Change Settings With Configuration Switches
Change Settings With Configuration Switches
Page 1 of 1
show the entry list Change settings with configuration switches Display part number
QUESTION: Why are the DIP switches configuration changes not accepted? ANSWER: All configuration changes of DIP or turnswitches will be read at S7-200 extension modules respectively on the RS232/PPI Multi-Master cable after power return. This means that, if the settings of the switches were changed, the power supply has to be switched off and on again before the new settings will be accepted. Following modules or components are affected: Module EM 231 Analog input module EM 231Analog input thermocouple module EM 231 Analoginput-RTD module EM 235 Analoginput/Analogoutput module EM 277 Profibus-DP module EM 241 Modem module RS232/PPI Multi-Master cable MLFB 6ES7 231-0HCxx-0XA0 6ES7 231-7PD2x-0XA0 6ES7 231-7PB2x-0XA0 6ES7 235-0KDxx-0XA0 6ES7 277-0AA2x-0XA0 6ES7 241-1AA22-0XA0 6ES7 901-3BC30-0XA0