Standard Technical Specifications for Electrical Works

TRANSFORMERS / REACTORS / RESISTORS


( Data Sheets )

11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA

___________________________________________________________________________________
_____

177536141.xls

Page 1 of 8

ADDC/AADC STANDARD : D-TRAFO-PMT-11-400 (Rev.1-2008)

___________________________________________________________________________________
_____

177536141.xls

Page 2 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA

Table of Content
Page

1.00

GENERAL

2.00

RATING

3.00

INSULATION LEVEL

4.00

TESTS

5.00

OPERATIONAL DETAILS

6.00

DESIGN DETAILS AND FEATURES

7.00

MASSES, MEASURES AND DRAWINGS

________________________________________________________________________________________________________
_____

177536141.xls

Page 2 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

1.00

GENERAL

1.01

Manufacturer

1.01.1

name

1.01.2

country of manufacturing

TENDERED

1.02

Place of testing

1.03

Kind of installation

1.04

Applicable standards

1.05

Type of core

core type

1.06

Type of tank

corrugated sheet steel


hermetically sealed

1.07

Specification of transformer oil

2.00

RATING

2.01

Rated power

2.02

Service conditions

outdoor, pole-mounted
IEC

60076

IEC

60296 class II

kVA

400

2.02.1

maximum service temperature

50

2.02.2

maximum service altitude

1000

2.03

Temperature rise limit at all tap changer settings

2.03.1

oil / top

45

2.03.2

winding / average

55

2.03.3

winding / hot spot

68

2.04

Rated voltages

2.04.1

primary

kV

11

2.04.2

secondary at no-load

kV

0.415

2.05

Number of phases

2.06

Rated current

2.06.1

primary (at principal tap)

2.06.2

secondary

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 3 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

TENDERED

2.07

Vector group symbol

2.08

Rated frequency

Hz

50

2.09

Impedance voltage (75oC) at full rated power

4.0

2.10

Magnetic flux density

Dyn11

2.10.1

at nominal voltage and frequency

Tesla

2.10.2

at maximum system voltage

Tesla

2.10.3

saturation

Tesla

2.11

No-load losses, at rated voltage and frequency

kW

2.12

No-load current (Io/In)

2.13

Core losses (W17/50)

W/kg

2.14

Load losses (75oC)

kW

2.15

Tap changer current rating

2.16

Tapping range

2.17

Number of steps

No.

2.18

Tapped winding

2.19

Principal tapping at

3.00

INSULATION LEVEL

3.01

Primary (windings/bushings)

1.72

max. 0.55

max. 1.12
max. 4.5

2 x 2.5
2
HV

kV

11

3.01.1

power frequency withstand voltage (winding)

kV

38

3.01.2

lightning impulse level (winding)

kV

95

3.01.3

power frequency withstand voltage (bushings)

kV

38

3.01.4

lightning impulse level (bushings)

kV

95

3.02

Secondary (windings/bushings)

3.02.1

power frequency withstand voltage

kV

3/10

3.02.2

lightning impulse level

kV

NA/20

3.03

Minimum creepage distance of bushings

3.03.1

primary

mm

3.03.2

secondary

mm

543

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 4 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

TENDERED

4.00

TESTS

4.01

Routine tests according to IEC 60076

on each unit

4.02

Separate source AC withstand voltage test

on each unit

4.02.1

test voltage / primary

kV

38

4.02.2

test voltage / secondary

kV

4.03

Induced AC withstand voltage test

on each unit

4.03.1

test voltage / primary

kV

23.1

4.03.2

test voltage / secondary

kV

0.83

4.04

Heat run test ( for pre-qualification only )

type test on one unit

4.05

Lightning impulse tests on HV windings


(for pre-qualification only)

type test on one unit

4.05.1

test voltage / full wave

kV

95

4.05.2

test voltage / chopped wave

kV

105

4.06

Short circuit test ( for pre-qualification only )

4.06.1

name of independent testing laboratory


who carried out the short circuit test
on similar transformer

4.06.2

test certificates attached

4.06.3

validity of quality control certificate

4.06.4

name of issuing authority

5.00
5.01

yes

OPERATIONAL DETAILS
#NAME?

Constant power at all taps

5.02

Cooling method

5.03

Noise level (LpA) at measuring distance of 0,3 m

5.04

Permissible over-load and duration (in minutes)

5.05

20 % over-load

5.05.1

at 30oC

yes
ONAN
dB(A)

min.
min.

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 5 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

5.05.2

at 40oC

min.

5.05.3

at 50oC

min.

5.06

30 % over-load

5.06.1

at 30oC

min.

5.06.2

at 40oC

min.

5.06.3

at 50oC

min.

5.07

40 % over-load

5.07.1

at 30oC

min.

5.07.2

at 40oC

min.

5.07.3

at 50oC

min.

5.08

TENDERED

50 % over-load

5.08.1

at 30oC

min.

5.08.2

at 40oC

min.

5.08.3

at 50oC

min.

6.00

DESIGN DETAILS AND FEATURES

6.01

Current densities at rated power

6.01.1

primary

A/mm2

max. 2.48

6.01.2

secondary

A/mm2

max. 2.48

6.02

Winding resistances at 750C

6.02.1

primary

/phase

6.02.2

secondary

/phase

6.03

Type of windings

6.03.1

primary

6.03.2

secondary

6.04

Winding conductor material (all windings)

6.05

Winding connections / braced or crimped

6.06

Branded or core bolt construction

6.07

Thermal class of insulation

copper

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 6 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.
6.08

REQUIRED
Insulation material

6.08.1

primary

6.08.2

secondary

6.08.3

tapping leads

6.08.4

core lamination

6.09

Radiators / wall thickness

6.10

Type of valves

6.11

Efficiencies

mm
globe or gate valve

6.11.1

at 25 % of rated power

6.11.2

at 50 % of rated power

6.11.3

at 75 % of rated power

6.11.4

at 100 % of rated power

6.11.5

at 125 % of rated power

6.11.6

at 150 % of rated power

6.12

Voltage regulation at 75oC and rated power

6.12.1

at power factor 0.80

6.12.2

at power factor 0.85

6.12.3

at power factor 0.90

6.12.4

at power factor 0.95

6.13

TENDERED

Thickness of tank cover, walls and bottom

6.13.1

cover

mm

6.13.2

walls (except corrugated sheet steel radiators)

mm

6.13.3

bottom

mm

6.13.4

nominal internal pressure at full load

max. bar

6.13.5

internal withstand test pressure at full load

bar

7.00

MASSES, MEASURES AND DRAWINGS

7.01

Overall dimensions

7.01.1

height

min. 6

mm

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 7 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

7.01.2

depth

mm

7.01.3

width

mm

7.02

Shipping dimensions

7.02.1

height

mm

7.02.2

depth

mm

7.02.3

width

mm

7.03

Height of crane hook

7.04

Transformer masses

7.04.1

total mass

kg

7.04.2

transportation mass

kg

7.04.3

untanking mass

kg

7.04.4

mass of core

kg

7.04.5

mass of windings

kg

7.04.6

mass of tank and fittings

kg

7.04.7

mass of insulation liquid

kg

7.05

TENDERED

Drawings

7.05.1

dimensional drawings

No.

7.05.2

connection diagram

No.

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 8 of 8

TRANSFORMERS / REACTORS / RESISTORS


11 5% kV / 0.415 kV Pole-Mounted Transformer, 400 kVA
Sl. No.

REQUIRED

TENDERED

TENDERER`s STAMP SIGNATURE


__________________________________________________________________________________________________________________
_
177536141.xls
Page 9 of 8