External Alarm Configuration Procedure

1 Introduction to Hardware Ports and Alarm Cables


1.1 Monitoring Ports on the BBU The UPEU on the BBU has two Boolean input ports, as shown in the following figure:

Boolean input ports on the UPEU in the upper part of the BBU:

EXT-ALM0: port for Boolean inputs 0 to 3 EXT-ALM1: port for Boolean inputs 4 to 7

The BBU supports a maximum of 16 Boolean inputs. Each UPEU supports eight Boolean inputs. The BBU is configured with one UPEU in the lower part by default.

2011-03-17

Huawei Confidential

Page 1 of 5

External Alarm Configuration Procedure

1.2 Color Definitions for the Boolean Alarm Cables on the BBU
RJ45 Pin/Color 1 Orange white 2 Orange 3 Green white 4 Blue 5 Blue white 6 Green 7 Brown white 8 Brown Recommends Cable Leading Sequence for the BBU Boolean input 1+ Boolean input 1 (GND) Boolean input 2+ Boolean input 3- (GND) Boolean input 3+ Boolean input 2- (GND) Boolean input 4+ Boolean input 4- (GND) Twisted Pair 1 and 2 twisted 1 and 2 twisted 3 and 6 twisted 4 and 5 twisted 4 and 5 twisted 3 and 6 twisted 7 and 8 twisted 7 and 8 twisted

2011-03-17

Huawei Confidential

Page 2 of 5

External Alarm Configuration Procedure

1.3 Hardware Connection of External Alarms For the detailed information about port numbers and slots, see the following table:
Name and BOM of Monitoring BTS Type Device Device Port Position Number Cable 4 5 UPEU (The Boolean alarms BTS3900 of a UPEU are reported on the GTMU) EXT-ALM0 2 3 alarm cable X1.5/X1.4 X1.7/X1.8 Blue white/blue Brown white/white EXT-ALM1 6 The UPEU is in slot 19 of 7 frame 0. The GTMU is in slot 6 of frame 0. 0 1 BBU Boolean X1.1/X1.2 X1.3/X1.6 Orange white/orange Green white/green X1.7/X1.8 Brown white/white alarm cable X1.5/X1.4 Blue white/blue BBU Boolean the Cable X1.1/X1.2 X1.3/X1.6 Orange white/orange Green white/green Monitoring Frame Position - Slot Port the Monitoring Number of Cable color Core

2011-03-17

Huawei Confidential

Page 3 of 5

External Alarm Configuration Procedure

2 Setting the Boolean Alarm of the BBU


2.1 Setting the Boolean Alarm of the BBU on the BSC6900 Step 1: As shown in figure 1, set the alarm name, alarm level, and the gateway categories on the MML. The command used on the MML is SET ENVALMPARA. The alarm ID here is the alarm ID of the port to be set.

Figure 1

Step 2: In the MML input serial port, type the SET BTSENVALMPORT command to set the high and low voltage levels of the dry contacts on the UPEU.

Figure 2

Note: For the current BTS in the BSC6900, the numbers of the ports on the PEU in both upper and lower parts of the PEU are in range of 0 to 7.

Step 3: Use the MML command (LST BTSENVALMPORT) to check whether the numbers of the ports where dry contacts are set and the alarm levels are correctly set.

2011-03-17

Huawei Confidential

Page 4 of 5

External Alarm Configuration Procedure

2.2 Alarm ID of the Boolean Alarm The alarm ID of Boolean alarm which can be defined by the user starts from 65033 to 65533.

2011-03-17

Huawei Confidential

Page 5 of 5