D184S007U02
Rev. 01 / 04.2002
Fig. 1
I Function With this electromagnetic flowmeter system the flow rate of liquids, slurries, pulps and sludges can be accurately measured when the conductivity is above 0.05 S/cm. I Main applications For fluids with very low conductivities ( 0,05 S/cm); for fluids which form insulating coatings on the liners; for fluids which would corrode the electrodes. I Main instrument advantages Long term, stable accuracy < 1 % of rate as a result of digital signal processing combined with pulsed DC field technology and absolute zero stability. Automatic system monotoring with error diagnostics in clear text and notification over contact output. I Main instrument features Process flange DIN/ANSI/BS/JIS Meters size DN 25 to DN 300. Standardize installation length to VDI/VDE 2641, DVGW short, ISO 13359.
Measuring deviation < 1 % of rate. Fluid temperature -25 C to +80 C Ambient temperature -25 C to +60 C PED certificate to 97/23/EG, Fluidgroup 1 Liner material ETFE I Converter Communication HART-Protocol, PROFIBUS DP, ASCII-Protocol. Pulse output active/passive 2 Flow ranges/Preset counter A single converter module for all flowmeter sizes easy exchange of the electronics by EEPROM technology, no reentering of parameter required.
COPA-CM / MAG-CM
D184S007U02
Design
Fixed Flanges
Fixed Flanges
< 1 % of rate Alum. Series 4000 DC43F DN 25-250 300 25-300 25-100 PN 10-40 10-25 150/300 lb 10 ETFE (Tefzel) 0.05 S/cm SST 1.4571 IP 67 -25 C to +80 C -25 C to +60 C
< 1 % of rate Alum. Series 4000 DC41F DN PN 25-300 10-40 300 10-25 25-300 150/300 lb 25-100 10 ETFE (Tefzel) 0.05 S/cm SST 1.4571 IP 67, IP 68 (Option) -25 C to +80 C -25 C to +60 C
Flowmeter Primary
Model Number Process Connection Flange to DIN 2501 Flange to ASME Flange to JIS K 10 - B2210 Liner Material Conducticity Process Connection Material Protection Class to EN 60529 Fluid Temperature Ambient Temperature
Converter
Model Number Power Supply Current Output Standard Pulse Output 1-Channel Std. Ext. Zero Return Ext. Totalizer Reset Forward/Reverse Flow Metering Data Link Communication Self Monitoring Local Indication / Totalization 2 Flow Ranges Preset counter Autom. Density Correction Housing Design 50XM2000 50XM2000 24 V, 115 V, 230 V AC, 24 V DC 0/2-10 mA, 0-5 mA, 0/4-20 mA, 0/4-10/12-20 mA Active 24 V DC, Opto coupler yes yes yes RS 485, PROFIBUS DP ASCII-Protocol, PROFIBUS DP, HART-Protocol yes yes yes, automatic or external switching contact yes, START/STOP over contact input, STOP over contact output yes, manual entry (Totalizer and flow indication in weight units) Compact Field Housing
Page 2 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
Functional Description
The Faraday Laws of Induction provide the basis for the electromagnetic flowmeter measurements. A voltage is generated in a conductor as moves through a magnetic field. This measurement principle is applied to a conductive fluid which flows in a pipe traversed by a magnetic field, which is generated perpendicular to the flow direction (see Schematic). The voltage which is induced in the fluid is measured at two electrodes located diametrically opposite to each other. The signal measurement is made capacitively, i.e. the electrodes do not come in contact with the fluid. Each electrode forms a coupling capacitor with the interior wall of the metering spool, on which the signal potential exists, whose dielectric is the liner material. The flow rate proportional measurement signal is fed to the input of the integrated preamplifiers over this coupling capacitance. The signal voltage UE is proportional to the magnetic induction B, the electrode spacing D and the average flow velocity v. Since the magnetic induction B and the electrode spacing D are constant values it follows that a proportionality exists between the signal voltage UE and the average flow velocity v. The equation for calculating the volumetric flow rate indicates that the signal voltage UE is linearly proportional to the volumetric flow rate. This induced signal voltage is converted into scaled, analog and digital signals in the converter.
Accuracy % of rate
3 2 1 0 1 2 3 4 5 6 7 8 9 10 100 % v 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 15 Q Range m s
Fig. 2
Magnet Coil
y
z
Meter Tube in Electrode Plane
v B D
Measuring Electrode
E
x
UE
Signal Voltage
UE B D v qv
= Signal Voltage = Magnetic Induction = Electrode Spacing = Average Flow Velocity = Volumetric Flow Rate
UE
B.D.v
2
D -v q v = --------4
UE
qv
Fig. 3
04.02
Page 3 of 20
COPA-CM / MAG-CM
D184S007U02
1. 2.
Determine the diameter ratio d/D. Determine the flow velocity as a function of the size and the instantaneous flow rate:
100
Electrode Axis
v=8m/s 7m/s 6m/s 5m/s
10
4m/s
3m/s
2m/s
Fig. 4
Electrode axis
Installations in Larger Size Pipelines The flowmeter primary can readily be installed in larger pipeline sizes by utilizing reducers (e.g. flanged reducers DIN 28545). The pressure drop which results from the reduction can be determined from the Nomograph Fig. 5. The pressure drop is determined in the following manner:
1m/s
0.5
0.6
0.7
0.8
0.9
Page 4 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
l/min m3/h
l/s
3 4 3 2 2 10 3 8 6 5 4 3 2
D D
8 6 5 4 3 2
10 4 8 6 5 4 3
30
10 8 6 5 4 3 2
D D N 80 10
D D N
N 0 12 5
103 8
6 5 4 3 2
6 5 4 3 2
15
Fig. 6
10 2 8
20
25
10 8 6 5 4 3 2
10 2 8 6 5 4 3 2
6 5 4 3 2
D N 25
40
10 8
D 50
65
1 8 6 5 4 3 2
50
65
80
20 C 80 C
100
Materials
Part Liner Flanges Metering Tube Housing DN 25 to 300 Connection box Standard ETFE SST 1.4571 SST 1.4301 Two piece housing cast alum, painted Paint coat 60 m thick RAL 9002 Alum alloy, painted, Paint coat 60 m thick, low section RAL 7012 dark gray, upper section (cover) RAL 9002 light gray. Polyamide M20 x 1.5
Cable connector
04.02
Page 5 of 20
COPA-CM / MAG-CM
D184S007U02
Signal Cable (only MAG-CM) The maximum cable length between the flowmeter primary and the converter is 200 m. A 10 m long signal cable is shipped with each metering system. If a longer cable is require, see Ordering Information MAG-CM.
Design
DN 25 to DN 300 Two clam shell housings: Cast alum., painted Connection box: Cast alum., painted1) Flanges: Stn Stl 1.4571
1) Paint coat 60 m thick, lower section RAL 7012 dark gray, upper section (cover) RAL 9002 light gray
40
0 -25 -25 0 50 80
Fluid Temp. C
Weight
See Dimensions
45 40 35 30 25 20 15 10 5 0 -30 -10 10 30 50 70 90 PN 16 PN 10 PN 25
PS (40 bar) PS (25 bar) PS (16 bar) PS (10 bar)
PN 40
0 -25 -25 0 80
Fluid Temp. C
55 50
45 40
300lb
Fig. 9
35 30 25
20 15 10
PS (300lb) PS (150lb)
Protection Class
Standard IP 67 IP 68 (only MAG-CM) upon request Ambient Temperature -25 C to +60 C
150lb
5 0
-30 -10 10 30 50 70 90
Connections
Process Connections Flanged per DIN, ANSI, JIS K10 Electrical Connections Screw terminals Cable connector M20 x 1.5
JIS-Flanges, 10K-B2210
Size DN 25 - DN 100 Material SST 1.4571 PN [bar] 10 TS [C] -25 C bis +90 C PS = 10 bar
Page 6 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
Z
142 70 Cable Connectors Cable Connectors
80
Number of holes N
d2
G
View
V 70,01% V 10230m3
d4
A *L
Tolerance L* DN 3 200 +0 3 +0 5
V 70,01% V 10230m3
k H
All dims in mm
DN 250 300
E1
PN 25-40 10-40 10-16 25-40 10-40 10-16 25-40 10-16 25-40 10-16 25-40 10 16 25 40 6 10 16 25 40 10 16 25
*L 200 200 200 200 200 250 250 250 250 300 300 350 350 350 350 450 450 450 450 450 500 500 550
b 25 21 21 25 27 24 28 25 29 25 31 28 28 34 38 26 30 30 36 42 31 33 39
k 85 125 145 145 160 180 190 210 220 240 250 295 295 310 320 335 350 355 370 385 400 410 430
d2 18 18 18 18 18 18 22 18 26 22 26 22 22 26 30 18 22 26 30 33 22 26 30
d4 68 102 122 122 138 158 162 188 188 212 218 268 268 278 285 312 320 320 335 345 370 378 395
D 115 165 185 185 200 210 235 250 270 285 300 340 340 360 375 375 395 405 425 450 445 460 485
N 4 4 4 8 8 8 8 8 8 8 8 8 12 12 12 12 12 12 12 12 12 12 16
A 122 116 100 100 100 130 130 124 124 170 170 195 195 195 195 250 250 250 250 250 250 250 250
E 125 125 138 138 144 164 164 152 152 173 173 205 205 205 205 233 233 233 233 233 276 276 276
E1 129 129 153 153 159 179 179 169 169 190 190 222 222 222 222 250 250 250 250 250 293 293 293
F 90 90 104 104 110 130 130 127 127 148 148 179 179 179 179 207 207 207 207 207 250 250 250
G 288 228 242 242 248 268 268 261 261 282 282 314 314 314 314 336 336 336 336 336 379 379 379
G1 157 157 171 171 177 197 197 195 195 216 216 248 248 248 248 276 276 276 276 276 319 319 319
H 115 165 185 185 200 220 235 250 270 285 300 340 340 360 375 375 395 405 425 450 445 460 485
250
300
*L + 3 mm (DN 25 - 100) L + 5 mm (DN 125 - 300) for a single grounding plate on one side in stn. stl. 1.4571. Others upon request. L + 6 mm (DN 25 - 100) L + 10 mm (DN 125 - 300) for oritection plates mounted on flange in stn. stl. 1.4571. Others upon request. Fig. 10 Flowmeter primary DN 25 to DN 300
04.02
Page 7 of 20
G1
COPA-CM / MAG-CM
D184S007U02
MAG-CM
80
Number of holes N
Cable Connectors
E1 G1
All dims in mm
ISO Projection Method E
View
G
d2
A *L
d4 D
Tolerance L* 1/8 8 10 12 +0 3 +0 5
k H
V 70,01% V 10230m3
V 70,01% V 10230m3
DN
1
PN
150lb 300lb JIS K10 150 lb 300 lb JIS K10 150 lb 300 lb JIS K10 150 lb 300 lb JIS K10 150 lb 300 lb JIS K10 150 lb 300 lb 150 lb 300 lb 150 lb 300 lb 150 lb 300 lb 150 lb 300 lb
*L
270 270 200 280 280 200 330 330 200 340 340 200 400 400 250 450 450 450 450 500 500 550 550 620 620
b
21.0 24.5 18.0 21.0 20.4 20.0 24.2 27.0 20.0 23.8 28.6 20.0 27.3 35.3 22.0 27.8 38.9 29.4 40.5 33.6 46.3 35.2 52.6 36.7 55.8
k
79.2 88.9 90.0 120.6 127.0 120.0 139.7 149.2 140.0 152.4 168.3 150.0 190.0 200.0 175.0 216.0 235.0 241.0 270.0 298.0 330.0 362.0 387.0 431.8 450.8
d2
15.7 19.0 19.0 19.1 19.1 19.0 19.1 22.3 19.0 19.0 22.2 19.0 19.0 22.2 19.0 22.2 22.2 22.2 22.2 22.2 25.4 25.4 28.6 25.4 31.7
d4
N
4 4 4 4 8 4 4 8 4 8 8 8 8 8 8 8 8 8 12 8 12 12 16 12 16
A
122 122 122 116 116 116 100 100 100 112 112 112 130 130 130 124 124 170 170 195 195 250 250 250 250
E
98 98 98 124 124 124 138 138 138 144 144 144 164 164 164 152 152 173 173 205 205 233 233 276 276
E1
129 129 129 129 129 129 153 153 153 159 159 159 179 179 179 169 169 190 190 222 222 250 250
F
73 73 73 90 90 90 104 104 104 110 110 110 130 130 130 127 127 148 148 179 179 207 207 250 250
G
228 228 228 228 228 228 242 242 242 248 258 258 268 268 268 261 261 216 216 248 248 276 276 379 379
G1
157 157 157 157 157 157 171 171 171 177 177 177 197 197 197 195 195 216 216 248 248 276 276
H
108 124 124 153 166 155 188 191 175 191 210 185 229 254 210 254 279 279 318 343 381 406 444 482.6 520.7
50.8 108.0 50.8 123.9 70.0 125.0 92.1 152.4 92.1 165.1 100.0 155.0 104.8 177.8 104.8 190.5 120.0 175.0 127.0 190.5 127.0 209.5 130.0 195.0 157.0 229.0 157.0 254.0 195.0 210.0 186.0 254.0 186.0 279.0 216.0 279.0 216.0 318.0 270.0 343.0 270.0 381.0 324.0 406.0 324.0 444.0 381.0 482.6 381.0 520.7
2 1/2
5 6 8 10 12
*L + 3 mm (DN 25 - 100) L + 5 mm (DN 125 - 300) for a single grounding plate on one side in stl stl 1.4571. Others upon request. L + 6 mm (DN 25 - 100) L + 10 mm (DN 125 - 300) for protection plates mounted on flange in stn stl 1.4571 Others upon request.
Fig. 11
Flowmeter primary DN 1 to DN 12
Page 8 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
MAG-CM
E 25 50 65 80 1H 1Q 1F 2H 2F 3M C D E F K P Q 3 A B C S A D A D
A 2
A 2
1) Grounding plate mounted at one end, Protection flange mounted on both ends, other material upon request. 2) Certificates for meter tube and process connections.
04.02
Page 9 of 20
COPA-CM / MAG-CM
D184S007U02
COPA-CM
Ordering No. DC43F Supply Power 230 V 50/60 Hz 115/120 V 50/60 Hz 24 V 50/60 Hz 24 V DC Display Magnetic Stick operation and lighted display Contact In-/Output Opto coupler/Opto coupler Opto coupler/Relay
B C F H D 0 1
In-/Output Options Current output + Pulse output active 1 Current output + Pulse output passive 3 Current output + Pulse output passive + HART-Protocol 4 Current output + Pulse output active + HART-Protocol 5 Current output + Pulse output passive3) + RS485 (ASCII) 6 7 Current output + Pulse output passiev3) + PROFIBUS DP Current output + Pulse output passive3) + PROFIBUS DP with M12 cable connector 9 Parameter Entry Mode Standard with 3 buttons and magnetic stick (Data can be entered without opening the housing cover) 3) Contact output not available
Page 10 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
Accuracy: 1% of rate
Electrical Connections Screw terminals, cable connector M20 x 1.5/NPT. Weight approx. 4.2 kg Field mount housing Signal Cable (only MAG-CM) The max. cable length between the flowmeter primary and the converter is 200 m. A 10 m long signal cable is shipped with each metering system. If a longer cable is require, see Ordering Information MAG-CM., Page 25, Footnote. Parameter Settings Data can be entered in one of 9 different languages using the converter keypad. Magnetic stick operation is available for direct external operation with a closed field housing. Data safeguarded utilizing a NV-RAM. All parameters and totalizer values are stored for over 10 years without power. Display 2x16-character LCD-Dot-Matrix-Display with LED-Background lighting. The separate internal flow totalizers for each flow direction totalize in 16 different engineering units. The flow rate is indicated in percent or 45 different engineering units.
Fig. 12
Flow Range Continuously selectable between 0.5 and 15 m/s Forward / Reverse Metering The flow direction is indicated in the display by a direction arrow and externally by a relay or optocoupler output. Minimum Conductivity 0.05 S/cm Reproducibility
0.1% of rate
F F
70.01 % 10230 m3
Response Time 0 - 99% corresponds to. 5 A step change 0 - 99 % 0.5 s Supply Power 115/230 V AC -15 % / + 10 % 24 V AC -15 % / +10 % 50 / 60 Hz 6 % 24 V DC -25 % / +30 %, ripple 1.5 Vp. Magnetic Field Excitation 12 1/2, 25 Hz Power consumption 23 VA (flowmeter primary including converter) for AC supply power 10 W for DC supply power Ambient Temperature -25 C to +60 C See Temperature Diagram on Page 6 Protection Class per EN 60529 IP 67 for field mount housing Design - Field mount housing, diecast alum, painted - Paint coat 60 m thick, lower section RAL 7012 dark gray; - Upper section (cover) RAL 9002 light gray
The units listed below can be selected using the arrow keys. The units selected apply to the Range, Qmax forward and reverse when a direct reading display is desired. In multiplex operation the flow rate can be displayed in %, engineering units or as a bargraph, totalizer value forward or reverse, TAG-No., or current are additionally available for display in the 1st or 2nd line.
Unit Milliliter Liter Hectoliter Megaliter Cubic meter Imperial-gallon per U.S.-mill.-gall per/d U.S.-gall.per Beer Barrel Oil Barrel Gram U.S. Ton Kilogram Ton Pound Kilo-gallon per Kg/s t/s lb/s kgal/s g/s bbl/s gpm bbl/min bls/min g/min uton/min Kg/min t/min lb/min kgal/min gph bbl/h bls/h g/h uton/h Kg/h t/h lb/h kgal/h uton/day bls/day m3/s igps Second ml/s l/s hl/s Minute ml/min l/min hl/min Ml/min m3/min igpm Hour ml/h l/h hl/h Ml/h m3/h igph mgd ML/day Day
04.02
Page 11 of 20
COPA-CM / MAG-CM
D184S007U02
Current output 0 - 20 mA
The instantaneous flow rate in % of the selected flow range or engineering units is displayed in the 1st line. The integrated flow totals are displayed in the 2nd line (including units). During multiplex operation an additional display values can be selected for the 1st and 2nd display lines. The display includes LED-Background lighting. System Monitor and Alarm Output Automatic system monitoring with error diagnostics on the display and an signal over a contact output. All errors are stored in the error register.
Current Output, configurable, terminals +/Range 0 - 5 mA 0/2 - 10 mA 0/4 - 20 mA 0-10,10-20 mA 4-12, 12-20 mA Load Resistance
RB
Optocoupler P1, P2 EB, CB 16 V UCEH < 30 V 0 V UCEH < 2 V 0 mA ICEH< 0.2 mA 2 mA ICEL < 15 mA
Operating current
The individual subassemblies can be checked with the Function Test parameter. All outputs can be simulated for start-up and checking.
Output Characteristics
Current I max Current I max
Functiontest Iout
Reverse Flow 0 % Forward Flow 100 % Flowrate 100 % Current output (0-5 mA, 0-10 mA, 0-20 mA)
I min Reverse Flow 0 % Forward Flow 100 % Flowrate 100 % Current output (0-10 mA, 4-20 mA)
Note: The instrument corresponds to the NAMUR-Recommendations EMC Guidelines for Manufacturers and Users of Electrical Equipment and Systems Part 1, 5/93 and EMC-Guideline 89/336/EWG (EN 50081-1, EN 50082-2). Warning: The EMC-Protection is reduced when the housing cover is removed.
Current 20 mA 10 mA
Current 20 mA 12 mA 4 mA
Reverse Flow 0 % Forward Flow 100 % Flowrate 100 % Current output with elevated zero (0-10-20 mA)
Reverse Flow 0 % Forward Flow 100 % Flowrate 100 % Current output with elevated zero (4-12-20 mA)
Page 12 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
Note:
The contact input should be closed for longer than 1 s (preset totalizer START/STOP >350 ms but not longer than 1.5 s).
Alarm output Automatic system monitor including checking for a CPU-Error with error diagnosis shown on the display and an error signal transmitted over the passive contact output. Errors 0-9 are stored in the submenu Alarm for correction purposes. The contact opens during an alarm condition. Programmable Output Contact output, passive; the following functions can be software selected:
Function Opens or Closes
16 V UCEH <30 V DC 0 V UCEL <2 V 0 mA ICEH <0.2 mA 2 mA ICEL < 250 mA fmax = 5 kHz When using a mechanical counter it is recommended that the pulse width 30 ms and fmax 3 Hz
Operating current When using a mechaniand frequency cal counter it is recommended that the pulse width 30 ms and fmax 3 Hz
General alarm Empty pipe MAX-Alarm MIN-Alarm MAX-MIN-Alarm F/R-Signal 2 flow ranges*) Preset totalizer*)
X X X X X
Programmable Input Contact input, active or passive; the following functions can be software selected:
Function active or Closes passive
Contact closed for the forward flow direction Contact opens when the preset quantity is reached (contact closes for the next start command and remains closed during the cycle.) Optocoupler G2, P7 E9, C9 P1, P2 EB, CB or Relay G2, P7 39, 40 P1, P2 96, 97
External Zero Return When the metering tube empties all output signals can be turned off. External Totalizer Reset The internal totalizer values and the overflow counter can be reset from a contact. Flow Range 1/2 *) External flow range selection Flow range 2 selected when the contact is closed. START/STOP *) Preset Totalizer External contact to start a preselected quantity. To initiate a safety stop, initiate again. Terminals Operating voltage Operating current
Output Mode Terminals COPA-CM Function Terminals MAG-CM Function Pulse Output Unscaled f = 0-10 kHz Terminals COPA-CM Function Terminals MAG-CM Function Operating voltage Operating current
16 V U 30 V
X1, U2 1) X1, G2 Jump G2 - g2 16 V UCEH <30 V 0 V UCEL <2 V Ri = 2.0 k 0 mA UCEH <0.2 mA 2 mA UCEL <15 mA
1) Optional functions for COPA-CM (internal 24 V DC-Supply) *) These functions must first be selected in the submenu Operating mode. X = Function is software selectable
04.02
Page 13 of 20
COPA-CM / MAG-CM
D184S007U02
RS 485 VPP = 5 V. Input impedance: 12 k, Max. cable length: 1200 m. Baudrate: 110-9600 Baud, 14400/28800 Baud. Max. 32 Instruments in parallel on a single bus. A shielded data cable with twisted pairs is recommended. Terminals: V1, V2, V3, V4; Function T-, T+, R-, R+.
Nr. 1
RS485
Nr. 32
4 - 20 mA
RS485
Rb = 250 Ohm
Serial data link RS485
HART
Fig. 14
Bell 202 Modem Box
Fig. 13
Transmission Mode FSK-Modulation on the current output 4-20 mA per Bell 202 Standard. Baudrate 1200 Baud Representation Logic 1: 1200 Hz, Logic 0: 2200 Hz Cable AWG 24 twisted Max. Cable Length 1500 m Max. Signal Amplitude 1.2 mAPP Current Output Load Min.: >250 , max.: <1000
A twisted shielded data cable is recommended. Max. cable length 1200 m (cable type A) Typical impedance 135-165 Ohm Max. 32 Instruments on a single bus Baudrate: 9.6-1500 kbit/s Distributed capacitance <30 pF/m, loop resistance 110 /km Max. tap line length 1 m. Entering and exiting cables on one terminal.
PLC
......
B A
B A
Converter 1
Converter 2
+VD B +5 V
A GND
Converter 32
Fig. 15
Bus Connections
GSE Profibus Description File The name of the Instrument Data Base file is ABB_6666.GSE and is included with the shipment. For a detailed description of the Data Link see the document ABB Part no. D184B093U05.
Page 14 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
G2 B 60 C9 40 P2 P7 59 E9 39 P1 G2
d)
A 11 T+ 9 RG2 10 V2 V3
VP 11R R+
e)
9 T61 g2 + V1
d)
c)
c)
b)
b)
1L1 L+ L
1L2 LN
a)
a)
X1
V4
AC Voltage 50/60 Hz
1)
2)
3)
4)
5)
Contact Output Terminals P7, G2 Contact format and functions can be selected in the Ordering Information. a)1) Software selections of the functions to be transmitted over the contact output: General alarm, limit alarm, forward direction, flow range, active, end contact, preset totalizer Function P1/P2, Optocoupler: 16 V UCEH < 30 V, 0 V UCEL < 2 V, 0 mA ICEH < 0.2 mA, 2 mA ICEL < 15 mA or Relay: 16 V U < 30 V, 0 mA I < 250 mA, P 3 Watt b) Alarm output relay contact; opens, specifications see a), Function 39, 40 c) Alarm output optocoupler; opens, specifications see a), Function C9, E9 d) Unscaled pulse output 0-10 kHz optocoupler output, specifications see a), Function 59, 60 2)2) Contact Input Terminals G2, X1 The following functions are software selectable: External zero return, external totalizer reset, flow range 2, Start/Stop preset totalizer, passive 16 V U < 30 V, Ri = 2 k 3) Current Output selectable, load 1000 Ohm for 0/4-20 mA, 0-10-20 mA, 4-12, 12-20 mA, load 2000 Ohm for 0/2-10 mA, load 4000 Ohm at 0-5 mA. Option HART-Protocol for 4-20 mA per Bell 202 Standard, Specifications see Page 31. 4) Scaled pulse output 1-channel, active or passive, pulse width selectable from 0.100 ms to 2000 ms or serial data link Terminals V1-V4 a) Active, 24 V DC load 150 Ohm, fmax = 5 kHz Function 10, g2 b) Passive, Function 61, G2 c)3) Serial data link RS 485, Function T-, T+, R-, R+ d) Option: scaled pulse output 2-channel, data link not available Active 24 V DC load 150 or passive relay contact (closes), 3 W; 250 mA; 28 V DC, fmax = 20 Hz or passive: V1, V2 Forward; Function 9, 11 Terminals: V3, V4 Reverse; Function 9, 11R e) Data link Profibus DP, Terminals V1, V2, V4, G2, Function (RxD/TxD-P(B), RxD/TxD-N(A), +5 V (VP), DGND (G2) or bus termination). 5) Supply Power, see Instrument Tag
1) 2) 3)
1)
Factory default setting is Forward direction signal. Factory default setting is External Zero Return. When using a RS 485 a shielded data cable with individually twisted pairs is recommended.
Fig. 16
04.02
Page 15 of 20
COPA-CM / MAG-CM
D184S007U02
external
external RB * 24 V+ 0V
MAG-CM
V9 (61) V8 (G2)
24 V+
Pulse Output Optocoupler, Single Channel, Separate Forward and Reverse Signal on Contact Output
internal
V1 (61) V3 (G2)
external
MAG-CM
V9 (61)
Reverse 0V 24 V+
Forward
G2 P7
Current Output
internal external
Current Output with Contact Output for Control of a Remote Recorder or Indicator
internal external
+
MAG-CM
+
Reverse
G2 P7
U CE * RB -----------I CE
0V
Forward 24 V+
P1 (96) P2 (97)
or MAG-CM
external +U RB *
external 0V 24 V+
0V 24 V+
Contact output for general alarm, Max-Min-Alarm, empty pipe, forward/reverse signal, flow range 1/2 or end contact preset totalizer Function software selectable
external
internal
P7 G2
MAG-CM
P2 (97) P1 (96)
Contact input for external zero return, external totalizer reset, flow range 2 or Start/Stop reset totalizer Function software selectable
internal
g2 G2
external
Passive internal
X1 G2
external +24 V
U2
0V
X1
Fig. 17
Page 16 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
Converter 50XM2000
c) G2 L+ L1L1 1L2 N L VP B A b) 9 11 9 11R EB CB a) T- T+ R- R+ 96 97 b) G2 61 E9 C9 a) 10 g2 39 40 + V8 V9 V5 V6 16 U+ 2 1 U- 3
M1 M3 g2 G2 U2 X1 V1 V2 V3 V4 P1 P2
2)
3)
4)
5)
6)
7)
8)
9)
1)
Ground
SE M1 M3
16 3 U+ 2
1 U- 3 SE
Flowmeter Primary
1) 2) 3)
4) a) b)
c) 5)
6) 7) * a) b) 8) a) b) 9)
Supply Power, see Instrument Tag Excitation Current Cable for flowmeter primary (e.g. shielded 2x1.5 mm2), Terminals M1, M3) Contact Input, functions software selectable as ext. zero return, ext. totalizer reset, ext.flow range selection or start contact for preset totalizer passive, over contact (closed), with ext. current supply, 16 V UCEH 30 V DC, Ri = 2k Terminals X1, G2. Active, over contact (closed), Terminals X2, U2, jumper Terminals g2/G2 Data Link RS 4851), Terminals V1-V4, Function (T-, T+, R-, R+) Option: Scaled Pulse output, 2-channel, data link not available active, 24 V DC, load 150 or passive relay contact (closed), 3 W; 250 mA; 28 V DC, fmax = 20 Hz or passive optocoupler, 5 V < UCE < 28 V DC, 5 mA < ICE < 30 mA; fmax 5 kHz Terminals: V1, V2 forward; Functions 9, 11 Terminals: V3, V4 reverse; Functions 9, 11R Data link Profibus DP, Terminals V1, V2, V4, G2, Function (RxD/TxD-P(B), RxD/TxD-N(A), +5 V (VP), DGND (G2) for bus termination. Contact Output, functions software selectable as general alarm, limit alarm, forward direction signal, 2 flow ranges or preset totalizer over relay contact 3 W; 250 mA; 30 V DC, Terminals P1/P2, Function (96/97) over optocoupler 16 V UCEH 30 V DC, 2 mA ICEL < 15 mA, Terminals P1/P2, Function (EB/CB) Current Output selectable, 0/4-20 mA load 1000 , 0/2-10 mA load 2000 , 0-5 mA load 4000 , Terminals +/) Scaled Pulse Output forward and reverse; active, 24 V DC, load 150 , fmax = 5 kHz, Terminals V8, V9, Function (g2/10) passive, 5 mA I 250 mA, 5 V U 25 V DC, fmax = 5 kHz, Terminals V8/V9, Function (G2/61) Alarm Output, relay contact 3 W; 250 mA; 30 V DC, opens at alarm, Terminals V6/V6 Function (39/40) Alarm output, optocoupler 16 V UCEH 30 V DC, 2 mA ICEL < 15 mA, ICE 7.5 mA, Terminals V5/V6, Function (E9, C9) Shielded Signal Cable, Part No. D173D018U02, 10 m included with shipment.
*) Scaled pulse output, active or passive, pulse width selectable from 0.100 to 2000 ms. 1) When using a RS 485 a shield data cable with individually twisted pairs is recommended.
Fig. 18
04.02
Page 17 of 20
COPA-CM / MAG-CM
D184S007U02
Dimensions: Converter
198 10
139.7
167
7
265
14.5
66 132
38 83.5
249
Mounting Dimensions
All dims in mm
Fig. 19
Page 18 of 20
04.02
COPA-CM / MAG-CM
D184S007U02
50XM2
5 * * A Z B 1 2 1 2 3 A B A C D E B C F H 1 2 3 9
Signal Cable: A 10 m long signal cable is included with each meter. For longer lengths please request Part.-No. D173D018U02.
04.02
Page 19 of 20
COPA-CM / MAG-CM
D184S007U02
Software
Meter identification software for PC upon request, SMART VISION Communication tool for HART Protocol the Test Version without charge for 90 days upon request.
www.abb.com
ABB Ltd. Oldends Lane, Stonehouse Gloucestershire, GL 10 3TA UK Tel: +44 (0)1453 826661 Fax: +44 (0)1453 827856
ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
ABB Automation Products GmbH Dransfelder Str. 2 37079 Goettingen Germany Tel: +49 551 905-0 Fax: +49 551 905-777
Subject to technical changes. Printed in the Fed. R. of Germany D184S007U02 Rev. 01 Issue 04.02