RESIDENTIAL ELECTRICAL LOAD WORKSHEET

O W N E R: A D D R E S S:

LIGHTING LOAD Art. 220 - 3(a) Total square footage of habitable living area : 2 @ 3 watts per sqft = @ 1500 watts each = @ 1500 watts each = @ 1500 watts = Lighting Load Subtotal = Table 220 - 11 First 3000 watts of lighting load subtotal: Remainder from 3001 to 120,000 watts: Remainder over 120,000 watts: @ 100% = @ 35% = @ 25% = 3000 watts watts watts watts watts 3000 watts watts watts watts

Art. 220 - 16(a) Two small appliance circuits @ 1500 watts each : Art. 220 - 16(a) Additional small appliance circuits each : Art. 220 - 16(b) Laundry circuit (washing machine) @ 1500 watts ea.

LIGHTING LOAD TOTAL =

APPLIANCE LOAD Art. 220 - 17 Disposal: Microwave: Compactor: Dishwasher: Food Center: _________________: _________________: X X X X X X X 600 1500 1200 1200 600 watts = watts = watts = watts = watts = watts = watts = Appliance Subtotal = watts watts watts watts watts watts watts watts

APPLIANCE TOTAL Art. 220 - 17 Appliance subtotal: watts X = watts

[ Less than 4 units @ 100%; 4 or more units @ 75% ]

Page 2
O W N E R: A D D R E S S:

ELECTRIC CLOTHES DRYER Art. 220 - 18 5000 watts OR nameplate rating: [ Whichever is larger ] DRYER TOTAL = watts

WATER HEATER Art. 220 - 3(b) @ Nameplate rating :

(if electric) WATER HEATER LOAD = watts

HOUSEHOLD COOKING EQUIPMENT Table 220 - 19 Cooking Units - Includes ranges, wall mounted ovens, countertop units, and other household cooking units. Number of Units ONE unit use TWO units use THREE units use FOUR units use FIVE units use 8,000 watts: 11,000 watts: 14,000 watts: 17,000 watts: 20,000 watts: COOKING TOTAL = watts

SPACE HEATING / AIR CONDITIONING Art. 220 - 4(a) Art. 220 - 21 Art. 220 - 15 Air conditioner nameplate rating [ @ 125% ] : OR [ Whichever is larger ] Electric heat nameplate rating [ @ 100% ] : HEAT PUMP Art. 220 - 4(a) Art. 440 - 33 Art. 220 - 15 Largest condensing unit nameplate [ @ 125% ] : AND Supplementary heat (resistance) [ @ 100% ] : ADDITIONAL HVAC EQUIPMENT Art. 440 - 33 Condensing units or A/C's : > watts X 100% = SPACE HEATING/AIR CONDITIONING TOTAL = watts watts watts X 100% = watts watts X 125% = watts watts X 125% = watts

Page 3
O W N E R: A D D R E S S:

OPTIONAL EQUIPMENT Art. 220 - 3(b) Art. 430 - 24 SWIMMING POOL and/or SPA: > Largest motor nameplate : watts X 125% = watts X 100% = watts X 100% = POOL/SPA TOTAL = watts watts watts watts

Remaining motor(s) nameplate(s) : Lights and other misc. equipment :

Art. 220 - 3(b) 1.

WELDERS, KILNS, ETC. Name or description of equipment : @ rated nameplate : watts X 100% = watts

2.

Name or description of equipment : @ rated nameplate : watts X 100% = watts

3.

Name or description of equipment : @ rated nameplate : watts X 100% = MISCELLANEOUS EQUIPMENT TOTAL = watts watts

TOTAL DEMAND ON SYSTEM Art. 220 - 10 Sum of all totals : LIGHTING LOAD TOTAL = APPLIANCE TOTAL = DRYER TOTAL = WATER HEATER TOTAL = COOKING TOTAL = SPACE HEATING/AIR CONDITIONING TOTAL = POOL/SPA TOTAL = MISCELLANEOUS EQUIPMENT TOTAL = TOTAL LOAD FOR DWELLING= watts watts watts watts watts watts watts watts watts

Page 4
O W N E R: A D D R E S S:

MAIN SERVICE SIZING Art. 220 - 2 TOTAL LOAD DIVIDED BY: volts = Amps

[ NOTE: For 120/240 Volt systems use 240 volts; for 120/208 Volt systems use 208 volts ]

Art. 220 - 10 Table 310 - 16 Table 250 - 94

MINIMUM SERVICE SIZE SERVICE ENTRANCE CONDUCTORS GROUNDING ELECTRODE CONDUCTOR

AMPS AWG, Cu, AWG Copper AWG, Al.

OPTIONAL CALCULATION FOR DWELLING UNIT Table 220 - 30 100% of the nameplate rating(s) of the air conditioning 100% of the first 10 kVA of all other load 40% of the remainder of all other load TOTAL OPTIONAL LOAD Art. 220 - 2 TOTAL OPTIONAL LOAD: DIVIDED BY: watts watts watts watts volts = Amps

[ NOTE: For 120/240 Volt systems use 240 volts; for 120/208 Volt systems use 208 volts ]

Art. 220 - 10 Table 310 - 16 Table 250 - 94

MINIMUM SERVICE SIZE SERVICE ENTRANCE CONDUCTORS GROUNDING ELECTRODE CONDUCTOR

AMPS AWG, Cu, AWG Copper AWG, Al.

Revised 6/24/03