Professional Documents
Culture Documents
DESCRIPTION
The LonWorks driver allows the FieldServer to transfer data to and from devices using LonWorks protocol. Data transfer occurs via TP/FT10 twisted pair interface with an exhaustive list of protocols including Modbus, BACnet etc. Data transfer is via 2 basic functional blocks, Input and Output allowing Float and Word SNVT data types. The FS-B30 Series and SlotServer can handle up to 4096 Network Variables and the FS-B2011, QuickServer, ProtoNode and ProtoCessor up to 1000 which can be of the Standard Network Variable Types (SNVT) and/or User-defined Network Variable Types (UNVT). The FieldServer LonWorks device can be used with explicit and/or implicit addressing and can be bound to a maximum of 15 other LonWorks nodes. The FS-B30 Series can handle a maximum of 4096 explicitly addressed nodes and the FS-B2011 up to 1000. The FieldServer currently supports a default of 63 network variable aliases to avoid network variable connection constraints. The FieldServer can transfer data (Network Variables) in two ways. It can poll (request data from) other devices at a regular interval. It can send Network Variable Updates At a regular interval When the data has changed In throttled mode using minimum and maximum send time and change on delta parameters.
The FieldServer is capable of being configured by Network Management Tools such as LonMaker. For binding (implicit mode), a Network Management Tool is necessary to create the bindings. It is possible to place a FieldServer into a Network for explicit communications without using a Network Management Tool, but this requires intimate knowledge of the network in question. The external interface file (.XIF) for the FieldServer can be uploaded from the FieldServer for the particular application. The FieldServer differs from most other LonWorks devices in that its XIF file is not fixed due to varying applications. The list of points available to the network will vary depending on the other networks connected to the FieldServer, and the requirements of the particular application. The recommended procedure for obtaining the XIF file for the FieldServer is to upload it. The following FieldServer Platforms are LonMark Certified: FS-B20 FS-B35 FS-B40 FS-SlotServer FS-QuickServer-Lon ProtoCessor-Lon
The FieldServer provides the capability of defining multiple functional blocks, but only a single LonMark object. The user can create multiple functional blocks or a LonMark object by filling out the Node Self-Documentation String and the respective Network Variable Self-documentation String fields in the FieldServer configuration file.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 1 of 7
LonWorks
Now supporting SNVT Master List Version 11
The following table summarizes the FieldServer LonWorks drivers capabilities: FS-B2011, ProtoNode 1000 15 63 2 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes QuickServer, ProtoCessor, FS-B30, SlotServer 4096 15 63 2 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Number of Network Variables Address Table Entries Network Variable Aliases Number of Domain Tables
3 2
Support for SNVTs Support for UNVTs Explicit Addressing Implicit Addressing XIF file Supports Polled Network Variables Supports Network Variable Updates Supports Configuration Properties Supports Node and Network Variable Self-documentation Strings Support for SCPTs Network Management Tools such as LonMaker Supported Commissioning without Network Management Tool Supported Service Pin Supported LonMark Object and Functional Profiles definition FieldServer Mode Client Server
7 6 5 4
Nodes 1 1
Comments The FieldServer can only represent one LonWorks device on the LonWorks Network. A LonWorks device is unique in terms of its Neuron Chip Identification Number.
The length of Network Variable names,complexity of the configuration, and hardware license purchased may limit the actual number of usable Network Variables 2 One of the two domains is the zero domain used by Network Management Tools 3 SNVT Master List Version 11 is supported 4 Implemented with Configuration Network Variables 5 Only selected SCPTs are supported, extra SCPTs can be added on a per configuration basis 6 Explicit Addressing Only 7 Only approved LonMark objects are supported, see www.lonmark.org
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 2 of 7
LonWorks
Now supporting SNVT Master List Version 11
COMPATIBILITY MATRIX
Compatible with this driver No Yes No Yes Yes Yes Yes Yes
FieldServer Model FS-x2010 FS-x2011 FSx25 FS-x30 SlotServer ProtoCessor ProtoNode QuickServer
CONNECTION INFORMATION
Connection type: Baud Rates: Hardware interface:
FTT-10 Free Topology Network Transceiver 78125 bps (bits per second) PCC10 LonWorks adapter ISA card ( FS-X40 ) Built in LonWorks FTT-10 interface ( FS-X2011 and FSB30 ) Additional information on cabling and junction boxes that may be used in twisted pair LonWorks networks are detailed in the following Echelon Publication: http://www.echelon.com/support/documentation/bulletin/005-0023-01O_Jbox_wiring.pdf
DEVICES TESTED
Tested (Factory, Site) Factory/Site Factory/Site Site Factory Site Site Factory Factory Site Factory/Site Factory/Site
Device LonMaker for Windows V3.1 TAC Xenta TAC VISTA Electronic Systems USA Echelon ILon 100 Plexus Technologies Invensys I/A Series Circon UHC 300 (and others) Distech PureChoice Nose Honeywell and many others
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 3 of 7
LonWorks
Now supporting SNVT Master List Version 11
CONNECTION CONFIGURATIONS
The connection diagram below shows how the FieldServer FS-B2011 and FS-B30 are connected to a LonWorks network:
To other LonWorks Nodes
FieldServer Interface
FieldBus Connector
6.1
Connection Notes
The screw plug supplied with the FieldServer LonWorks interface will connect the FieldServer to the FTT-10 network. The 2wire twisted-pair connection to the network is polarity insensitive. The FTT-10 network is a free topology network which supports star, loop and/or bus wiring connections. Please refer to the FTT-10A Free Topology Transceiver Users Guide from Echelon Corporation for recommended wiring practices if necessary. Additional information on cabling and junction boxes that may be used in twisted pair LonWorks networks are detailed in the following Echelon Publication: http://www.echelon.com/support/documentation/bulletin/005-0023-01O_Jbox_wiring.pdf.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 4 of 7
LonWorks
Now supporting SNVT Master List Version 11
7 7.1
FieldServer Data Type Integers (Long, unsigned) Float Byte Bit short,
7.2
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 5 of 7
LonWorks
Now supporting SNVT Master List Version 11
SNVT Type Name SNVT_press SNVT_res SNVT_res_kilo SNVT_sound_db SNVT_speed SNVT_speed_mil SNVT_str_asc SNVT_str_int SNVT_telcom SNVT_temp Reserved Entry SNVT_vol SNVT_vol_kilo SNVT_vol_mil SNVT_volt SNVT_volt_dbmv SNVT_volt_kilo SNVT_volt_mil SNVT_amp_f SNVT_angle_f SNVT_angle_vel_f SNVT_count_f SNVT_count_inc_f SNVT_flow_f SNVT_length_f SNVT_lev_cont_f SNVT_mass_f SNVT_power_f SNVT_ppm_f SNVT_press_f SNVT_res_f SNVT_sound_db_f SNVT_speed_f SNVT_temp_f SNVT_time_f SNVT_vol_f SNVT_volt_f SNVT_btu_f SNVT_elec_whr_f SNVT_config_src SNVT_color SNVT_grammage SNVT_grammage_f
SNVT Type Number 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153
SNVT Type Name SNVT_hvac_overid SNVT_hvac_status SNVT_press_p SNVT_address SNVT_scene SNVT_scene_cfg SNVT_setting SNVT_evap_state SNVT_therm_mode SNVT_defr_mode SNVT_defr_term SNVT_defr_state SNVT_time_min SNVT_time_hour SNVT_ph SNVT_ph_f SNVT_chlr_status SNVT_tod_event SNVT_smo_obscur SNVT_fire_test SNVT_temp_ror SNVT_fire_init SNVT_fire_indcte SNVT_time_zone SNVT_earth_pos SNVT_reg_val SNVT_reg_val_ts SNVT_volt_ac SNVT_amp_ac Reserved Entry Reserved Entry Reserved Entry SNVT_turbidity SNVT_turbidity_f SNVT_hvac_type SNVT_elec_kwh_l SNVT_temp_diff_p SNVT_ctrl_req SNVT_ctrl_resp SNVT_ptz SNVT_privacyzone SNVT_pos_ctrl SNVT_enthalpy
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 6 of 7
LonWorks
Now supporting SNVT Master List Version 11
SNVT Type Name SNVT_file_req SNVT_file_status SNVT_freq_f SNVT_freq_hz SNVT_freq_kilohz SNVT_freq_milhz SNVT_lux Reserved Entry
SNVT Type Number 154 155 156 157 158 159 160 161
SNVT Type Name SNVT_gfci_status SNVT_motor_state SNVT_pumpset_mn SNVT_ex_control SNVT_pumpset_sn SNVT_pump_sensor SNVT_state_64 SNVT_nv_type
7.3
The Driver can read and write remote Configuration Properties implemented as Network Variables.
FieldServer as a Client Polled Network Variables: -Send Network Variable Fetch -Send Network Variable Poll
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 7 of 7