Standard Technical Specifications for Electrical Works

MV SWITCHGEAR
( Data Sheets )

11 kV Switching Station
(Withdrawable 11 kV CB's)

ADWEA/ADDC/AADC STANDARD : D-AAA-SWG-MV-SWST-WD


(Rev.0-2015)

________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 1 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Table of Content

Page

1.00 GENERAL 3

2.00 CONSTRUCTION DATA 3


A. 11 kV Air-Insulated Switchgear 3
B. Wiring 8

3.00 ELECTRICAL DATA 8


A. General 8
B. 11 kV Air-Insulated Switchgear 8
C. Wiring 13

4.00 OTHER PERFORMANCE DATA 13


A. Voltage and Current Transformers 13
B. Metering Devices, Instruments 13
C. Protection 13

5.00 OTHER PERFORMANCE DATA 13

6.00 SUPPORTING DOCUMENTS 14

_____________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 2 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

1.00 GENERAL

1.01 Applicable standards IEC 60298

1.02 Type test


1.02.1 carried out yes/no

1.02.2 date dd-mm-yy

1.02.3 testing laboratory


1.02.3.1 name
1.02.3.2 country
1.03 Type
1.04 Commercial operation time of offered switchgear years 5
type

2.00 CONSTRUCTION DATA

A. 11 kV Air-Insulated Switchgear
2.01 Manufacturer
2.01.1 name
2.01.2 country of manufacturing
2.02 Enclosure (one feeder)
2.02.1 type metal-clad

2.02.2 material galvanised steel

2.02.3 grade
2.02.4 arc-proof yes

2.02.5 thickness
2.02.5.1 base frame mm

2.02.5.2 side panels mm

2.02.5.3 top cover mm

2.02.5.4 doors mm

2.02.6 gaskets
2.02.6.1 material

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 3 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

2.02.7 over pressure relief flap yes

2.02.8 dimension
2.02.8.1 height mm

2.02.8.2 width mm

2.02.8.3 depth mm

2.02.9 extensible at both sides yes

2.02.10 color RAL 7032

2.03 Compartments
2.03.1 circuit breaker
2.03.1.1 degree of protection IP 4X

2.03.1.2 automatic safety shutter system


2.03.1.2.1 material
2.03.1.2.1.1 shutters
2.03.1.2.1.1.1 glass-fibre reinforced epoxy yes

2.03.1.2.1.2 operating mechanism


2.03.1.2.1.2.1 glass-fibre reinforced epoxy yes
2.03.1.2.1.2.2 plastic covered steel parts are used yes/no

2.03.1.3 interlocks provided yes

2.03.2 VTs
2.03.2.1 degree of protection IP 4X

2.03.3 busbars
2.03.3.1 degree of protection IP 4X

2.03.4 cable sealing ends and CTs


2.03.4.1 degree of protection IP 4X

2.03.5 control, protection, etc.


2.03.5.1 degree of protection IP 4X

2.03.6 separation sheets of compartments


2.03.6.1 material galvanised steel

2.03.6.2 thickness mm

2.04 Busbars

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 4 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

2.04.1 insulation medium air

2.04.2 material copper

2.04.3 single busbars yes

2.04.3.1 location upper part

2.04.3.2 sections No. 2

2.04.3.3 elevated busduct yes

2.04.3.4 number of runs No.

2.04.3.5 dimensions
2.04.3.5.1 height mm

2.04.3.5.2 width mm

2.04.4 minimum clearances


2.04.4.1 between phases mm

2.04.4.2 phases to earth mm

2.04.5 phase barrier provided yes/no

2.04.6 bus-joints
2.04.6.1 silver-plated yes

2.04.6.2 thickness of plating μm

2.04.7 busbar cover PVC sleeves

2.04.8 calculation establishing adequacy of yes


cross-section and supports for short circuit and
thermal current
2.04.9 busbar support insulators
2.04.9.1 manufacturer
2.04.9.1.1 name
2.04.9.1.2 country of manufacturing
2.04.9.2 applicable standards IEC

2.04.9.3 creepage distance mm

2.05 Risers
2.05.1 material
2.05.2 dimension
2.05.2.1 height mm

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 5 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

2.05.2.2 width mm

2.05.3 number of runs No.

2.06 Earthing busbar


2.06.1 material
2.06.2 dimension
2.06.2.1 height mm

2.06.2.2 width mm

2.06.3 number of runs No.

2.07 Circuit breaker


2.07.1 manufacturer
2.07.1.1 name
2.07.1.2 country of manufacturing
2.07.2 applicable standards IEC 62271-100

2.07.3 type withdrawable

2.07.4 no. of poles 3

2.07.5 arc quenching medium


2.07.5.1 vacuum yes/no

2.07.5.2 SF6 yes/no

2.07.6 operating facilities


2.07.6.1 hand yes

2.07.6.2 motor yes

2.07.6.3 counter yes

2.07.7 operation mechanism


2.07.7.1 opening spring

2.07.7.2 closing spring

2.07.7.3 tripping coils, including trip cct. supervision


2.07.7.3.1 incomer and bus-sections No. 2

2.07.7.3.2 others No. 1

2.07.8 mechanical position indicator of main contact yes

2.07.9 mechanical trip free operation mechanism in yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 6 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

transformer feeder
2.08 Earthing
2.08.1 each busbar section earthing switch (directly)

2.08.2 feeder earthing switch (directly)

2.09 Earthing switch


2.09.1 manufacturer
2.09.1.1 name
2.09.1.2 country of manufacturing
2.09.2 applicable standards IEC 62271-102

2.09.3 no. of poles 3

2.09.4 arc-quenching medium air

2.09.5 remote operation (if applicable) yes/no

2.09.5.1 closing time with motor drive ms

2.09.5.2 opening time with motor drive ms

2.09.6 operating facilities


2.09.6.1 hand yes

2.09.6.2 motor yes

2.09.7 mechanical position indicator of main contact yes

2.10 Space heater


2.10.1 manufacturer
2.10.1.1 name
2.10.1.2 country of manufacturing
2.10.2 applicable standards IEC

2.10.3 application
2.10.3.1 LV compartments yes

2.10.3.2 each switchgear compartment yes

2.10.4 control system


2.10.4.1 humidistat PTC type

2.10.4.2 thermostat PTC type

2.10.5 MCB for each heater provided yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 7 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

2.11 Fault indicator


2.11.1 manufacturer
2.11.1.1 name
2.11.1.2 country of manufacturing
2.11.2 applicable standards IEC

2.11.3 housing
2.11.3.1 material
2.11.3.2 window transparent plastic

2.11.4 remote indication provided yes

2.11.5 current transformer


2.11.5.1 core-balance yes

2.11.5.2 burden VA

2.11.6 type
2.11.7 re-set manual with remote end re-set facilities yes

2.11.7.1 re-set automatic no

2.11.7.2 power
2.11.7.2.1 from CT or AC auxiliary supply yes

2.11.7.2.2 from built-in battery no

2.12 Potential indicators


2.12.1 manufacturer
2.12.1.1 name
2.12.1.2 country of manufacturing
2.12.2 applicable standards IEC 61243-5

2.12.3 type plug-in

2.12.4 provided for each phase yes

2.12.5 provided at each feeder yes

2.12.6 provided with optical output for capacitor type yes

2.13 Weights
2.13.1 one complete feeder panel kg

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 8 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

B. Wiring
2.14 Material
2.14.1 stranded copper wires for cross-sections yes
>2.5mm2 else solid copper wires
2.15 Cross-sections
2.15.1 power circuits (min) mm2 1.5

2.15.2 control circuits mm2 1

2.15.3 CT circuits (min) mm2 2.5

2.15.4 2 1.5
VT circuits (min) mm

2.15.5 telecommunication/control/protection connections


2.15.5.1 pairs are screened (for communication) yes

2.15.5.2 external wiring mm2 1.5

2.15.5.3 2 0.5
other wiring mm

3.00 ELECTRICAL DATA

A. General
3.01 Radio Influence Voltage at 1 MHz dB

3.02 Noise level dB(A) 48

3.02.1 applicable standards IEC 60551

3.03 Remote control Interface terminals/cubicle yes

B. 11 kV Air-Insulated Switchgear
3.04 Common
3.04.1 nominal operating voltage kV 11

3.04.2 rated voltage kV 12

3.04.3 frequency Hz 50

3.04.4 insulation level


3.04.4.1 power frequency withstand voltage, 1 min.
3.04.4.1.1 phase to phase and phase to earth kV 28

3.04.4.1.2 across isolating distance kV 32

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 9 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

3.04.4.2 lightning impulse withstand voltage


3.04.4.2.1 phase to phase and phase to earth kV 75

3.04.4.2.2 across isolating distance kV 85

3.04.5 rated short-circuit current, 1s kA 25

3.05 Busbars
3.05.1 insulation medium air

3.05.2 rated current carrying capacity at max. 40°C A 1250

3.05.3 operating current carrying capacity at max. 50°C A

3.06 Circuit breaker (vacuum)


3.06.1 rated currents at 40°C
3.06.1.1 outgoing feeder A 630

3.06.1.2 incoming feeder A 630

3.06.1.3 busbar sectionaliser A 1250

3.06.2 operating currents at 50°C


3.06.2.1 outgoing feeder A

3.06.2.2 incoming feeder A

3.06.2.3 busbar sectionaliser A

3.06.3 rated breaking current capacity


3.06.3.1 short circuit breaking current
3.06.3.1.1 AC component r.m.s. value kA >25

3.06.3.1.2 DC component %

3.06.3.1.3 asymmetrical including DC component kA

3.06.3.2 line charging breaking current A

3.06.3.3 cable-charging breaking current A 50

3.06.3.4 maximum capacitive breaking current A 0.8 x In

3.06.3.5 small inductive breaking current A 10

3.06.3.6 out of phase breaking current A

3.06.4 rated making current capacity


3.06.4.1 short circuit making current kA

3.06.5 time ratings

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 10 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

3.06.5.1 opening time at


3.06.5.1.1 10% of rated short-circuit current ms

3.06.5.1.2 30% of rated short-circuit current ms

3.06.5.1.3 60% of rated short-circuit current ms

3.06.5.1.4 100% of rated short-circuit current ms

3.06.6 maximum spring recharging time sec 25

3.06.7 interrupter
3.06.7.1 manufacturer
3.06.7.1.1 name
3.06.7.1.2 country of manufacturing
3.06.7.2 arc quenching medium vacuum

3.06.7.3 pressure/vacuum inside the interrupter mmHg

3.06.7.4 contact wear indication provided yes

3.06.7.5 facility for checking loss of vacuum provided yes/no

3.06.7.6 vacuum monitoring relay provided yes/no

3.06.7.7 shielding against X-Ray radiations provided yes/no

3.06.7.8 length of interruption mm

3.06.7.9 type of contact material


3.06.7.9.1 main
3.06.7.9.2 arcing
3.06.7.9.3 contacts silver plated yes

3.06.7.9.3.1 thickness of plating µm

3.06.7.9.4 contact pressure on main contacts kg/m2

3.06.7.9.5 contact pressure on arcing contacts kg/m2

3.06.7.10 maximum temperature rise over the specified °C


ambient temperature
3.06.7.11 heat dissipation at normal current kW

3.06.7.12 number of switchings during life time


3.06.7.12.1 with rated current No.

3.06.7.12.2 with rated short circuit breaking current No.

3.06.7.13 number of operations within 10 years

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 11 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

(before first inspection and maintenance)


3.06.7.13.1 switching at rated load No. min. 20000

3.06.7.13.2 switching at 100% fault capacity No. min. 100

3.06.7.13.3 switching at 50% fault capacity No.

3.06.7.13.4 making under fault conditions No.

3.06.8 whether the circuit breaker is suitable for yes/no


trip-free or fixed trip operation (mechanically)
and (electrically)
3.06.9 whether the circuit breaker designed to close yes/no
and latch on making or fitted with current
release
3.06.10 whether any pumping device provided yes/no

3.06.11 rated supply voltage of operating mechanism


3.06.11.1 closing coil Vdc 48

3.06.11.1.1 allowable variation of voltage ±% +10% -20%

3.06.11.1.2 power required at normal voltage kW

3.06.11.2 tripping coil Vdc 48

3.06.11.2.1 allowable variation of voltage ±% +10% -20%

3.06.11.2.2 power required at normal voltage kW

3.06.11.3 spring charging motor Vdc 48

3.06.11.3.1 allowable variation of voltage ±% +10% -20%

3.06.11.3.2 power required at normal voltage kW

3.06.11.3.3 motor rated current A

3.06.11.3.4 motor starting current A

3.06.12 rated voltage of shunt opening release V

3.06.12.1 normal current at rated voltage A

3.06.12.2 power W

3.06.12.3 duration ms

3.06.13 whether control circuitry is suitable for yes/no


monitoring of closing and tripping circuits
3.06.14 auxiliary switches
3.06.14.1 type

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 12 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

3.06.14.2 number No.

3.06.14.3 normal current at rated voltage A

3.06.14.4 breaking current A

3.06.15 current required at rated voltage by other


auxiliaries A

3.06.16 auxiliary contacts (directly driven)


3.06.16.1 normally open (NO) when breaker is closed No. 10

3.06.16.2 normally close (NC) when breaker is closed No. 10

3.06.16.3 adjustable w.r.t the position of main contacts No.

3.06.17 wiping contacts


3.06.17.1 number No. 2

3.06.17.2 current carrying capacity A

3.06.17.3 breaking capacity A

3.06.17.4 voltage Vdc 48

3.07 Earthing switch


3.07.1 motor drive
3.07.1.1 power W

3.07.1.2 rated voltage Vdc 48

3.07.1.3 rated current A

3.07.1.4 starting current A

3.07.2 auxiliary contacts (directly driven)


3.07.2.1 NO No. 10

3.07.2.2 NC No. 10

3.07.2.3 breaking capacity kA

3.08 Space heater


3.08.1 power W

3.08.2 rated voltage Vac 230

3.08.3 rated current A

C. Wiring
3.09 Power frequency withstand voltage kV ac1min 2

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 13 of 14
MV SWITCHGEAR
11 kV Switching Station (Withdrawable 11 kV CB's)

Sl. No. REQUIRED TENDERED

4.00 OTHER PERFORMANCE DATA

A. Voltage and Current Transformers as per requirement


specified in standard
technical specification,
part: S-AAA-SWG-MV-LV-VTCT

B. Metering Devices, Instruments as per requirement


specified in standard
technical specification,
part: S-AAA-MET-GEN

C. Protection as per requirement


specified in standard
technical specification
part: S-AAA-CPS-MV-LV-PROT

5.00 OTHER PERFORMANCE DATA


5.01 First commercial operation of the offered unit
5.01.1 date dd-mm-yy

5.01.2 according to the attached reference list/sheet

6.00 SUPPORTING DOCUMENTS


6.01 Type test reports enclosed yes

6.02 Technical literature enclosed yes

6.03 Standard conditions of installation enclosed yes

6.04 Relevant drawings enclosed yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-SWST-WD (Rev.0-2015) Page 14 of 14