Standard Technical Specifications for Electrical Works

MV SWITCHGEAR
( Data Sheets )

22 kV RMU with Load-Break Switches and Vacuum/SF6


Breaker
(Self-Powered Scheme)

ADWEA/ADDC/AADC STANDARD : D-AAA-SWG-MV-RMU-22-SP


(Rev.0-2018)

________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 1 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Table of Content

Page

1.00 GENERAL 3

2.00 CONSTRUCTION DATA 3


A. External Housing 3
B. 22 kV RMU 6
C. Protection (Only for transformer Feeders) 10
D. Wiring 11

3.00 ELECTRICAL DATA 12


A. General 12
B. 22 kV Switchgear (RMU) 12
C. Wiring 21

4.00 OTHER TECHNICAL DATA 22


A. Voltage and Current Transformers 22
B. Metering Devices, Instruments 22
C. Corrosion Protection 22

5.00 OTHER PERFORMANCE DATA 22

6.00 SUPPORTING DOCUMENTS 22

_____________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 2 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

1.00 GENERAL

1.01 Applicable standards IEC 62271

1.02 Type test


1.02.1 carried out yes/no

1.02.2 date dd-mm-yy

1.02.3 testing laboratory


1.02.3.1 name
1.02.3.2 country
1.03 Installation location yes/no

1.03.1 outdoor No

1.03.2 indoor Yes

1.04 Weight of complete assembled RMU kg

1.05 Type
1.06 Commercial operation time of offered switchgear years min.5

1.07 Type

2.00 CONSTRUCTION DATA

A. External Housing
2.01 Manufacturer
2.01.1 name
2.01.2 country of manufacturing
2.02 Applicable standards IEC

2.03 Dimensions
2.03.1 length mm

2.03.2 width mm

2.03.3 height mm

2.04 Degree of protection IP 4X (Min)

2.05 Base plate


2.05.1 material galvanised steel sheet

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 3 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.05.2 grade
2.05.3 applicable standards
2.05.4 minimum thickness mm 3

2.06 Walls
2.06.1 material galvanised steel sheet

2.06.2 applicable standards


2.06.3 minimum thickness mm 2

2.07 Roof
2.07.1 material galvanised steel sheet

2.07.2 applicable standards


2.07.3 minimum thickness mm 2

2.08 Door
2.08.1 material galvanised steel sheet

2.08.2 applicable standards


2.08.3 minimum thickness mm 2

2.08.4 door stopper


2.08.4.1 gas-spring type yes/no
2.08.5 door fixings to fix the door panel during yes
maintenance
2.09 Protection against accumulation of water on roof yes

2.10 Ventilation yes

2.11 Vermin proof yes/no

2.12 Earthing arrangement


2.12.1 earth bar
2.12.1.1 material copper
2
2.12.1.2 minimum cross-section mm 120

2.12.1.3 dimension
2.12.1.3.1 width mm

2.12.1.3.2 height mm
2.12.2 interconnection between external housing and
RMU tank

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 4 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.12.2.1 material stranded copper


conductor

2.12.2.2 minimum cross-section mm2 120

2.12.3 number of connections for external earthing No. 2

2.12.4 copper rods at housing


2.12.5 external earthing rods
2.12.5.1 material copper covered
stainless steel

2.12.5.2 minimum number No. 2

2.12.5.3 diameter mm 19

2.13 Danger sign details (at door)


2.13.1 material stainless steel

2.13.1.1 grade 1.4301 (V2A)

2.13.2 width mm

2.13.3 height mm

2.13.4 letters
2.13.4.1 quality of paint sun light proof, no fading

2.13.4.2 height of letters mm 100

2.13.5 colors
2.13.5.1 background
2.13.5.2 letters red

2.13.6 fixing bolts


2.13.6.1 material stainless steel

2.13.6.1.1 grade 1.4301 (V2A)

2.13.7 numbers No.

2.14 Identification plate details


2.14.1 material stainless steel

2.14.1.1 grade 1.4301 (V2A)

2.14.2 width mm

2.14.3 height mm

2.14.4 letters

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 5 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.14.4.1 quality of paint sun light proof, no fading

2.14.4.2 height of letters mm 100

2.14.5 colors
2.14.5.1 background
2.14.5.2 letters red

2.14.6 fixing bolts


2.14.6.1 material stainless steel

2.14.6.1.1 grade 1.4301 (V2A)

2.14.7 numbers No. 1

2.15 Lifting devices details


2.15.1 housing
2.15.1.1 number 4

2.16 Cable protection yes

2.16.1 22 kV underground cable protection box yes


2.17 Stainless steel used for handles, hinges, signs,
bolts, nuts, etc.
2.17.1 grade 1.4301 (V2A)

B. 22 kV RMU
2.18 Manufacturer
2.18.1 name
2.18.2 country of manufacturing
2.19 Tank
2.19.1 material
2.19.1.1 stainless steel yes/no

2.19.2 grade
2.19.3 thickness mm 3

2.19.4 degree of protection IP 67


0
2.19.5 SF6 gas pressure at 20 C (Minimum) bar 0.2
0
2.19.6 SF6 gas pressure at 50 C bar

2.19.7 gaskets

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 6 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.19.7.1 material
2.20 Busbars
2.2.1 material copper

2.21.1 dimensions
2.21.1.1 height mm

2.21.1.2 width mm

2.21.2 number of runs No.

2.21.3 minimum clearances


2.21.3.1 between phases mm

2.21.3.2 phases to earth mm

2.21.4 insulation SF6

2.21 Busbar support insulators


2.21.1 manufacturer
2.21.1.1 name
2.21.1.2 country of manufacturer
2.21.2 applicable standards IEC

2.21.3 type
2.21.4 material
2.21.5 creepage distance mm
2.22 Min. distance between center hole of bushings mm 600
and bottom plate
2.23 Circuit breaker (transformer 1 or 2)
2.23.1 manufacturer
2.23.1.1 name
2.23.1.2 country of manufacturing
2.23.2 applicable standards IEC 62271-100

2.23.3 class E2-C2-M1

2.23.4 no. of poles 3

2.23.5 arc-quenching medium


2.23.5.1 vacuum yes/no

2.23.5.2 SF6 yes/no

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 7 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.23.6 operating facilities


2.23.6.1 hand yes

2.23.6.2 motor (provision only including wiring) yes

2.23.6.3 counter (with future motor) yes

2.23.6.4 remote control (provide DMS.Interfacing cubicle) yes

2.23.6.5 CT for SP protection yes

2.23.6.6 CT for metering (if applicable) yes

2.23.7 mechanical position indicator of main contact yes

2.23.8 interlocking with earth switch yes

2.23.9 mechanical trip free operation mechanism in yes

2.23.10 transformer feeder


2.23.11 operation mechanism
2.23.11.1 opening spring

2.23.11.2 closing spring


2.24 Load-break cum earthing switch 2F (for QRM & TRM) Yes
(incoming/outgoing feeders) 3F (for 3F+1T Conf) Yes

2.24.1 manufacturer 3F (for 3F Conf) Yes

2.24.1.1 name 4F (for 4F Conf) Yes

2.24.1.2 country of manufacturing


2.24.2 applicable standards IEC 62271-103

2.24.3 class E3-M1

2.24.4 no. of poles 3

2.24.5 arc-quenching medium


2.24.5.1 vacuum yes/no

2.24.5.2 SF6 yes/no

2.24.6 operating facilities


2.24.6.1 hand yes

2.24.6.2 motor yes

2.26.5.3 remote control (provide DMS marshalling box) yes

2.26.6 mechanical position indicator of main contact yes

2.26.7 operation mechanism

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 8 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.26.7.1 opening spring

2.26.7.2 closing spring

2.25 Earthing switch (transformer feeder)


2.25.1 manufacturer
2.25.1.1 name
2.25.1.2 country of manufacturing
2.25.2 applicable standards IEC 62271-102

2.25.3 class E2

2.25.4 no. of poles 3

2.25.5 arc-quenching medium


2.25.5.1 SF6 yes

2.25.6 operating facilities


2.25.6.1 hand yes

2.25.7 interlocking with CB provided yes

2.25.8 mechanical position indicator of main contact yes

2.26 SF6 pressure indicator


2.26.1 manufacturer
2.26.1.1 name
2.26.1.2 country of manufacturing
2.26.2 applicable standards IEC

2.26.3 remote indication provided yes

2.27 Fault indicator (Quntity as per Schematic Drawing and for all cable feeders)
2.27.1 manufacturer
2.27.1.1 name
2.27.1.2 country of manufacturing
2.27.2 applicable standards IEC

2.27.3 housing
2.27.3.1 material
2.27.3.2 window transparent plastic

2.27.3.3 degree of protection IP 54

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 9 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.27.4 remote indication provided yes/no

2.27.5 current transformer


2.27.5.1 core-balance yes

2.27.5.2 burden VA

2.27.6 type
2.27.7 re-set manual with remote end re-set facilities no

2.27.8 re-set automatic with remote end indication yes

2.27.8.1 power
2.27.8.1.1 from CT or AC auxiliary supply yes

2.27.8.1.2 from built-in battery no

2.28 Potential indicators


2.28.1 manufacturer
2.28.1.1 name
2.28.1.2 country of manufacturing
2.28.2 applicable standards IEC 61958
61234-5
2.28.3 type plug-in

2.28.4 provided for each phase and feeder yes

C. Protection (Only for transformer Feeders)


2.29 Self-powered numerical protection relays
2.29.1 manufacturer
2.29.1.1 name
2.29.1.2 country of manufacturing
2.29.2 applicable standards IEC 60255

2.29.3 type numerical

2.29.4 type test


2.29.4.1 carried out yes/no

2.29.4.2 date dd-mm-yy

2.29.4.3 testing laboratory


2.29.4.3.1 name
2.29.4.3.2 country

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 10 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

2.29.5 housing
2.29.5.1 material
2.29.5.2 window transparent plastic

2.29.5.3 degree of protection IP 54

2.29.6 withstand transformer inrush current yes

2.29.7 permits transformer overload yes

2.29.8 coordinated with down-stream HRC feeder fuses yes

2.29.9 self-check with status indications


2.29.9.1 overcurrent yes

2.29.9.2 earth-fault yes

2.29.10 energy storage capacitor bank built-in yes

2.29.11 time/current characteristsic submitted with the bid yes

2.29.12 schematic diagram submitted with the bid yes

2.30 Transformer oil temperature trip and alarm yes

2.30.1 Auxiliary relay provided in the RMU yes


2.31 Commercial operating time of offered switchgear years 5
type

D. Wiring
2.32 Material
2.34.1 stranded copper wires yes

2.33 Cross-sections
2.33.1 power circuits (min) mm2 1.5
2
2.33.2 control circuits mm 1
2
2.33.3 CT circuits (min) mm 2.5
2
2.33.4 VT circuits (min) mm 1.5

2.33.5 telecommunication/control/protection connections


2.33.5.1 pairs are screened (for communication) yes
2
2.33.5.2 external wiring mm 1.5
2
2.33.5.3 other wiring mm 0.5

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 11 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

E. DMS requirements
2.34 DC Voltage Refer to Note 4 V 24

2.35 Status Signals


Common Selector Switch for Incoming/Outgoing Local/Remote Selector
2.35.1
Feeders Switch
2.35.2 Incoming/Outgoing Feeders ON/OFF Switches

2.35.3 Transformer Feeder(s) ON/OFF CB


ON/OFF Dummy Relay
2.35.4 Common (RMU) ON/OFF (Ac&Dc) MCB
2.36 Control
OPEN/CLOSE
2.36.1 Incoming/Outgoing Feeder(s) Switches
OPEN CB
2.36.2 Transformer Feeder(s) (Closing only from RTU Panel and
not from DMS)
AUTO-RESET on Power
2.36.3 EFI at Outgoing restoration with Auxiliary Contact
for Remote Indication

2.36.4 Dummy relay CLOSE/OPEN

2.37 Alarm
2.37.1 Outgoing Feeder EARTH FAULT Indication
TRIP O/C
2.37.2 Transformer Feeder
TRIP E/F
ALARM SF6
2.37.3 Common (RTU) ALARM 24V Dc Fail
Transformer Relay Failure
R & B Current for
2.37.4 Measurement
Transformer Feeder
2.38 Marshalling Box Refer to Note 5

3.00 ELECTRICAL DATA

A. General
3.01 Radio influence voltage at 1 Mhz (maximum). dB

3.02 Noise level dB(A) 48

3.03 Remote control interface terminals/cubicle yes

B. 22 kV Switchgear (RMU)

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 12 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.04 Common
3.04.1 nominal operating voltage kV 22

3.04.2 rated voltage kV

3.04.3 maximum system voltage kV 24

3.04.4 frequency Hz 50

3.04.5 insulation level


3.04.5.1 power frequency withstand voltage, 1 min.
3.04.5.1.1 phase to phase and phase to earth kV 50

3.04.5.1.2 across isolating distance kV

3.04.5.2 lightning impulse withstand voltage


3.04.5.2.1 phase to phase and phase to earth kV 125

3.04.5.2.2 across isolating distance kV

3.04.6 short circuit withstand current, 1s


3.04.6.1 switches kA 20

3.04.6.2 circuit breaker kA 20

3.05 Busbars
3.05.1 rated current carrying capacity at 40°C A 630

3.05.2 operating current carrying capacity at 50°C A

3.06 Circuit breaker (Transformer Feeder No.1, as applicable)


3.06.1 currents at 400C
3.06.1.1 rated A 200

3.06.1.2 off-load transformer making capacity A

3.06.1.3 short-circuit breaking capacity kA 20

3.06.1.4 making capacity KApeak 50


0
3.06.2 currents at 50 C
3.06.2.1 rated A

3.06.2.2 off-load transformer making capacity A

3.06.2.3 short-circuit breaking capacity kA 20

3.06.2.4 making capacity KApeak 50

3.06.3 opening time at

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 13 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.06.3.1 10% of rated short-circuit current ms

3.06.3.2 30% of rated short-circuit current ms

3.06.3.3 60% of rated short-circuit current ms

3.06.3.4 100% of rated short-circuit current ms

3.06.4 interrupter
3.06.4.1 manufacturer
3.06.4.1.1 name
3.06.4.1.2 country of manufacturing
3.06.4.2 pressure/vacuum inside the interrupter mmHg

3.06.4.3 length of interruption mm

3.06.4.4 type of contact material


3.06.4.4.1 main
3.06.4.4.2 arcing
3.06.4.4.3 contacts silver plated yes

3.06.4.4.3.1 thickness of plating μm

3.06.4.4.4 contact pressure on main contacts kg/m2

3.06.4.4.5 contact pressure on arcing contacts kg/m2

3.06.4.5 maximum temperature rise over the specified


3.06.4.6 ambient temperature °C

3.06.4.7 heat dissipation at normal current kW

3.06.4.8 number of switchings during life time


3.06.4.8.1 with rated current No.

3.06.4.8.2 with rated short circuit breaking current No.


3.06.4.9 number of operations within 10 years
(before first inspection and maintenance)
3.06.4.9.1 switchings at rated load No. min. 2000

3.06.4.9.2 switchings with rated making current No. <10

3.06.4.9.3 switching at OFF load (mechanical) No. min. 2000

3.06.4.9.4 making under fault conditions No.


3.06.5 whether the circuit breaker is suitable for yes/no
trip-free or fixed trip operation (mechanically)

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 14 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

and (electrically)
3.06.6 whether anti pumping device provided yes/no

3.06.7 rated supply voltage of operating mechanism


3.06.7.1 closing coil Vac

3.06.7.1.1 allowable variation of voltage ±% -0.1

3.06.7.1.2 power required at normal voltage kW

3.06.7.2 tripping coil Vac

3.06.7.2.1 allowable variation of voltage ±% -0.1

3.06.7.2.2 power required at normal voltage kW

3.06.7.3 spring charging motor Vac

3.06.7.3.1 allowable variation of voltage ±% -0.1

3.06.7.3.2 power required at normal voltage kW

3.06.7.3.3 motor rated current A

3.06.7.3.4 motor starting current A

3.06.8 rated voltage of shunt opening release V

3.06.8.1 normal current at rated voltage A

3.06.8.2 power W

3.06.8.3 duration ms
3.06.9 whether control circuitry is suitable for yes/no
monitoring of closing and tripping circuits
auxiliary switches
3.06.9.1 type
3.06.9.2 number No.

3.06.9.3 normal current at rated voltage A

3.06.9.4 breaking current A

3.06.10 current required at rated voltage by other


3.06.11 auxiliaries A

3.06.12 auxiliary switch contacts


3.06.12.1 NO No. 2

3.06.12.2 NC No. 2

3.06.12.3 those adjustable w.r.t the position of main No.

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 15 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.06.12.4 contacts
3.06.12.5 current carrying capacity A

3.06.12.6 breaking capacity kA

3.06.12.7 voltage Vdc

3.07 Circuit breaker (Transformer Feeder No.2, as applicable)


3.07.1 currents at 400C
3.07.1.1 rated A 200

3.07.1.2 off-load transformer making capacity A

3.07.1.3 short-circuit breaking capacity kA 20

3.07.1.4 making capacity KApeak 50


0
3.07.2 currents at 50 C
3.07.2.1 rated A

3.07.2.2 off-load transformer making capacity A

3.07.2.3 short-circuit breaking capacity kA 20

3.07.2.4 making capacity KApeak 50

3.07.3 opening time at


3.07.3.1 10% of rated short-circuit current ms

3.07.3.2 30% of rated short-circuit current ms

3.07.3.3 60% of rated short-circuit current ms

3.07.3.4 100% of rated short-circuit current ms

3.07.4 interrupter
3.07.4.1 manufacturer
3.07.4.1.1 name
3.07.4.1.2 country of manufacturing
3.07.4.2 pressure/vacuum inside the interrupter mmHg

3.07.4.3 length of interruption mm

3.07.4.4 type of contact material


3.07.4.4.1 main
3.07.4.4.2 arcing
3.07.4.4.3 contacts silver plated yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 16 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.07.4.4.3.1 thickness of plating μm

3.07.4.4.4 contact pressure on main contacts kg/m2

3.07.4.4.5 contact pressure on arcing contacts kg/m2


3.07.4.5 maximum temperature rise over the specified
ambient temperature °C

3.07.4.6 heat dissipation at normal current kW

3.07.4.7 number of switchings during life time


3.07.4.7.1 with rated current No.

3.07.4.7.2 with rated short circuit breaking current No.


3.07.4.8 number of operations within 10 years
(before first inspection and maintenance)
3.07.4.8.1 switchings at rated load No. min. 2000

3.07.4.8.2 switchings with rated making current No. <10

3.07.4.8.3 switching at OFF load (mechanical) No. min. 2000

3.07.4.8.4 making under fault conditions No.


3.07.5 whether the circuit breaker is suitable for yes/no
trip-free or fixed trip operation (mechanically)
and (electrically)
3.07.6 whether anti pumping device provided yes/no

3.07.7 rated supply voltage of operating mechanism


3.07.7.1 closing coil Vac

3.07.7.1.1 allowable variation of voltage ±% -0.1

3.07.7.1.2 power required at normal voltage kW

3.07.7.2 tripping coil Vac

3.07.7.2.1 allowable variation of voltage ±% -0.1

3.07.7.2.2 power required at normal voltage kW

3.07.7.3 spring charging motor Vac

3.07.7.3.1 allowable variation of voltage ±% -0.1

3.07.7.3.2 power required at normal voltage kW

3.07.7.3.3 motor rated current A

3.07.7.3.4 motor starting current A

3.07.8 rated voltage of shunt opening release V

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 17 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.07.8.1 normal current at rated voltage A

3.07.8.2 power W

3.07.8.3 duration ms
3.07.9 whether control circuitry is suitable for yes/no
monitoring of closing and tripping circuits
3.07.10 auxiliary switches
3.07.10.1 type
3.07.10.2 number No.

3.07.10.3 normal current at rated voltage A

3.07.10.4 breaking current A

3.07.11 current required at rated voltage by other


3.07.12 auxiliaries A

3.07.13 auxiliary switch contacts


3.07.13.1 NO No. 2

3.07.13.2 NC No. 2
3.07.13.3 those adjustable w.r.t the position of main No.
contacts
3.07.13.4 current carrying capacity A

3.07.13.5 breaking capacity kA

3.07.13.6 voltage Vdc


3.08 Load-break cum earthing switch
(incoming/outgoing cable feeders)
3.08.1 currents at 400C
3.08.1.1 rated A 630

3.08.1.2 short-circuit breaking capacity kA 20

3.08.1.3 making capacity KApeak 50

3.08.1.4 breaking capacity


3.08.1.4.1 charging current A

3.08.1.4.2 earth leakage fault current A

3.08.1.4.3 no-load cable current A

3.08.2 currents at 500C

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 18 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.08.2.1 rated A

3.08.2.2 short-circuit breaking capacity kA 20

3.08.2.3 making capacity KApeak 50

3.08.2.4 breaking capacity


3.08.2.4.1 charging current A

3.08.2.4.2 earth leakage fault current A

3.08.2.4.3 no-load cable current A

3.08.2.5 type of contact material


3.08.2.5.1 main
3.08.2.5.2 arcing
3.08.2.5.3 contacts silver plated yes

3.08.2.5.3.1 thickness of plating µm

3.08.2.5.4 contact pressure on main contacts kg/m2

3.08.2.5.5 contact pressure on arcing contacts kg/m2

3.08.2.6 maximum temperature rise over the specified °C

3.08.2.7 ambient temperature


3.08.2.8 heat dissipation at normal current kW

3.08.2.9 number of switchings during life time


3.08.2.9.1 with rated load-breaking current No.

3.08.3 remote operation (if applicable) yes

3.08.3.1 closing time with motor drive ms

3.08.3.2 opening time with motor drive ms

3.08.3.3 min. break command time ms

3.08.3.4 arcing time ms

3.08.4 motor drive


3.08.4.1 power W

3.08.4.2 rated voltage Vac

3.08.4.3 rated current A

3.08.4.4 starting current A

3.08.5 no. of aux. contacts

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 19 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.08.5.1 NO No. 2

3.08.5.2 NC No. 2

3.08.5.3 breaking capacity kA

3.09 Earthing switch (transformer feeder)


3.09.1 no. of aux. contacts
3.09.1.1 NO No. 2

3.09.1.2 NC No. 2

3.09.1.3 breaking capacity kA


Self-Powered Numerical O/C & E/F Relay (Inverse &
3.10
Instantaneous), For Transformer Feeders Only
3.10.1 general
3.10.1.1 DC infeed
3.10.1.1.1 rated voltage V self-powered

3.10.1.1.2 DC/DC converter included yes

3.10.1.1.3 allowable tolerances % -0.666667

3.10.1.1.4 power consumption W

3.10.1.2 rated current A 1

3.10.1.3 permissible overload


3.10.1.3.1 continuously x IN x IN 2

3.10.1.3.2 for 1 s x IN 100

3.10.1.4 protection class of relay housing IP 52

3.10.2 architecture
3.10.2.1 characteristics
3.10.2.1.1 characteristic acc. to IEC 60255 yes

3.10.2.1.2 IDMT inverse yes

3.10.2.1.2.1 very inverse yes

3.10.2.1.2.2 extremely inverse yes

3.10.2.1.3 definite time yes

3.10.2.2 instantaneous element included yes

3.10.3 protection Measuring Units


3.10.3.1 current setting

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 20 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.10.3.1.1 phase elements 20 to 200%

3.10.3.1.1.1 in steps < 10%

3.10.3.1.2 earth element x IN 10 to 80%

3.10.3.1.2.1 in steps < 5%

3.10.3.1.3 operating time x IN

3.10.3.1.3.1 continuous variable yes

3.10.3.1.3.2 alternatively
3.10.3.1.3.3 variable in steps ms ≤ 10

3.10.3.2 high set 2 to 30x IN and blocked yes

3.10.3.3 high set continuously variable or in steps of x IN 1

3.11 Self powered numerical stand-by E/F relay (For Transformer Feeders Only)
3.11.1 general
3.11.1.1 DC infeed
3.11.1.1.1 rated voltage V

3.11.1.1.2 DC/DC converter included yes

3.11.1.1.3 tolerances requested % -0.666667

3.11.1.1.4 power consumption W

3.11.1.2 rated current A 1

3.11.1.2.1 permissible overload


3.11.1.2.1.1 continuously x IN x IN 2

3.11.1.2.1.2 for 1 s x IN 100

3.11.1.3 protection class of relay housing IP 52

3.11.2 architecture
3.11.2.1 characteristics
3.11.2.1.1 characteristic acc. to IEC 60255 yes

3.11.2.1.2 IDMT inverse yes

3.11.2.1.2.1 very inverse yes

3.11.2.1.2.2 extremely inverse yes

3.11.2.1.3 definite time yes

3.11.2.2 instantaneous element included yes

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 21 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

3.11.3 protection measuring units


3.11.3.1 current setting
3.11.3.1.1 phase elements x IN 20 to 200%

3.11.3.1.1.1 in steps < 10%

3.11.3.1.2 earth element x IN 10 to 80%

3.11.3.1.2.1 in steps < 5%

3.11.3.1.3 operating time


3.11.3.1.3.1 continuous variable yes

3.11.3.1.3.2 alternatively
3.11.3.1.3.3 variable in steps ms ≤ 10

3.11.3.2 high set 2 to 30x IN and blocked yes

C. DMS Requirements
Refer to Note 4 Vdc
3.12 Voltage 24

D. Wiring
3.13 Power frequency withstand voltage kVac/1min 2

4.00 OTHER TECHNICAL DATA

A. Voltage and Current Transformers as per requirement


specified in standard
technical specification,
part: S-AAA-SWG-MV-VTCT

B. Metering Devices, Instruments as per requirement


specified in standard
technical specification,
part: S-AAA-MET-AI, AAA-MET-DI,
S-AAA-MET-MPBEM-02S

C. Corrosion Protection as per requirement


specified in standard
technical specification,
part: S-AAA-CORR

5.00 OTHER PERFORMANCE DATA

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________
D-AAA-SWG-MV-RMU-22-SP (Rev 0-2018).xls Page 22 of 22
MV SWITCHGEAR
22 kV RMU with Load-Break Switches and Vacuum/SF6 Breaker (Self-Powered Scheme)

Sl. No. REQUIRED TENDERED

5.01 Date of first commercial operation of the offered unit dd-mm-yy


5.02 Reference list attached yes/no

6.00 SUPPORTING DOCUMENTS

6.01 Type test reports enclosed yes

6.02 Technical literature enclosed yes

6.03 Standard conditions of installation enclosed yes

6.04 Relevant drawings enclosed yes

NOTES

The Selector Switch for LOCAL/REMOTE control of RMU shall be fixed on the RTU panel. In the
1 LOCAL mode, the incoming/outgoing feeders and transformer CB shall be OPEN/CLOSE from the
RTU panel. Only in case of emergency, it can be operational from the switchgear

Only major parameter listed, other standard features and arrangement as per ADDC-AADC
2 specifications.

EFI shall be Lithium Battery powered and self-reset type (time based and upon power supply
3 restoration)

The 24V Battery shall be located within the RTU panel and shall be designed for a back-up of
4 minimum period of 24hrs after failure of the supply.

Supply of RTU is not included. However, a marshalling box shall be supplied and all Ai, DI & Dos shall
5 be wired upon the marshalling box.

6 Dummy relay is for the healthiness of the RTU/Communication and is part of RTU.

TENDERER`s STAMP SIGNATURE

___________________________________________________________________________________________________________________