You are on page 1of 16

Standard Technical Specifications for Electrical Works

MV SWITCHGEAR
( Data Sheets )

11 kV Switching Station
(11kV SWG Air or SF6 Insulated, Fixed CB)

________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 1 of 15
ADWEA/ADDC/AADC STANDARD : D-AAA-SWG-MV-SWST-FIXED
(Rev.0-2015)

________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 2 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Table of Content

Page

1.00 GENERAL 3

2.00 CONSTRUCTION DATA 3


A. 11 kV Air or SF6-Insulated Switchgear 3
B. Wiring 9

3.00 ELECTRICAL DATA 10


A. General 10
B. 11 kV Air or SF6-Insulated Switchgear 10
C. Wiring 15

4.00 OTHER TECHNICAL DATA 15


A. Voltage and Current Transformers 15
B. Metering Devices, Instruments 15
C. Protection 15

5.00 OTHER PERFORMANCE DATA 15

6.00 SUPPORTING DOCUMENTS 15

_____________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 2 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

1.00 GENERAL

1.01 Applicable standards IEC 60298

1.02 Type test


1.02.1 carried out yes/no

1.02.2 date dd-mm-yy

1.02.3 testing laboratory


1.02.3.1 name
1.02.3.2 country
1.03 Type
1.04 Commercial operation time of offered switchgear years 5
type

2.00 CONSTRUCTION DATA

A. 11 kV Air or SF6-Insulated Switchgear


2.01 Manufacturer
2.01.1 name
2.01.2 country of manufacturing
2.02 Modular type yes

2.03 Enclosure (one feeder)


2.03.1 type metal-clad

2.03.2 material galvanised steel

2.03.2.1 grade
2.03.2.2 arc-proof yes

2.03.2.3 thickness
2.03.2.3.1 base frame mm

2.03.2.3.2 side panels mm

2.03.2.3.3 top cover mm

2.03.2.3.4 doors mm

2.03.3 gaskets

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 3 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

2.03.3.1 material
2.03.4 over pressure relief flap yes

2.03.5 dimension
2.03.5.1 height mm

2.03.5.2 width mm

2.03.5.3 depth mm

2.03.6 extensible at both sides yes

2.03.7 color RAL 7032

2.04 Compartments/Modules
2.04.1 circuit breaker insulation medium air/SF6

2.04.1.1 degree of protection, air/SF6 IP 4X/65

2.04.1.2 interlocks provided yes

2.04.2 VTs
2.04.2.1 insulation medium air/SF6

2.04.2.2 degree of protection, air/SF6 IP 4X/65

2.04.3 busbars
2.04.3.1 insulation medium air/SF6

2.04.3.2 degree of protection, air/SF6 IP 4X/65

2.04.4 cable sealing end and CTs


2.04.4.1 insulation medium air

2.04.4.2 degree of protection IP 4X

2.04.5 control, protection, etc.


2.04.5.1 insulation medium air

2.04.5.2 degree of protection IP 4X

2.04.6 separation sheets of compartments


2.04.6.1 material galvanised steel

2.04.6.2 thickness mm

2.05 Busbars
2.05.1 material copper

2.05.2 single busbars yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 4 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

2.05.2.1 location upper part

2.05.2.2 sections No. 2

2.05.2.3 elevated busduct yes

2.05.2.4 number of runs No.

2.05.2.5 dimensions
2.05.2.5.1 height mm

2.05.2.5.2 width mm

2.05.3 minimum clearances


2.05.3.1 between phases mm

2.05.3.2 phases to earth mm

2.05.4 phase barrier provided yes/no

2.05.5 bus-joints
2.05.5.1 silver-plated yes

2.05.5.2 thickness of plating μm

2.05.6 busbar cover PVC sleeves

2.05.7 calculation establishing adequacy of yes


cross-section and supports for short circuit and
thermal current
2.05.8 busbar support insulators
2.05.8.1 manufacturer
2.05.8.1.1 name
2.05.8.1.2 country of manufacturing
2.05.8.2 type
2.05.8.3 material epoxy resin

2.05.8.4 applicable standards IEC

2.05.8.5 visible corona discharge voltage


2.05.8.6 creepage distance mm

2.06 Risers
2.06.1 material
2.06.2 dimension
2.06.2.1 height mm

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 5 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

2.06.2.2 width mm

2.06.3 number of runs No.

2.07 Earthing busbar


2.07.1 material
2.07.2 dimension
2.07.2.1 height mm

2.07.2.2 width mm

2.07.3 number of runs No.

2.08 Circuit breaker


2.08.1 manufacturer
2.08.1.1 name
2.08.1.2 country of manufacturing
2.08.2 applicable standards IEC 62271-100

2.08.3 type fixed

2.08.4 no. of poles 3

2.08.5 arc quenching medium


2.08.5.1 vacuum yes/no

2.08.5.2 SF6 yes/no

2.08.6 operating facilities


2.08.6.1 hand yes

2.08.6.2 motor yes

2.08.6.3 counter yes

2.08.7 operation mechanism


2.08.7.1 opening spring

2.08.7.2 closing spring

2.08.7.3 tripping coils, including trip cct. supervision


2.08.7.3.1 incomer and bus-section No. 2

2.08.7.3.2 others No. 1

2.08.8 mechanical position indicator of main contact yes

2.08.9 mechanical trip free operation mechanism in yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 6 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

transformer feeder
2.09 Earthing
2.09.1 each busbar section earthing switch (directly)

2.09.2 feeder isolator cum earthing switch


(through CB)

2.10 Isolator cum earthing switch


2.10.1 manufacturer
2.10.1.1 name
2.10.1.2 country of manufacturing
2.10.2 applicable standards IEC 62271-102

2.10.3 no. of poles 3

2.10.4 remote operation (if applicable) yes/no

2.10.4.1 closing time with motor drive ms

2.10.4.2 opening time with motor drive ms

2.10.5 operating facilities


2.10.5.1 hand yes

2.10.5.2 motor yes

2.10.6 mechanical position indicator of main contact yes

2.11 BB earthing switch


2.11.1 manufacturer
2.11.1.1 name
2.11.1.2 country of manufacturing
2.11.2 applicable standards IEC 62271-102

2.11.3 no. of poles 3

2.11.4 arc-quenching medium Air/SF6

2.11.5 remote operation (if applicable) yes/no

2.11.5.1 closing time with motor drive ms

2.11.5.2 opening time with motor drive ms

2.11.6 operating facilities


2.11.6.1 hand yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 7 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

2.11.6.2 motor yes

2.11.7 mechanical position indicator of main contact yes

2.12 Space heater


2.12.1 manufacturer
2.12.1.1 name
2.12.1.2 country of manufacturing
2.12.2 applicable standards IEC

2.12.3 application
2.12.3.1 LV compartments yes

2.12.3.2 each switchgear compartment yes

2.12.4 control system


2.12.4.1 humidistat PTC type

2.12.4.2 thermostat PTC type

2.12.5 MCB for heater provided yes

2.13 Fault indicator


2.13.1 manufacturer
2.13.1.1 name
2.13.1.2 country of manufacturing
2.13.2 applicable standards IEC

2.13.3 housing
2.13.3.1 material
2.13.3.2 window transparent plastic

2.13.4 remote indication provided yes

2.13.5 current transformer


2.13.5.1 core-balance yes

2.13.5.2 burden VA

2.13.6 type
2.13.7 re-set manual with remote end re-set facilities yes

2.13.8 re-set automatic no

2.13.8.1 power

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 8 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

2.13.8.1.1 from CT or AC auxiliary supply yes

2.13.8.1.2 from built-in battery no

2.14 Potential indicators


2.14.1 manufacturer
2.14.1.1 name
2.14.1.2 country of manufacturing
2.14.2 applicable standards IEC 61243-5

2.14.3 type plug-in

2.14.4 provided for each phase yes

2.14.5 provided at each feeder yes

2.14.6 provided with optical output for capacitor type yes

2.15 Weights
2.15.1 one complete feeder panel kg

B. Wiring
2.16 Material
2.16.1 stranded copper wires for cross-sections yes
>2.5mm2 else solid copper wires
2.17 Cross-sections
2.17.1 power circuits (min) mm2 1.5

2.17.2 control circuits mm2 1

2.17.3 2 2.5
CT circuits (min) mm

2.17.4 VT circuits (min) mm2 1.5

2.17.5 telecommunication/control/protection connections


2.17.5.1 pairs are screened (for communication) yes

2.17.5.2 2 1.5
external wiring mm

2.17.5.3 other wiring mm2 0.5

3.00 ELECTRICAL DATA

A. General

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 9 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

3.01 Radio Influence Voltage at 1 MHz dB

3.02 Noise level dB(A) 48

3.02.1 applicable standards IEC 60551

3.03 Remote control Interface terminals/cubicle yes

B. 11 kV Air or SF6-Insulated Switchgear


3.04 Common
3.04.1 nominal operating voltage kV 11

3.04.2 rated voltage kV 12

3.04.3 frequency Hz 50

3.04.4 insulation level


3.04.4.1 power frequency withstand voltage, 1 min.
3.04.4.1.1 phase to phase and phase to earth kV 28

3.04.4.1.2 across isolating distance kV 32

3.04.4.2 lightning impulse withstand voltage


3.04.4.2.1 phase to phase and phase to earth kV 75

3.04.4.2.2 across isolating distance kV 85

3.04.5 rated short-circuit current, 1s kA 25

3.05 Busbars
3.05.1 rated current carrying capacity at max. 40°C A 1250

3.05.2 operating current carrying capacity at max. 50°C A

3.06 Circuit breaker (vacuum)


3.06.1 rated currents at 40°C
3.06.1.1 outgoing feeder A 630

3.06.1.2 incoming feeder A 630

3.06.1.3 busbar sectionaliser A 1250

3.06.2 operating currents at 50°C


3.06.2.1 outgoing feeder A

3.06.2.2 incoming feeder A

3.06.2.3 busbar sectionaliser A

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 10 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

3.06.3 rated breaking current capacity


3.06.3.1 short circuit breaking current
3.06.3.1.1 AC component r.m.s. value kA >25

3.06.3.1.2 DC component %

3.06.3.1.3 asymmetrical including DC component kA

3.06.3.2 line charging breaking current A

3.06.3.3 cable-charging breaking current A 50

3.06.3.4 maximum capacitive breaking current A 0.8 x In

3.06.3.5 small inductive breaking current A 10

3.06.3.6 out of phase breaking current A

3.06.4 rated making current capacity


3.06.4.1 short circuit making current kA

3.06.5 time ratings


3.06.5.1 opening time at
3.06.5.1.1 10% of rated short-circuit current ms

3.06.5.1.2 30% of rated short-circuit current ms

3.06.5.1.3 60% of rated short-circuit current ms

3.06.5.1.4 100% of rated short-circuit current ms

3.06.6 maximum spring recharging time sec 25

3.06.7 interrupter
3.06.7.1 manufacturer
3.06.7.1.1 name
3.06.7.1.2 country of manufacturing
3.06.7.2 pressure/vacuum inside the interrupter mmHg

3.06.7.3 contact wear indication provided yes/no

3.06.7.4 facility for checking loss of vacuum provided yes/no

3.06.7.5 vacuum monitoring relay provided yes/no

3.06.7.6 shielding against X-Ray radiations provided yes/no

3.06.7.7 length of interruption mm

3.06.7.8 type of contact material

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 11 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

3.06.7.8.1 main
3.06.7.8.2 arcing
3.06.7.8.3 contacts silver plated yes

3.06.7.8.3.1 thickness of plating µm

3.06.7.8.4 contact pressure on main contacts kg/m2

3.06.7.8.5 contact pressure on arcing contacts kg/m2


3.06.7.9 maximum temperature rise over the specified °C
ambient temperature
3.06.7.10 heat dissipation at normal current kW

3.06.7.11 number of switchings during life time


3.06.7.11.1 with rated current No.

3.06.7.11.2 with rated short circuit breaking current No.

3.06.7.12 number of operations within 10 years


(before first inspection and maintenance)
3.06.7.12.1 switching at rated load No. min. 20000

3.06.7.12.2 switching at 100% fault capacity No. min. 100

3.06.7.12.3 switching at 50% fault capacity No.

3.06.7.12.4 making under fault conditions No.

3.06.8 whether the circuit breaker is suitable for yes/no


trip-free or fixed trip operation (mechanically)
and (electrically)
3.06.9 whether the circuit breaker designed to close yes/no
and latch on making or fitted with current
release
3.06.10 whether anti pumping device provided yes/no

3.06.11 rated supply voltage of operating mechanism


3.06.11.1 closing coil Vdc 48

3.06.11.1.1 allowable variation of voltage ±% +10% -20%

3.06.11.1.2 power required at normal voltage kW

3.06.11.2 tripping coil Vdc 48

3.06.11.2.1 allowable variation of voltage ±% +10% -20%

3.06.11.2.2 power required at normal voltage kW

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 12 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

3.06.11.3 spring charging motor Vdc 48

3.06.11.3.1 allowable variation of voltage ±% +10% -20%

3.06.11.3.2 power required at normal voltage kW

3.06.11.3.3 motor rated current A

3.06.11.3.4 motor starting current A

3.06.12 rated voltage of shunt opening release V

3.06.12.1 normal current at rated voltage A

3.06.12.2 power W

3.06.12.3 duration ms

3.06.13 whether control circuitry is suitable for yes/no


monitoring of closing and tripping circuits
3.06.14 auxiliary switches
3.06.14.1 type
3.06.14.2 number No.

3.06.14.3 normal current at rated voltage A

3.06.14.4 breaking current A

3.06.15 current required at rated voltage by other


auxiliaries A

3.06.16 auxiliary contacts (directly driven)


3.06.16.1 normally open (NO) when breaker is closed No. 10

3.06.16.2 normally close (NC) when breaker is closed No. 10

3.06.16.3 adjustable w.r.t the position of main contacts No.

3.06.17 wiping contacts


3.06.17.1 number No. 2

3.06.17.2 current carrying capacity A

3.06.17.3 breaking capacity A

3.06.17.4 voltage Vdc 48

3.07 Earthing cum isolating switch


3.07.1 motor drive
3.07.1.1 power W

3.07.1.2 rated voltage Vdc 48

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 13 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

3.07.1.3 rated current A

3.07.1.4 starting current A

3.07.2 auxiliary contacts (directly driven)


3.07.2.1 NO No. 10

3.07.2.2 NC No. 10

3.07.2.3 breaking capacity kA

3.08 BB earthing switch


3.08.1 motor drive
3.08.1.1 power W

3.08.1.2 rated voltage Vdc 48

3.08.1.3 rated current A

3.08.1.4 starting current A

3.08.2 no. of aux. contacts


3.08.2.1 NO No. 10

3.08.2.2 NC No. 10

3.08.2.3 breaking capacity kA

3.09 Space heater


3.09.1 power W

3.09.2 rated voltage Vac 230

3.09.3 rated current A

C. Wiring
3.10 Power frequency withstand voltage kV ac1min 2

4.00 OTHER TECHNICAL DATA

A. Voltage and Current Transformers as per requirement


specified in standard
technical specification,
part: S-AAA-SWG-MV-VTCT

B. Metering Devices, Instruments as per requirement


specified in standard

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 14 of 15
MV SWITCHGEAR
11 kV Switching Station (11kV SWG Air or SF6 Insulated, Fixed CB)

Sl. No. REQUIRED TENDERED

technical specification,
part: S-AAA-MET-GEN

C. Protection as per requirement


specified in standard
technical specification
part: D-AAA-CPS-MV-LV-PROT

5.00 OTHER PERFORMANCE DATA


5.01 First commercial operation of the offered unit
5.01.1 date dd-mm-yy

5.01.2 according to the attached reference list/sheet

6.00 SUPPORTING DOCUMENTS


6.01 Type test reports enclosed yes

6.02 Technical literature enclosed yes

6.03 Standard conditions of installation enclosed yes

6.04 Relevant drawings enclosed yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-FIX (Rev.0-2015) Page 15 of 15