Economical, Requirement Oriented & Type Tested: The 8PU Low Voltage Switchboard
1 2 3
Reference Indian and International Standards
4 5 6
IS 8623 : (Part I)
Specification for Low Voltage Switchgear & Controlgear Assemblies: Requirement of Type Tested & Partially Type Tested Assemblies. Low Voltage Switchgear & Controlgear Assemblies.
IS 13947 : Specification for Low Voltage (Part I) Switchgear & Controlgear Part I: General Rules. IEC 60947 : Specification for Low Voltage Switchgear & Controlgear.
IS 2147 :
Degree of Protection provided by Enclosures for Low Voltage Switchgear & Controlgear. Specification for Wrought Aluminium & Aluminium Alloy Bars, Rods, Tubes & Sections for Electrical Purposes. Specification for Copper Strip for Electrical Purposes.
IS 5082 :
IS 1897 :
IS 11353 : Guide for Uniform System of Marking & Identification of Conductors & Apparatus Terminals. IS 5578 : Guide for Marking of Insulated Conductors.
World Class Products with unmatched features catering to the entire low voltage spectrum
Power Control Centre is considered to be the heart of an electrical system in any industry. Particular demands are therefore made in terms of long term reliability and safety. This is to say, supply, coupling and feeder functions must be reliably available over long period of time. Maintenance and testing must not involve long down-times. Siemens 8PU meets these requirements with 8PUL4.5 Power Control Centres.
User friendly
Siemens drawout and non drawout circuit breakers are used for the rated current range from 630 to 6300A. This means: Free choice of the supply direction without any sacrifices in terms of technical specifications. High short-time current carrying capacity for time-graded short-circuit protection (upto 500ms) assures reliable operation of the switchboard without being affected by a short-circuit. Indication and operation in the door closed condition.
415V , 50Hz
630A 6300A 50kArms, 1sec and 105kA peak (Type tested design) Standard 40C Optional 45C, 50C Standard IP 42 Optional IP 54 upto 1600A Standard W D H 560/850/1000x1120x2300 mm
A unique design
Unique double panel design for the outgoing feeders in place of conventional double tier panel.
Independent auxiliary compartment gives optimum space for mounting auxiliary devices even for extensive control and interlocking schemes.
Fewer joints between busbars and air circuit breakers makes the panel cooler.
Independent access to power terminals ensures high degree of safety during operation as well as reduces down time during maintenance. Also more cabling space ensures easy cable termination for both the feeders.
Provides safety
Telescopic rail facilitates access for maintenance with ACB in the Panel.
All indicators like ACB position indicator, mechanical counter & ready to close condition are visible with the door closed.
All control accessories accessible from the front, hence testing is possible with the CB door closed.
The main busbars & neutral busbars are enclosed in separate busbar chambers thus eliminating phase to neutral faults.
Whether in power plants, industrial installations or office complexes, an adequate amount of energy must be available at the necessary location and at all times. However, requirements frequently change. For example, motor power ratings change or new loads have to be connected. Siemens 8PU drawout design offers the unmatched degree of power supply flexibility. Whats more, it was conceived on the basis of ergonomic criteria. Easy handling and short conversion times assure high availability of the system.
8PUS1.5 drawout design offers versatility and reliability with adaptation to changing requirements
Drawout modules of the same sizes are interchangeable, irrespective of equipment mounted. Neither any shutdown nor any cutting or drilling required for changing or adding feeders disposition at site. Direct alignment with Power control Centre (8PUL4.5) to form PMCCs.
Vertical busbars with a multi layer plating on Aluminium called Alstan which ensures reliable electrical contact, resistance to abrasion and better electrical properties.
Cable alley of internal width of 270mm facilitates ease in cable termination & maintenance.
Trolley width of more than 500 mm ensures better equipment dispersion as well as safe & easy equipment replacement and maintenance. Unique swivel lever arrangement which ensures faster positive movement and engagement of module inside the compartment.
Main busbars and control busbars totally segregated from each other. Upto 11 number control bus per panel can be offered which ensure that solid links are used instead of wires thus leading to reduction in inter-panel cabling.
10
Provides safety
Power terminals for lower rating being at the rear, makes them unapproachable without taking out the trolley as well as ensures maximum area for cable routing in cable alley.
Gravity operated shutters ensures positive isolation of module compartment with vertical busbars after the trolley is drawn out.
The Switch fuse unit upto 125A comes with built in lyra contacts with solid connections between the switch, lyra contact and vertical busbars. 11
8PUF4.5 Non Drawout Motor Control Centre Economical, Reliable and Flexible
In certain applications, either there is no need to replace components under operating conditions or short idle times are acceptable. In such cases, Siemens 8PUF4.5 non drawout design offers excellent economy, reliability and variability.
12
13
8PUF4.5 Non Drawout Motor Control Centre Economical, Reliable and Flexible
Provides safety
Vertical busbars are placed one behind the other with the access to the last vertical busbar available from front in case of single front panels & from both sides in case of double front panels.
Module width of 500 mm ensures better equipment dispersion as well as safe & easy equipment replacement.
Main busbars and control busbars are totally segregated from each other. Upto 11 number control bus per panel can be offered which ensure that solid links are used instead of wires thus leading to reduction in inter-panel cabling. Wider Cable alley makes cable termination easy.
14
Non compartmentalised distribution boards are new entrants in the Siemens Low Voltage Switchboards product range. They are designed for the various industrial applications as well as for the high rise buildings. These distribution boards can be used for distribution of electrical power for lighting and other resistive loads.
Technical Data
Rated Insulation Voltage Rated Operational Voltage Rated Current 660V, 50Hz 415V, 50Hz Incoming Switch/MCCB- 250A-400A Outgoing MCBs : upto 63A 10kA IP 52 W D H 500 x 300 x 500mm Wall Mounting
500 x 300 x 1000mm Wall Mounting 500 x 300 x 1500mm Wall Mounting 500 x 300 x 1550mm Floor Mounting 600 x 500 x 2000mm Floor Mounting
15
In any electrical system of an industry the busduct is an important link to feed the incoming supply from transformer to the main Power Control Centre. Siemens Low Voltage Busduct is type tested, light weight and very compact. The bolted design ensures high degree reliability and flexibility during installation and maintenance.
Technical Data
Rated Insulation Voltage Rated Operational Voltage Rated Current Short Circuit strength Degree of Protection 660V, 40-60Hz 415V, 50Hz upto 4000A 50kA 1 sec. IP 54
16
Siemens 8PU is a type tested switchboard whose physical characteristics were designed in the test laboratory both for normal operating conditions as well as for fault situations. These type tests, conducted in an independent test laboratory/Inhouse, assures maximum reliability and safety. A few of the major type tests carried out are: Verification of temperature rise limits. Verification of impulse voltage. Verification of the short circuit withstand. Verification of degree of protection. Every Siemens 8PU switchboard assembly undergoes routine testing before delivery which are : Inspection of the assembly including inspection of wiring and electrical operation test. Dielectric Test. Checking of protective measures and of the electrical continuity of the protective circuits. Verification of mechanical operation.
Siemens 8PU adheres to the most stringent quality norms with a strict emphasis on the quality of materials and equipments that comprise the end product. Some of the salient features are: Conformances of our quality management system to ISO 9001. Conformances of our manufacturing facility to ISO 14001. Computer assisted project planning at all stages of product manufacturing. Use of exclusive, high grade insulating material and reliable Siemens make Switchgear/Controlgear.
17
Your partners
WEST Offices: Ahmedabad - 380009 3rd Floor, Prerna Arbour Girish Cold Drinks Cross Roads Off. C. G. Road : +91 79 40207600 Fax: +91 79 40207699 Mumbai - 400018 130, Pandurang Budhkar Marg, Worli : +91 22 24987000-02 Fax: +91 22 24987312 Nagpur - 440010 5th Floor, Landmark Building Ramdas Peth : +91 712 6633000 Fax: +91 712 6633111 Pune - 411016 Tower B / 701 - 705, ICC Trade Tower 403A, Senapati Bapat Road : +91 20 2570 6000 Fax: +91 20 2570 6060 SOUTH Offices: Bangalore - 560001 1st Floor, Jyothimahal #49, St. Marks Road : +91 80 22042000 Fax: +91 80 22224131 Chennai - 600034 4, Mahatma Gandhi Road : +91 44 28334000 Fax: +91 44 28334088 Coimbatore - 641018 7th Floor, East Wing, Global Towers 1057, Avinashi Road : +91 422 4336300 Fax: +91 422 4336310 Hyderabad - 500004 5-9-19, Lakshmi Narsinh Estate 4th Floor, Secretariat Road Opp. Secretariat, Saifabad : +91 40 23482500 Fax: +91 40 23243145 NORTH Offices: Chandigarh - 160017 SCO 189 - 191, 3rd Floor Sector 17C : +91 172 4690300 Fax: +91 172 4690399 Lucknow - 226001 28/45, Ashok Marg Opposite Indira Bhawan : +91 522 4031022, 4031000 Fax : +91 522 4031019 New Delhi - 110002 4A, Ring Road, I.P. Estate : +91 11 42995000-09 Fax: +91 11 42995030 EAST Offices: Kolkata - 700042 43 Shanti Palli, R B Connector Eastern Metropolitan Bypass : +91 33 24449000, 24428641-47 Fax: +91 33 24449010 / 13
Siemens Ltd. Industry Sector Switchboards and Busways Thane Belapur Road Thane - 400 601 Fax: +91 22 27623725 www.siemens.com/industry
Siemens Ltd. A&D-03-151-013
This replaces A&D-03-151-001 Product upgradation is a continuous process. Hence, data in this catalog is subject to change without prior notice. For the latest information, please get in touch with our Sales Offices.