You are on page 1of 2

VOLTECH ENGINEERS PVT. LTD.

TEST REPORT FOR CURRENT


TRANSFORMER
CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013
PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 1 of 2

Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL
Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu
Designation : Senior
commissioning Engineer
Designation : Manager Electrical Designation :Manager E&I
Signature &
Date
Signature &
Date
Signature &
Date

1. Equipment Details

Make : Schneider Electric
Sl. No. : 12/023936
Ratio : 50/1A
VA : 15
Class : 5P10
Terminal : 1S1-1S2
Mfg year : 2012

2. Feeder Name : Generator Neutral Side

3. Location : NGR Panel

4. General Inspection : Ok




5. Insulation Resistance Measurement: ( Using 500V Megger )


TERMINALS
Values
Neutral CT
Primary Earth 601 M
Primary Secondary 571 M
Secondary Earth 221 M










6. Secondary Winding Resistance: Temperature: 29C

VOLTECH ENGINEERS PVT. LTD.
TEST REPORT FOR CURRENT
TRANSFORMER
CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013
PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 2 of 2

Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL
Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu
Designation : Senior
commissioning Engineer
Designation : Manager Electrical Designation :Manager E&I
Signature &
Date
Signature &
Date
Signature &
Date

Core Between Terminal Values
Core 1 1S1-1S2 1.68

7. Polarity Test: (By connecting positive battery terminal P1 side and Negative battery terminal P2 side
with 1.5V DC supply)
Core Between Terminal Values
Core 1 1S1-1S2 OK

8. Ratio Test:
















9. Remarks: CT check found OK

Primary Applied
Current (A)
Measured Secondary Current in (A)
20 0.203
40 0.391
60 0.693
80 0.804