Guaranteed technical particulars against tender enquiry no.

Sr.No. Particulars 1 Name of the manufacturer & Country 2 Applicable Standard 3 Maximum continuous rating 4 5 6 7 8 No load voltage ratio at Principal (Nominal) tap Rated frequency No. of Phase Type of cooling Connections i) H.V Winding ii) L.V Winding Vector Symbol Tappings a) Range b) Number of steps c) Variation of voltage in each step i) Temperature rise under normal operating condition above ambient temperature a) Top Oil b) Windings ii) Maximum hot spot temperature of Copper Winding 12 Magnetising current referred to H.V. at rated frequency a) At 90% rated Voltage b) At 100% rated Voltage c) At 110% rated Voltage 13 Power factor magnetising current at 100% rated Voltage and frequency. 14 No load current at rated voltage and rated frequency % % % 1% (with IS Tolerance) 2% (with IS Tolerance) 4% (with IS Tolerance) 0.03 (APPROX) Unit Value Prime Electric Limited, Nellore, India IS-2026, 2099, 335, 6600 10 33/11 50 3 ONAN Delta Star Dyn 11 Kv + 5% to - 15% 16 Steps & 17 Positions 1.25%

MVA KV Hz

9 10

11

o o o

C C C

40 45 98.5 oC over and yearly weighted Ambient temperature of 32 oC (calculated as per IS-2026)

Amps

2% (with IS Tolerance)

Sr.No. Particulars 15 No load loss KW at rated frequency and voltage a) At lowest tap b) At principal tap c) At highest tap 16 Load loss in kW at 75 oC at rated output and frequency a) At lowest tap b) At principal tap c) At highest tap Percentage regulation at full o load at 75 C a) At unity power factor b) At 0.8 power factor lagging

Unit

Value

kW kW kW

7 (Max) 7 (Max) 7 (Max)

kW kW kW

65 (approx) 56.5 (max) 55 (approx)

17

0.91 5.65

18

Efficiencies at 75 oC a) At full load i) At unity power factor ii) At 0.8 power factor lagging b) At 3/4 full load i) At unity power factor ii) At 0.8 power factor lagging c) At 1/2 full load i) At unity power factor ii) At 0.8 power factor lagging 19 Impedance voltage on rated MVA base at rated current and frequency for the pricipal tapping at 75C 20 a) Reactance voltage at rated current and frequency for the principal tapping at 75C

% %

99.37 99.21

% %

99.49 99.36

% % %

99.58 99.48