VCT7-12 Series
Indoor Ac High Voltage Vacuum Circuit Breaker
of the manufacturer
● The two wiring shall refer to the two drawing of the circuit breaker
● The manufacturer will not be liable for any failure caused by failure to comply
1. Introduction 1
3. Using Conditions 1
4. Technical Data 2
5. Basic Structure 3
6. Working Principal 3
15. Ordering 10
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
1. Introduction
AC high voltage circuit breaker type VCT7-12 series (short named as“VCB”below) is an indoor switchgear
component of three-phase, AC 50Hz, rated voltage 12kV. It tallies with the specifications of national and international
standards AC High Voltage Circuit Breaker GB/T 1984 and AC High Voltage Circuit Breaker IEC62271-100 etc..
The product is used as control and protection in entriprises of mining and industry, power generating plant and
substation etc as well as in occasions switching frequently, which has high reliability in switching and long endurance.
The assembling form inside switchgear cubicle for VCB can be in type of withdrawal trolly, or in fixed type.
3. Using Conditions
3.1 Normal using conditions
● Ambient temperature: -5℃~+40℃;
● Elevation above sae level: not more than 1000m;
● Relative humidity: daily average relative humidity does not exceed by 95%, monthly average relative humidity does
not exceed by 90%; daily average saturation pressure does not exceed 2.2kPa, monthly average saturation pressure
does not exceed 1.8kPa.
● Earthquake Intensity: not more than magnitude 8;
● Places without fire, explosion, heavy pollution, chemical corrosion and violent shocking.
1
Installing and Operating Instruction
4. Technical Data
4.1 Technical parameters of breaker Table 1 Main technical parameter of VCB
No. Name Unit Data
1 Rated voltage kV 12
4.2 The techanical data for spring charging motor of operation mechanism refer to table 2.
Rated voltage (V) Rated output power (W) Scope of normal working voltage (V) Charging time under rated voltage (s)
DC110
90 85%~110% ≤15
DC220
4.3 The techanical data of opening and closing coils refer to table 4.
Rated switching voltage (V) DC220, DC110, AC220, AC110 DC220, DC110, AC220, AC110
2
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
5. Basic Structure
a) Intermediate sealing type porcelain or glass vacuum interrupter TD14-24 series is fitted with the product, which adopts
CuCr material of contact and cup-like structure of axial magnetic field (AMF). The features is small in electrical wearing,
long in electrical endurance, high in withstanding voltage level, stable in medium dielectric strength, quick in post-arc
recovering, low in current choping and strong in breaking capacity.
b) Total structure of VCB adopts the form of operation mechanism in front and interrupter at rear, main conductive circuit is
three-phase structure of falling-to-the-ground type, vacuum circuit breaker is fitted horizontally inside an insulating tube,
which is made of epoxy resin by APG processing, it is especially with anti-creepage. The structure of design can greatly
reduce the dust on the surface of interrupter. It can not only prevent vacuum interrupter from destroying from external
factors, but ensure high resistance state to voltage-effection even under moisture and hot condition, as well as heavy
polluted areas.
c) It is fitted with spring charging operation mechanism, having functions of manual charging and electrical motor charging.
The mechanism is an independent function unit, which intergrate charging, transmitting output and trip etc, and is arranged
in front of the box of interrupter. It has features of compact in structure, small in volume and reliable in switching.
d) VCB has the advantages of long endurance, simple maintenance, no pollution and explosion as well as low noise,
which is used in places switching frequently.
6. Working Principal
6.1 Arc-quenching theory
Much higher vacuum degree is hold as fitted with vacuum interrupter. Vacuum arc will occur between contacts when
opening of moving and fixed contact is done afffected by operation mechanism. Meanwhile, the axial magnetic
field, produced in the gap of contact, make vacuum arc diffusion and maintain low arc voltage because of special
structure of contact. The residual ions, electrons and metal vapour can be compounded or condensed on the
surface of contact and on screen cover withinμs order of magnitude as current passes zero, the midium dielectric
strength of interrupter breaks recover quickly to quench the arc. It has strong and stable capacity of breaking
current, because vacuum circuit breaker adopts AMF to control vacuum arc.
6.2 Operating theory
The structure diagram of operation mechanism refers to Fig.1.
closing cam
closing wheel
main shaft
opening wheel
3
Installing and Operating Instruction
a. Charging operation
Whether it is charging handle or the charging motor, drive the storage shaft rotate when operation, stretch the closing
spring, and charge the spring, when spring reaches the highest point, the closing cam leans on the closing keeping
detent, the storage operation is done.
b. Close operation
When it is electric closing coil or manual push closing coil to drive the closing button and closing link, keep the closing
holding detent open and the closing cam rotates, drive the closing wheel on spindle to make the spindle rotates, press
the big crank arm to make the mechanism close.
c. Open operation
After closing the mechanism, keep the detent against the opening roller on the spindle, so that the mechanism is close,
when it is electric opening coil or manual push opening button to drive the opening button and opening link, so that
the opening keeping detent is open, when the keep detent rotates, spindle loses it’s support and rotates, and the
mechanism is open.
X: 8 32 26 24 25 4 20 31 3 5 9 7 34 23 28 41 43 46 2 27
1 1 1 1
+ - + - + - + -
1 CK
2 1 1
U1 U2 2 U3 U4
KO Y1 YT
2 M 2 2 2
53 2 2
1
54 QF
R0
2
JP2 YC 1 1
JP1 Y7 Y8
1
51 13 73 11 2 2
31 41 61 71 81 23 33 43 63 83
13 21 21 13 21
52 QF 14 S1 74 QF 12 QF 32 42 62 72 82 24 34 44 64 84 QF
14 S3 22 S3 22 S2 14 S2 22 S4
KO
X: 18 42 36 35
10 30 13 15 19 17 45 33 38 22 44 12 37 48
X: 11 52 29 6 57 55
13 23 33 43 53
14 S9 24 S9 34 S9 44 S9 54 S9
13 23 33 43 53
14 S8 24 S8 34 S8 44 S8 54 S8
21
22 QF
X: 21 50 51 53 54 39 16 49 14 58 56
Figure 2 Handcart
4
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
XT: 8 32 26 24 25 4 20 31 11 3 5 9 7 34 23 28 41 43 16 2 27
21 CK1
22
1 1 1 1
+ - + - + - + -
2 CK
2 1 1
U1 U2 1 U3 U4
KO Y1 YT
2 M 2 2 2
53 2 2
1
54 QF
R0
2
JP2 YC
JP1 1
1 1
51 13 73 11 21 31 41 61 71 81 23 33 43 63 83 Y7 Y8
13 21 21 13 21
52 QF 14 S1 74 QF 12 22 32 42 62 72 82 24 34 44 64 84 2 2
QF QF
14 S3 22 S3 22 S2 14 S2 22 S4
KO
30 21 13 15 19 17 45 33 38 22 44 12 37 1
XT: 18 42 36 35 14 10
S1, S2, S3, S4- energy storage position switch M- energy storage motor YC- closing coil YT- reclosing
coil Y1- locking electromagnet QF- and circuit breaker auxiliar y switch X- two plug S8- handcart test
position switch S9- hand position switch K0- skip relay
Note: The state of this diagram is that the circuit breaker is in the sluice, the non storage and the middle.
This diagram shows only one of the schemes, and the actual product will be different because of
the different requirements. Please refer to the random file.
A
128 510.5 P P 43
30
W
(275)
VCT7
25
638
555
370
280
74
79
38 430 D
B
200 600 C
5
Installing and Operating Instruction
93 536 838
275 275 43
30
W
(310)
VCT7
A
25
605
370
295
86
76
38 361 776
834
200 585.5
852
Fig.5 Outline and assembling sizes of trolly type circuit breaker (Distance between poles 275mm)
6
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
8.2 The outline and sizes of fixed type VCB refer to Fig.4, Fig.5.
P P 108.5
M16 E
VCT7
(275)
579
25
512
348.5
237
M12
45
45
4xM12 A C 65 20
B 275
630 25、31.5、40
1250 25、31.5、40 210 520 588 20 395
1600 25、31.5、40
12
630 25、31.5、40
1250 25、31.5、40 275 720 770 40 415
1600 25、31.5、40
7
Installing and Operating Instruction
275 275 A
130 Ø120 4xM10
80
A
60
(310)
VCT7
632
25
444
348.5
252
M12
45
45
4xM12 720 40 65 20
770 275
415
Fig.7 The outline and assembling sizes of fixed type VCB ( Distance between poles 275mm)
9.2 Checking-up
The following works shall be done after consignee receives the product:
a) Check by packing list whether the goods are in shortage;
b) Check the goods whether are in complete form, or being destroyed (e.g. become damp or other unfavourable influences);
c) Inform the supplier instantly and make records if goods are found destroyed heavily.
9.3 Assembling
Perfect and perfessional assembling is a basic condition for VCB operation without faults. The following points
shall be noted in assembling VCB:
a) Ensure VCB not being pulled, pressed or became deformed, and its four assembling bolts connected closely without
loosing if VCB is fixed inside switchgear cubicle;
b) Permanent pulling force and pressure shall be avoided for bus as connecting them together, and ensure the screw
bolts being fixed closely;
d) Ensure trolly pushing and taking out flexibly without blocking when withdrawal VCB is fitted inside switchgear cubicle.
The double-offset-ring contact and stationary contact inside cubicle are matched well. The interlocking of trolly and
cubicle body are fitted fine.
8
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
9
Installing and Operating Instruction
3 Fail to open Opening coils has no power. Connect with power source.
Note: Please contact with after-sale presonnel of our company if other faults appear or above faults can not be cleared.
15. Ordering
Please mention the following items:
a) Model, name and quantity of circuit breaker;
b) Rated voltage, rated current and rated short circuit breaking current of circuit breaker;
c) Rated switching voltage;
d) Name and quantity of accessories and spare parts;
e) Please mention in ordering if customer has other special requirements.
10
VCT7-12 Series Indoor Ac High Voltage Vacuum Circuit Breaker
11