THE ABC OF SWITCHBOARD MAINTENANCE

By Mark Betcher Blacktown City Switchboards

National Electrical Switchboard Manufacturers Association

DEFINITIONS
Maintenance a combination of acts carried out to retain an item in or restore it to, an acceptable condition . in, to condition Acceptable condition the condition in which an item is able to perform its required function and/or meet the e eva t specification. relevant spec cat o .

National Electrical Switchboard Manufacturers Association

DEFINITIONS
Non-routine maintenance Preventative maintenance Post fault maintenance Repair or corrective maintenance Routine maintenance

National Electrical Switchboard Manufacturers Association

WHY MAINTAIN
Economics Responsibility AS3439.1:2002 Clause 5.3 It is the responsibility of the owner of the ASSEMBLY to institute a system of maintenance. The manufacturers recommendations should be addressed, together with the recommendations of AS2467 in a planned AS2467, preventative maintenance programme. This will minimise the risk of injury or breakdown and the f j y consequent human suffering and/or loss of supply.

National Electrical Switchboard Manufacturers Association

WHAT & HOW TO MAINTAIN


The Metalwork

National Electrical Switchboard Manufacturers Association

WHAT & HOW TO MAINTAIN


The Busbar System y

National Electrical Switchboard Manufacturers Association

WHAT & HOW TO MAINTAIN


The Busbar System y

National Electrical Switchboard Manufacturers Association

Main Switchboard
CHASSIS CH3 - 48 POLE, DIN TYPE, 18mm PITCH LINK RED PHASE TO BE REMOVED WHEN PFC UNIT IS CONNECTED QM1 200A 250A INCOMING CABLES 8 x 1c 300mm FED FROM EXISTING INTEGRAL SUB No 8615 SERVICE PROTECTION DEVICE FACILITY TO BE LOCKED IN 'ON' & 'OFF' POSITIONS. DO NOT SWITCH OFF IN CASE OF FIRE
3 3 3

CT2
3

SPD - 1250A SET @ 1250A

CT1 PF1

QM2 100A 100A

PF2
3 3

DISTRIBUTION BOARD DB-WAREHOUSE BEHIND DESPATCH OFFICE S/E WALL

CHASSIS CH1 1250A 18 POLE 1

QM3 100A 100A

SD1

DISTRIBUTION BOARD DB-ENGINEERING N/E WALL BEHIND

CT METER PANEL MOUNTED REMOTE BY OTHERS

M1 MTB1

QM4 100A 100A

DISTRIBUTION BOARD DB-UPS NORTH WALL ADMIN

FT1 P1

3 3

SPARE SPACE FOR 3P CB UP TO 250A QM6 300A 630A

POWER FACTOR CORRECTION UNIT PFC1 ADJACENT

CHASSIS CH2 1250A 24 POLE


3 3 3 3 3 3 3 3

QM14 300A 400A DISTRIBUTION BOARD DB-CENTRE CENTRE WAREHOUSE SPARE SPACE FOR 3P CB UP TO 630A SPARE SPACE FOR 3P CB UP TO 630A

QM11 200A 250A AIR CONDITIONING SUB BOARD A/C PLANTROOM NORTH

QM10 200A 250A DISTRIBUTION BOARD DB-OFFICE NORTH WALL ADMIN

QM9 200A 250A DISTRIBUTION BOARD DB-FAR ELECTROBAR WEST WALL SPARE SPACE FOR 3P CB UP TO 250A SPARE SPACE FOR 3P CB UP TO 250A

SINGLE LINE DIAGRAM

National Electrical Switchboard Manufacturers Association

Service Protection Device

National Electrical Switchboard Manufacturers Association

Service Protection Device

National Electrical Switchboard Manufacturers Association

Revenue CTs

National Electrical Switchboard Manufacturers Association

Surge Diverter

ATS /MTS

National Electrical Switchboard Manufacturers Association

Outgoing Circuit Breakers

National Electrical Switchboard Manufacturers Association

Motor Control Centre


01 02 03

TO POINT OF ATTACHMENT

METER PANEL

Q1M 125A CON NT'D ON LINE 31


60

TO LIGHT & POWER DB

Q2M 50A

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

F1

F2

F3

Q100 6A

QA1 20A

QB1 20A
A

QC1 20A
A

QD1 20A
A

QE1 20A
A

QF1 20A

MAIN EARTH

MEN LINK

PC2 SUPPLY MONITORING CIRCUIT


REF. DRG. 0602033-203

PD2 KC1 FC1


REF. DRG. 0602033-206

PE2 KD1 FD1


REF. DRG. 0602033-206

PF2 KE1 FE1


REF. DRG. 0602033-206

VSD STARTER
REF. DRG. 0602033-204

VSD STARTER
REF. DRG. 0602033-204

KF1 FF1
REF. DRG. 0602033-206

N NEUTRAL EARTH
UA VA WA UB VB WB UC VC

WC

UD

VD

WD

UE

VE

WE

UF

VF

WF

Q1M
AUX

0000

b 0000 TO PLC .

00C

M
INFLUENT PUMP No.1 1.1 kW 2.6 A "A"

M
INFLUENT PUMP No.2 1.1 kW 2.6 A "B"

M
ASPIRATING AERATOR No.1 2.2 kW "C"

M
ASPIRATING AERATOR No.2 2.2 kW "D"

M
WAS PUMP 0.75 kW "E"

M
WAS STORAGE TANK TRANSFER PUMP 3.5 kW "F"

00C

SCA No.1

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

SCA No.1

CONT'D FROM LINE 30

QG1 20A
A A

QH1 20A

QJ1 20A

QK1 20A
A

QL1 20A
A

QM1 20A

QN1 20A

QP1 20A

QQ1 20A

QR1 20A

PG2 KG1 FG1


REF. DRG. 0602033-207

PH2 KH1 VSD STARTER


REF. DRG. 0602033-205

PL2 KL1

PM2 KM1 KN1


REF. DRG. 0602033-208

KP1
REF. DRG. 0602033-208 UP VP

KQ1
REF. DRG. 0602033-208 UQ VQ

KR1
REF. DRG. 0602033-208 UR VR

VSD STARTER
REF. DRG. 0602033-205

REF. DRG. 0602033-207

REF. DRG. 0602033-207

REF. DRG. 0602033-207

UN

VN

UG

VG

WG

UH

VH

WH

UJ

VJ

WJ

UK

VK

WK

UL

VL

WL

UM

VM

WM

SN2
FIELD ISOLATOR OFF ON

SP2
FIELD ISOLATOR OFF ON

SQ2
FIELD ISOLATOR OFF ON

SR2
FIELD ISOLATOR OFF ON

M
EFFLUENT REUSE PRESSURE PUMP 0.75 kW "G"

M
SUPERNATANT RETURN PUMP 1.1 kW 2.6 A "H"

M
EFFLUENT PUMP No.1 1.1 kW 2.6 A "J"

M
EFFLUENT PUMP No.2 1.1 kW 2.6A "K"

M
LPGS PUMP UNIT 0.75 kW 1.8 A "L"

M
WATER SUPPLY PRESSURE PUMP 1.5 kW 3.4 A "M"

M
ALUM DOSING PUMP No.1 0.05 kW 0.42 A "N"

M
ALUM DOSING PUMP No.2 0.05 kW 0.42 A "P"

M
SODA ASH DOSING PUMP No.1 0.05 kW 0.42 A "Q"

M
SODA ASH DOSING PUMP No.2 0.05 kW 0.42 A "R"

National Electrical Switchboard Manufacturers Association

CONT'D ON LINE 61

Motor Control Centre

National Electrical Switchboard Manufacturers Association

Motor Control Centre

National Electrical Switchboard Manufacturers Association

Power Factor Correction Unit

National Electrical Switchboard Manufacturers Association

Power Factor Correction Unit

National Electrical Switchboard Manufacturers Association

Power Factor Correction Unit

National Electrical Switchboard Manufacturers Association

WHEN TO MAINTAIN
The effect on business Form of Construction Location Environment Duty

National Electrical Switchboard Manufacturers Association

WHEN TO MAINTAIN
AS 2467 clauses 4 4 3 4 4 4 & 4 4 5 4.4.3, 4.4.4 4.4.5 Inspect 12 months Examine 5 years Overhaul 15 years

National Electrical Switchboard Manufacturers Association

CONCLUSION

National Electrical Switchboard Manufacturers Association

Predictive maintenance

National Electrical Switchboard Manufacturers Association

Specialist Companies

National Electrical Switchboard Manufacturers Association

Specialist Companies

National Electrical Switchboard Manufacturers Association

Specialist Companies

National Electrical Switchboard Manufacturers Association

Specialist Companies

National Electrical Switchboard Manufacturers Association

You might also like