Classification Zone 0 Zone 20 Zone 1 Zone 21 Zone 2 Zone 22
Criteria For Zone
Flammable material always present or for long periods (e.g.1000 hours or more per year)
ATEX Marking
G D G D G D Category 1 Equipment
Flammable material present in normal operation (e.g. 10-1000 hours/year)
Category 2 Equipment
Flammable material present for short periods only (e.g. less than 10 hours/year)
Category 3 Equipment
AREA CLASSIFICATION CONTINUOUS HAZARD NORTH AMERICA (CEC/NEC) CENELEC/IEC INTERMITTENT HAZARD HAZARD UNDER ABNORMAL CONDITIONS Division 2 or Zone 2 Zone 2
Division 1 Zone 0 Zone 0 Zone 1 Zone 1
HAZARDOUS LOCATIONS GAS GROUPS
TYPICAL GAS HAZARD ACETYLENE HYDROGEN ETHYLENE PROPANE METHANE
NORTH AMERICA CEC SECTION 18, NEC ARTICLE 500 A or IIC B or IIC C or IIB D or IIA Group D (gaseous mines) or I
CENELEC/IEC CENELEC, EN 50014, IEC 79-0 IIC IIC IIB IIA I
TEMPERATURE CODE/CLASS
MAXIMUM SURFACE TEMPERATURE (C) NORTH AMERICA Temp Code CENELEC/IEC Temp Class
450 300
280
260
230
215
200
180
165
160
135
120
100 85
T1 T2
T2A
T2B
T2C
T2D
T3
T3A
T3B
T3C
T4
T4A
T5 T6
T1
T2
T3
T4
T5 T6