Walls

U values for production

Size of doors and windows and thermal bridge

construction
Rsi internal leaf(prefrab) insulation rockwool hardrock outer leaf(prefrab) Rse

d (m)

(W/mK)

R=d/( mK/W)
0,13 0,19 5,41 0,09 0,04 5,85 0,17

Ref: DS 418 surface tention values chapter 6.2 Table F.2 Page 84 REF legend surface tention values chapter 6.2 construction Single door Double door windows 1 windows 2

0,15 0,2 0,07

0,8 0,037 0,8 1/U'=R= U'=

size of unit Height (m) width (m) 2,108 0,908 2,108 1,808 1,212 3,212 1,212 2,212

size of hole in wall Height (m) width (m) 2,12 0,932 2,12 1,832 1,236 3,236 1,236 2,236

size of thermal bridge Height (m) width (m) 2,174 1,148 2,174 2,048 1,344 3,344 1,452 2,452

Area of doors , windows and thermal bridges construction single door Double door window 1 window 2 Quantity 4 3 11 4 areas (m) 7,90 11,65 16,80 6,11 42,47 Total (m)

Lk

159,79 permeter construction Single door double doors

length of wall Height of wall external area of wall

187,18 5,3 992,054

m 11,5 15,1 29,1 24,1

U' for thermal bridge for wall

construction
Rsi internal leaf polyesteren outer leaf Rse

d (m)

(W/mK)
0,25 0,04 0,25 1/U'=R= U'=

R=d/( mK/W)
0,13 0,60 0,50 0,28 0,04 1,55 0,65

Ref: DS 418 surface tention values chapter 6.2 Table F.2 Page 84

windows 1 windows 2

0,15 0,02 0,07

surface tention values chapter 6.2

thermal bridge thermal bridge thermal bridge thermal bridge thermal bridge

solid door Double door window window window

2,08 1,71 4,66 1,70 0,00 10,14

Total U' for wall


Component Wall thermal bridge in wall Lk(perimiter) * total sums 992,05 10,14 159,79 (W/m C) Corrected Area(m) 939,44 10,14 949,58 U* area (m) 160,58 6,54 0,00 167,12 0,18

0 sum

Total U' =(A*U'+Lk*+Xj*Aw)/AT

U =U g + U f + U r U g=U''x(Ri/Rt) U f= U r= U =U'+U

0,005 0,000 0,005 0,000 0,18

DS418 page 59 DS418 page 59 DS418 page 61 DS418 page 69 U'' 0

Aw Lk U g U f U r Ri Rt U'' REF

Area of wall perimiter of thermal bridge linear coeficient values can be edited is a correction for air-cracks in the insulation layer is a correction for ties and similar mechanical fixations is a correction for precipitation on upside down roof, value is taken as being 0 is the heat flow resistance of the insulation layer is the total heat flow resistance of the construction is the correction for air-cracks in the insulation layer. SBI derivative 189 pg. 44

U f 0,005