XDRCUPBT 500kV - 2
XDRCUPBT 500kV - 2
Technical data
Copper conductor cross-section mm
2
Outer diameter (approx.) mm 129 137 137 138 145 146 147
Capacitance
Impedance (90C, 50 Hz) /km 0.21 0.20 0.19 0.19 0.18 0.18 0.17
Surge impedance
Min. bending radius mm 2600 2750 2750 2800 2900 2950 2950
54 51 48 45 44 42 37
Ampacity
Diectly buried
Diectly buried 20C 1.0 Km/W A 1036 1212 1311 1407 1503 1668 1833
In ducts
In ducts 20C 1.0 Km/W A 989 1156 1250 1341 1432 1585 1738
In free air
In free air 35C A 1348 1614 1781 1933 2085 2411 2737
In ductbank 15C 0.8/1.0 Km/W A 1060 1241 1344 1443 1541 1712 1882
Directly buried
20C 1.0 Km/W A 944 1106 1190 1275 1359 1485 1611
20C 1.0 Km/W A 957 1117 1206 1292 1378 1518 1658
40C 1.4 Km/W A 670 780 833 890 947 1016 1085
Calculation basis: Conductor temperature 90C, 50 Hz, load factor 1.0, laying depth 1200 mm, phase distance at flat formation 30 cm Earthing method: Single-Point Bonding or Cross-bonding Brugg Kabel AG 2008, Subject to modifications