TRANSFORMER CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013 PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 1 of 2
Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu Designation : Senior commissioning Engineer Designation : Manager Electrical Designation :Manager E&I Signature & Date Signature & Date Signature & Date
1. Equipment Details
Make : Schneider Electric Sl. No. : 12/023936 Ratio : 50/1A VA : 15 Class : 5P10 Terminal : 1S1-1S2 Mfg year : 2012
2. Feeder Name : Generator Neutral Side
3. Location : NGR Panel
4. General Inspection : Ok
5. Insulation Resistance Measurement: ( Using 500V Megger )
TERMINALS Values Neutral CT Primary Earth 601 M Primary Secondary 571 M Secondary Earth 221 M
6. Secondary Winding Resistance: Temperature: 29C
VOLTECH ENGINEERS PVT. LTD. TEST REPORT FOR CURRENT TRANSFORMER CLIENT : M/S .RUKMANI POWER AND STEEL LTD DATE :25.09.2013 PROJECT : 10MW POWER PLANT AT KHARSIA Sheet No.: 2 of 2
Test Performed by: VEPL Witnessed by: RPSL Witnessed by: RPSL Name : Mr. T.Balaji Name :Mr.K.K.Banerjee Name :Mr.O.P.Sahu Designation : Senior commissioning Engineer Designation : Manager Electrical Designation :Manager E&I Signature & Date Signature & Date Signature & Date
Core Between Terminal Values Core 1 1S1-1S2 1.68
7. Polarity Test: (By connecting positive battery terminal P1 side and Negative battery terminal P2 side with 1.5V DC supply) Core Between Terminal Values Core 1 1S1-1S2 OK
8. Ratio Test:
9. Remarks: CT check found OK
Primary Applied Current (A) Measured Secondary Current in (A) 20 0.203 40 0.391 60 0.693 80 0.804