running with AVR-A selected 4.6MW and Volts =11KV, Ampere = 288A, Power Factor = 0.84pf.
Response of Mr. Cock after correction of
problem in AVR
The main problem you noticed was that the voltage became high
and could not be lowered using the lower command. Because of
the twisted wiring AVR-B measured a leading power factor. The
sign of the measured power factor was inversed.
When running with a single generator on the load the plant
forms, this will give lagging VAr's. The VAr' s increase with the
load power. Therefore when below say 15 MWatt the VAr's will
be below the set limit of the Under Excitation Limiter. even with
the inverted sign.
Only above about 15 MW the VAr' s will be sufficient to activate
the Under excitation limitter (when the measured sign is inversed
becauseing of the twisted wiring) With the corrected wiring the
correct lagging power factor is seen by the AVR and the Under
Excitation Limiter will remain NOT active.
THANK YOU