Rsi internal leaf(prefrab) insulation rockwool hardrock outer leaf(prefrab) Rse
d (m)
(W/mK)
R=d/( mK/W)
0,13 0,19 5,41 0,09 0,04 5,85 0,17
Ref: DS 418 surface tention values chapter 6.2 Table F.2 Page 84 REF legend surface tention values chapter 6.2 construction Single door Double door windows 1 windows 2
size of unit Height (m) width (m) 2,108 0,908 2,108 1,808 1,212 3,212 1,212 2,212
size of hole in wall Height (m) width (m) 2,12 0,932 2,12 1,832 1,236 3,236 1,236 2,236
size of thermal bridge Height (m) width (m) 2,174 1,148 2,174 2,048 1,344 3,344 1,452 2,452
Area of doors , windows and thermal bridges construction single door Double door window 1 window 2 Quantity 4 3 11 4 areas (m) 7,90 11,65 16,80 6,11 42,47 Total (m)
Lk
construction
Rsi internal leaf polyesteren outer leaf Rse
d (m)
(W/mK)
0,25 0,04 0,25 1/U'=R= U'=
R=d/( mK/W)
0,13 0,60 0,50 0,28 0,04 1,55 0,65
Ref: DS 418 surface tention values chapter 6.2 Table F.2 Page 84
windows 1 windows 2
thermal bridge thermal bridge thermal bridge thermal bridge thermal bridge
0 sum
U =U g + U f + U r U g=U''x(Ri/Rt) U f= U r= U =U'+U
Aw Lk U g U f U r Ri Rt U'' REF
Area of wall perimiter of thermal bridge linear coeficient values can be edited is a correction for air-cracks in the insulation layer is a correction for ties and similar mechanical fixations is a correction for precipitation on upside down roof, value is taken as being 0 is the heat flow resistance of the insulation layer is the total heat flow resistance of the construction is the correction for air-cracks in the insulation layer. SBI derivative 189 pg. 44
U f 0,005