TEST REPORT FOR T/F BUSHING CURRENT TRANSFORMER

DATE : DATE : 12/10/2011 CLIENT : M/s. CETHAR VESSELS LTD PROJECT: ACB India Ltd 2X135MW TPP, Kasaipali, Korba.

Page No
Sheet No 1 of 2

1. Equipment Details Make Type CT. Ratio Class Mfg Year

: : : : 7530.88/2 A : 3 : 2010

2. Location & Feeder Name: TRANSFORMER BUSHING CT LV 3. General Inspection : OK

4. Insulation Resistance Test: (Using 500VMegger)

Circuit Ref Core to Earth

V Ph

5. Polarity Test: (P1 TOWARDS BUSHING)

Circuit Ref Core 1

V Ph OK

Test Performed by VOLTECH Name :S.MUTHUKUMAR Designation: T&C Er. Signature & Date

Witnessed by ABB Name: VIVEKBAGLE Designation Signature & Date

Witnessed by CVL Name: PRAVEENKUMAR Designation Signature & Date

Witnessed by ACB (I) Ltd Name Designation Signature & Date

TEST REPORT FOR T/F BUSHING CURRENT TRANSFORMER


DATE : DATE : 12/10/2011 CLIENT : M/s. CETHAR VESSELS LTD PROJECT: ACB India Ltd 2X135MW TPP, Kasaipali, Korba.

Page No
Sheet No 2 of 2

6. Ratio Test: Circuit Ref CT Ratio Applied Current in primary (A) 376.5 753 1129.5 Measured Current in secondary (A) V Ph 0.097 0.197 0.294

Core 1 7530.88/2 A

7. Winding resistance tests:

Circuit Ref 1S1 -1S2

V Ph 6.6

8. Remarks

Test Performed by VOLTECH Name :S.MUTHUKUMAR Designation: T&C Er. Signature & Date

Witnessed by ABB Name: VIVEKBAGLE Designation Signature & Date

Witnessed by CVL Name: PRAVEENKUMAR Designation Signature & Date

Witnessed by ACB (I) Ltd Name Designation Signature & Date