Professional Documents
Culture Documents
Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ©ABB Industrie AG
ACS 2000 4 kV
Medium Voltage Switchgear Guide
Table of content:
1 General ..................................................................................................................... 2
1.1 Scope ........................................................................................................... 2
1.2 Standards ..................................................................................................... 2
1.3 System Description ...................................................................................... 2
1.4 Acronyms/Term Definitions .......................................................................... 2
2 Overview ................................................................................................................... 2
2.1 Function ....................................................................................................... 2
2.2 Optional Cable Protection............................................................................. 3
3 Switchgear Selection Criteria.................................................................................. 3
3.1 Standards ..................................................................................................... 3
3.2 Open Timing................................................................................................. 3
3.3 Close Timing ................................................................................................ 4
3.4 Control Power .............................................................................................. 4
3.5 Test / Service Operation ............................................................................... 4
3.6 Control Interface ........................................................................................... 4
4 Wiring Diagrams ...................................................................................................... 5
4.1 Exclusive Closing Control ............................................................................. 5
4.2 Wiring Configuration for MV Contactor ......................................................... 5
4.3 Wiring Configuration for MCB with Closing Coil and Undervoltage Trip
Coil ............................................................................................................... 7
4.4 Wiring Configuration for MCB with Closing and Opening Coil, and
Undervoltage Trip Coil .................................................................................. 8
5 Switchgear Operation ............................................................................................ 10
6 Control Interface Details ........................................................................................ 10
6.1 Control Interface Overview ......................................................................... 10
6.2 Control Interface Wiring Diagram ............................................................... 12
7 Interface Parameter Details ................................................................................... 13
7.1 Control Signaling Configuration .................................................................. 13
7.2 Feedback Signaling Configuration .............................................................. 13
7.3 Fault / Alarm Messages Configuration ........................................................ 14
No. of p.
Prep. Alex Ward 06/16/2011 MV Switchgear Guide
Appr. Tim Wagner 06/16/2011 ACS 2000 4 kV 15
Resp.
dept. MV Drives
Document number Lang. Rev. ind. Page
1.1 Scope
This document is to be used as a guide for selection of proper Medium Voltage (MV) switchgear to be
utilized with the ACS 2000 4 kV variable speed drive. Application of the MV switchgear and overall
system overview is also provided in this document.
This document does not apply to ACS 2000 4kV variable speed drives ordered with the Integral Input
Contactor and Disconnect option. The requirements, functions, and wiring shown within this document
are fulfilled with this option, refer to Appendix P - Integral Input Contactor Disconnect for details. It is
recommended that the customer provides a Medium Voltage maintenance disconnect in accordance
with local and national electrical codes when this option is ordered.
1.2 Standards
The following standards are referenced in this document:
• All MV Switchgear IEC or NEMA standards for specific application must be followed
2 Overview
2.1 Function
A MV switchgear device must be used at the main power supply of the ACS 2000 converter. The
switchgear is the main connection and disconnection point from the main power supply to the converter.
The switchgear must be able to communicate with and respond to commands from the converter. MV
switchgear acts as a protection device for the fuse-less versions of the ACS 2000, preventing hazard to
personnel and damage to equipment.
Figure 1 shows a single-line diagram of a typical drive system. A typical drive system includes a main
power feed, switchgear, an optional transformer, the ACS 2000 converter, and electrical motor.
Switchgear
Optional
transformer/cable
protection relay
CT
MCB control
interface
Optional
converter power
transformer
Higher level
ACS2000
control system
On / Off control
Motor M
3.1 Standards
Switchgear selection must be in accordance with IEC or NEMA and local standards regarding supply
voltage, load current, and short-circuit current. The ACS 2000 drive requirements are provided in this
section.
Switchgear that does not meet these requirements may cause physical injury and damage to
equipment.
Table 2: Supported switchgear control circuit ratings (All ratings in Amperes (A))
Refer to Section 6 of this document for more details on the control interface between the converter and
switchgear.
4 Wiring Diagrams
NOTICE
Commissioning will not proceed without submittal, verification, and sign-off of site specific MV switchgear
control wiring. Please consult Commissioning checklist, Chapter 7 of the user manual for details.
WARNING
The ACS 2000 must have exclusive control of closing the MV switchgear. Uncontrolled closing
of the switchgear may cause physical injury and damage the drive. ACS 2000 supplied with the optional
integral input contactor disconnect has this switching integral to the drive. See Appendix P for details.
It is also required that the attached switchgear opens upon loss of switchgear power. Typical devices
providing this behavior are contactors and circuit breakers with undervoltage trip devices. This section
provides details on the control wiring between the converter and different types of MV switchgear.
101T
101B
102B
103T
103B
/ MCB order trip
K1901 104T
106T
106B
MCB order close
K1903 107T
104B
105T
/ MCB order open Contactor
K1902 105B coil
IOEC 2 terminals
X12:9
MCB status closed Aux contact
IOEC/DI10 X12:10
X12:7
MCB status open
IOEC2/DI09 X12:8
X13:1
MCB status ok
IOEC2/DI11 X13:2
4.3 Wiring Configuration for MCB with Closing Coil and Undervoltage Trip Coil
A MCB with a closing coil and undervoltage trip coil is an acceptable switchgear configuration. In this
configuration, pulsed signals are used to apply power to the close coil or remove power from the
undervoltage trip coil. Two auxiliary contacts which follow the main contact provide feedback signals to
the drive. Figure 3 shows complete wiring details for this configuration.
X10 terminal block
Drive wiring Customer wiring
100T
Switchgear power
100B
101T
101B
102B
103T
103B
/ MCB order trip
K1901 104T
106T
106B
MCB order close Closing
K1903 107T coil
104B
105T Undervoltage
/ MCB order open
trip coil
K1902 105B
IOEC 2 terminals
X12:9
MCB status closed
IOEC2/DI10 X12:10
X13:1
MCB status ok
IOEC2/DI11 X13:2
Figure 3: Typical MCB with closing and undervoltage trip coil control wiring diagram
Table 4 lists the corresponding control signal parameter configurations for a MCB with closing and trip
coils and converter system. Refer to Appendix M: Signal and Parameter Table for more detailed signal
parameter information.
4.4 Wiring Configuration for MCB with Closing and Opening Coil, and Undervoltage Trip Coil
A MCB with a closing and opening coils, and an undervoltage trip coil is an acceptable switchgear
configuration. In this configuration, pulsed signals are used to apply power to the close and open coils or
remove power from the undervoltage trip coil. Two auxiliary contacts which follow the main contact
provide feedback signals to the drive. Figure 4 shows complete wiring details for this configuration, which
provides the highest reliability of opening the switchgear.
101T
101B
102B
103T
103B
/ MCB order Trip
K1901 104T
Undervoltage trip Open and Close coils
coil
are high activate pulsed
106T
signals.
106B
MCB order Close Undervoltage Trip coil is
K1903 107T Closing coil
low activate maintained
104B signal. Close is wired in
105T Opening coil series with trip.
/ MCB order Open
K1902 105B
IOEC 2 terminals
X12:9
MCB status Closed
IOEC2/DI10 X12:10
X13:1
MCB status Ok
IOEC2/DI11 X13:2
Figure 4: Typical MCB with closing, opening and undervoltage trip coil control wiring diagram
Table 5 lists the corresponding control signal parameter configurations for a MCB with closing, opening,
and trip coils and converter system. Refer to Appendix M: Signal and Parameter Table for more detailed
signal parameter information.
Name Setting
group.index
MCB Control PULSE SIGN
signal
21.14
MCB Control Default is 3
Pulse time seconds
21.15
MCB Feedback TWO SIGNALS
signal
21.16
MCB Closing Default is 3
time limit seconds
5 Switchgear Operation
Under normal operation the drive opens and closes the switchgear. The ACS 2000 must have exclusive
control of closing the attached switchgear. Uncontrolled closing of the switchgear may cause
physical injury and damage the drive.
Additional trip devices such as external emergency off switches can be wired into emergency off portion
of the control interface as shown in Section 6.2. Opening of this circuit will remove power to the close
and trip circuits and will notify the drive of why the switchgear opened. The drive will trip when this circuit
opens.
The drive can be configured to use a variety of control locations for pre-charging and discharging of the
internal power electronics. Closing and opening of the attached switchgear is coordinated with the
internal drive activities and optional isolating equipment. Upon a 'Supply On' request, if no trips are
present and the drive grounding switch is open, the drive will pre-charge and close the switchgear. Upon
a 'Supply Off' request, fault class 1 trip, or an emergency off signal, the drive will open the switchgear
and discharge. The 'On' and 'Off' commands for the drive can be from the following locations.
• The 'Supply On' and 'Supply Off' buttons on the front panel of the drive
• Remote control locations wired into IOEC digital inputs DI07 and DI13
• Optional fieldbus interface (refer to Appendix B: Fieldbus Adapter Manuals for more details)
V003
not connected *
X10 : 104T
MCB order close X10 : 106T IOEC 2 Active to close switchgear
DO06
V003
X10 : 106B
X10 : 107T
/ MCB order open X10 : 104B IOEC 2 Active when not opening switchgear
DO05
V003
X10 : 105T
X10 : 105B
Feedback signals
MCB status closed X12 : 9 IOEC 2 Feedback from switchgear
V004
DI12
DI14
V004
DI13
100T
100B
101T
Customer
emergency off
101B loop
102T
102B
103T
103B
/ MCB order trip
K1901 104T
106T
106B
MCB order close
K1903 107T
104B
105T
/MCB order open
K1902 105B
IOEC 2 terminals
X12:9
MCB status Closed
IOEC2/DI10 X12:10
X12:7
MCB status Open
IOEC/DI09 X12:8
X13:1
MCB status Ok
IOEC/DI11 X13:2
C N/A There were no changes from B to C. Not sure why REV C was 01/09/20 JK
released. REV C was created only to satisfy SAP.
D ALL Update to match current master schematics with interposing 01/10/20 JK
relays K1901, K1902, and K1903. TB04 is now TB10.