You are on page 1of 52

Users Manual

DOS-Controller
2C

















COE DT / 1.1/ 20.06.2006


TABLE OF CONTENTS

INTRODUCTION..................................................................................................................................................4
GENERAL DESCRIPTION............................................................................................................................................4
FEATURES.................................................................................................................................................................5
SYSTEM FLOW CHARTS AND CONTROL PANEL KEYS ...............................................................................................6
HARDWARE SETUP............................................................................................................................................7
NOTES ON SAFETY....................................................................................................................................................7
MOUNTING AND LOCATION.......................................................................................................................................7
WIRING NOTES..........................................................................................................................................................7
INPUTS......................................................................................................................................................................7
OUTPUTS...................................................................................................................................................................8
CONFIGURING THE SYSTEM..........................................................................................................................9
GENERAL..................................................................................................................................................................9
ENTERING CONFIGURATION MODE...........................................................................................................................9
SELECT LANGUAGE.................................................................................................................................................10
INPUT CONFIGURATION ..........................................................................................................................................10
Select sensor type...............................................................................................................................................10
Configuration of conductivity sensor .................................................................................................................11
Configuration of direct display of input signal ..................................................................................................12
EQUIPMENT CONFIGURATION.................................................................................................................................12
Setting Equipment Mode ....................................................................................................................................13
Select flow meter ................................................................................................................................................14
Select pump type.................................................................................................................................................14
Flow Rate Input / Teach In.................................................................................................................................14
Control of product flow......................................................................................................................................15
OPERATION MODE..................................................................................................................................................16
Select Operation Mode.......................................................................................................................................16
Analogue regulator ............................................................................................................................................16
Volume fix ..........................................................................................................................................................17
Dependant ..........................................................................................................................................................17
Set points for Init. Charge and Start-Up............................................................................................................18
Return to Configuration Menu...........................................................................................................................18
READING / RESETTING TOTAL CONSUMPTION........................................................................................................18
NETWORK SETTING.................................................................................................................................................19
Changing the Password .....................................................................................................................................19
Input / Output Test .............................................................................................................................................20
Resume Operation..............................................................................................................................................21
OPERATING INSTRUCTIONS........................................................................................................................22
OPERATION OF DOS-CONTROLLER-2C ..................................................................................................................22
AUTOMATIC DOSING...............................................................................................................................................23
Analogue regulator ............................................................................................................................................23
Volume fix ..........................................................................................................................................................24
Dependant ..........................................................................................................................................................24
DOSING AN INITIAL CHARGE/ START-UP................................................................................................................24
MANUAL DOSING....................................................................................................................................................25
NETWORK OPERATION............................................................................................................................................27
Operation as "Master".......................................................................................................................................27
Operation as "Slave"..........................................................................................................................................27
TROUBLESHOOTING......................................................................................................................................28
ALARMS AND WARNINGS .......................................................................................................................................28
Alarm messages .................................................................................................................................................28
Warning messages..............................................................................................................................................29
SYSTEM NOT FUNCTIONAL.....................................................................................................................................30


TABLE OF CONTENTS


Page 3

JohnsonDiversey DOS-Controller 2C
EXAMPLE............................................................................................................................................................31
SYSTEM-CONFIGURATIONEN IN STAND-ALONE-MODE ............................................................................................31
SYSTEM-CONFIGURATIONEN IN MASTER-SLAVE-MODE.........................................................................................32
APPENDIX A: SPECIFICATIONS................................................................................................................................35
APPENDIX B: ELECTRICAL CONNECTIONS ..............................................................................................................36
APPENDIX C: MENU SCHEMES................................................................................................................................40
Operation Menu.................................................................................................................................................40
Configuration Menu...........................................................................................................................................41
Input Configuration, Submenu to Configuration ...............................................................................................42
Equipment Configuration (stand alone mode) ...................................................................................................43
Equipment Configuration (Master)....................................................................................................................44
Equipment Configuration (Slave) ......................................................................................................................45
APPENDIX D: PARAMETER LIST..............................................................................................................................46
APPENDIX E: MOUNTING DIAGRAM .......................................................................................................................50
APPENDIX F: SPECIFIC CONDUCTIVITY DIAGRAMS..................................................................................................51
GLOSSARY..........................................................................................................................................................52




Introduction

Page 4

Introduction
General Description
The DOS-Controller-2C is part of an innovative modular system solution for the dosing of cleaning products for
bottle-washing machines. It offers a high level of flexibility:
The concentration of product can be controlled via dosing of fixed volume per time or by
measuring and controlling the conductivity of the cleaning fluid.
An additive can be added either as fixed volume per time or proportional to the volume of the
main product.
One DOS-Controller-2C is controlling two different parts of a bottle washer.
Two DOS-Controller-2Cs can be coupled together using the same equipments controlling three
different parts of a bottle washer.
The system consists of a DOS-Controller-2C unit and one dosing pump per product. Additional inputs are
necessary for operation. To improve operation additional flow sensors can be added to control consumption. If
necessary, level sensors can be added to check the level of product.
A second DOS-Controller-2C may be coupled together using the same equipment and controlling different
stages of a machine. In this case one DOS-Controller-2C is "Master" and controls all dosing equipment and one
part of the machine. The other DOS-Controller-2C acts as a slave, and controls valves from the transport line, to
the second and third part of the machine. DOS-Controller-2Cs communicate via CAN-Bus.
* * *
When a system with a single DOS-Controller-2C is running in Automatic Mode, the DOS-Controller-2C works
automatically stand-alone. A system, composed of two DOS-Controller-2C's running in Automatic Mode,
requires CAN-Bus -Interfaces. In this case the "Slave"-Controls requests a product type and wait for a response
by its "Master".
The possible activities of a DOS-Controller-2C are as follows:
No Release : no dosing activity possible
Automatic : Dosing automatically
Initial Charge : Dosing an initial charge
start-up : Dosing a start-up charge
Manual : Dosing a manually set charge of product
* * *
The DOS-Controller-2C system is comprised of a wall mountable control unit with a separate access area for the
port connections. The control panel has 4 keys and a LCD display with 2 x 16 digits. All activities of the dosage
system are regulated from the control panel, and from the attached external devices. The control system is
configured using the commands and input screens on the LCD display.

Four relay outputs control the four dosing equipments (dosing pumps or valves). For each dosing item, there is
one power digital output driving the pump or, in "Slave"-Mode the valves. Four additional opto-coupler
outputs control the stroke pulses if stroked dosing pumps are used. DOS-Controller-2C systems can be activated/
inhibited by external devices through one trigger release. "Initial Charge" and "Start-Up"-dosing can be started
by external devices through separate trigger inputs. Optionally, systems can be networked to a computer running
a configuration and monitoring software through a CAN-Bus interface.

JohnsonDiversey DOS-Controller 2C


Introduction

Page 5

Features
Controls dosing processes for product and additive in two baths
Monitors daily and total consumption for each cleaning product and bath.
Triggers alarm messages and halts current processing step when physical alarms occur.
Systems can be networked through an optional CAN-Bus interface.
Password protection.
Different operating modes for dosing pump
Different operating modes for concentration control

Example for a DOS-Controller-2C network with the maximum of 1 master and 1 Slave.



In this example the master controls bath 1 and the dosing pumps. Slave 1 controls bath 2 and bath 3 .
An activated valve opens the way to the bath. Every controller gets a trigger signal from his bath to start the
dosing process.
Every bath is be controlled by an analogue regulator. The level control indicators must be connected to the
Master control only.

JohnsonDiversey DOS-Controller 2C


Introduction

Page 6

System Flow Charts and Control Panel Keys
The four system flow charts - Operation Menu and Configuration Menu (includes two submenus) (see Appendix
C) - are the road maps that will guide you through the DOS-Controller-2C system. Whether you want to
configure the system to run automatically, activate a manual dosage, or view product consumption totals, the
flow charts will show you the route you must take to accomplish your task. You can photocopy the three flow
charts, for greater ease of use.

The DOS-Controller-2C system commands, which appear on the LCD display, rotate in a looping fashion.
Depending on which key you press on the control panel, different areas of the systems menu will be accessed.

The two control panel keys, Select and Enter, are indicated on the flow charts by S and E, respectively.
These keys generally represent the two different options which are available from any given display screen in the
ED-Control system. With the Enter key, you can also generally proceed through the system and view system
settings, without changing the data.



SELECT SELECT: moves to the next menu item (and/or does not start function).



ENTER ENTER: confirms last entry and continues.



The two arrow keys on the control panel are generally used to set numeric entries:


Down arrow: decreases number in digit field,
toggles between Y and N in Yes / No field,
(or pre-sets fields with zero entries).


Horizontal arrow: moves cursor to the next digit field,
(or pre-sets fields with preceding entries).

JohnsonDiversey DOS-Controller 2C


Hardware Setup

Page 7

Hardware Setup
Notes on Safety
To ensure that the controller functions perfectly and has a long, useful life, the user must observe the instructions
in this manual and must proceed according to the conditions of use. Commissioning and maintenance personnel
must have been trained and authorized to carry out such activities. Appropriate measures must be taken to
prevent unintended actuation and resulting detrimental influences on the process. The applicable prevention and
safety regulations for electrical devices must be observed during operation, maintenance and repair of the
controller.

All electrical connections must be made by a qualified electrician. Always disconnect from power supply before
opening cover. Danger of electrical shock inside.

Electrical components should not be exposed to water or moisture. If this occurs by accident, the unit must be
serviced by a qualified electrician.

Mounting and location
The DOS-Controller-2C unit should be mounted on a clean, vertical surface and kept away from heat (<50C),
moisture and vibrations. As shown in the mounting diagram (Appendix E), there are six mounting holes to
mount the DOS-Controller-2C unit to a wall - three on each side on the back wall of the plastic box. When you
have located the place for the control unit, mount the box securely in place.

The flow sensors must be installed in a straight length of pipe, with a minimum of ten diameters of straight pipe
before and five diameters of straight pipe after the sensor to ensure correct operation.

Wiring notes
For the electrical wiring of the components, pay attention to the maximum cable lengths between the ED-Control
unit and the other components (refer to the technical manuals of the components). Connect wiring as shown in
wiring diagram (Appendix B).

Connect power to the port labeled N, PE, L1. Make sure that all attached equipment is in conformance with the
electrical specifications (Appendix A).

Inputs
Release Trigger. The Release Trigger can be connected to a switch or to an external device, for remote
triggering of the system. The system will only run when the external contact is closed or when the Release
Trigger signal is set to low.

Initial Charge/ Start-Up. These inputs can be connected to a switch or to an external device, for remote start of
an initial charge (or start-up) dosing. The system will start when the external contact is closed or when this input
signal is set to low.

Flow Sensor: The flow sensors are optional and can be disabled during configuration. In this case no control
over consumption of product is possible, product flow will be calculated from the characteristics of the dosing
pump. The product consumption can be calculated too.

JohnsonDiversey DOS-Controller 2C


Hardware Setup

Page 8

Level alarm: Connect level switches for the empty level. All input clamps also feature 0 volt and 24 volt
access. A high' signal (open contact) refers to an empty tank; a low' signal (closed contact) refers to a tank
which is not empty. A broken wire or a faulty connection will also prompt an alarm. This contact is closed if
product is running empty, an immediate alarm will be produced.

Outputs

Connect the pumps to the respective output ports. If you are using a Stroke pump, connect the pump also to the
corresponding Stroke output port.

The system provides two relay outputs as alarm and running signal. The Alarm output can be used to trigger an
external alarm, by attaching it to a lamp or a horn. The Running output signifies normal operation, and can be
attached to an external device.

For the maximum output ratings, see the Specifications sheet (Appendix B)
.
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 9

Configuring the System
General
The DOS-Controller-2C system automatically controls the concentration of Product and feeds the necessary product
into the machinery. To accomplish this, the DOS-Controller-2C controls 2 sensors and 4 pumps.

Sensor: Sensor 1 : measures the product concentration in bath 1
Sensor 2 : measures the product concentration in bath 2
Pumps: Equip. 1 : pumps main product to bath 1
Equip. 2 : pumps additive to bath 1
Equip. 3 : pumps main product to bath 2
Equip. 4 : pumps additive to bath 2

Equipment 1/3 can be configured to perform a time constant dosing ("Volume Fix") or to control the concentration of
product. When the system is running in Automatic Mode, dosing will be performed automatically until the Trigger
Release input is set to low.

When inappropriate values are entered in the Configuration Menu, or a setting is not possible, the DOS-Controller-2C
system will inform the user.

While the system is being configured, the DOS-Controller-2C system will not perform any dosages - all of the system
outputs are blocked and set to low. When the Configuration Menu is exited, the system is immediately ready to
perform dosages.

The system is configured using the four control keys on the control unit and the commands on the LCD display. It is
necessary to use the systems flow charts - Operation Menu and Configuration Menu (including two submenus) - in
order to configure the system (see System Flow Charts and Control Panel Keys, page 7).

Entering Configuration Mode
When the control unit is turned on for the first time, the start-up screen will read:

Configuration
Enter

As shown on the Operation Menu flow chart (bottom left corner), press the Enter key to confirm, and begin
Configuration.

Enter Password
xxxx

The system requires that you enter a password in order to have access to configuration capabilities. Enter your four-
digit password, using the down arrow key and the horizontal arrow key. Press the Enter key again, and you will be in
the Configuration Menu - see the Configuration Menu flow chart.

The general set-up of the control system will now be configured., product consumption totals can be read and reset here,
the password may be changed, and the inputs and outputs can be tested.

Referring to the Configuration Menu flow chart (Appendix A), use the keys on the control panel to respond to the
information on the LCD display (see System Flow Charts and Control Panel Keys).


JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 10

Select language
The language of the user interface can be selected to suit the personal needs of the user/ operator.

Language Setting
Enter

If this menu item is selected, a choice of four languages is presented

Sel. Language
(E/D/F/Sp/P): E

The following languages are integrated and can be selected:
English (E)
German (D)
French (F)
Spanish (Sp)
Portugese (P)


After selection of the language, the actual type and version of the software is displayed.

DOS-Controller-2C
Version 1.0


Input Configuration
The first screen in the Configuration Mode is:

Sensor Config.
Enter

As shown in the Control Configuration flow chart, press the Enter key, to confirm and proceed to Input Configuration.

Input Configuration Flow Chart

All of the parameters which define the specific operation of both inputs (sensors) will now be configured.

Referring to the Input Configuration flow chart (Appendix C), use the keys on the control panel to respond to the
information on the LCD display (see System Flow Charts and Control Panel Keys).

Select sensor type

Select sensor
1: Conduct.

The sensor input can be connected to different types of sensors. Press the down arrow key, to toggle between the
following choices:
Conductivity : Conductivity sensor, different options for displayed unit and range as well as internal or
external temperature compensation can be configured
direct : The direct display of the input current can be in "mA" or in "%" of full scale.

JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 11


Sel. Current Min
1: (0/4mA): 4

In any case the minimum current of the sensor has to set. A selection of 0 A or 4 mA is possible depending whether a
"live zero" (4-20mA) is used or not (0-20mA)

Configuration of conductivity sensor
Every step in configuration can be left by pressing the SELECT-key. In this case DOS-Controller-2C switches back to
the screen "Select sensor / 1: ...".


Cond. Sel. Unit
1: mS

The conductivity sensor input signal (analogue input 1) can be displayed in various ways. The direct display in "mS" or
"S" is possible as well as an indirect display in terms of concentration of a product. to different types of sensors. Press
the down arrow key, to toggle between the following choices:
mS / S : Conductivity displayed in physical units, either mS or S. The maximum scale has to be
set also ("Cond. Scale max.", see below).
NaOH : The concentration of NaOH is displayed. The measured conductivity is transformed into a
concentration value via a stored calculation diagram. The maximum scale has to be set also.
KOH : The concentration of KOH is displayed. The measured conductivity is transformed into a
concentration value via a stored calculation diagram. The maximum scale has to be set also
H3PO4 : The concentration of H
3
PO
4
(Phosphorous acid) is displayed. The measured conductivity is
transformed into a concentration value via a stored calculation diagram. The maximum
scale has to be set also
H2SO4 : The concentration of H
2
SO
4
(Sulphuric acid) is displayed. The measured conductivity is
transformed into a concentration value via a stored calculation diagram. The maximum
scale has to be set also
HNO3 : The concentration of HNO
3
(Salpetric acid) is displayed. The measured conductivity is
transformed into a concentration value via a stored calculation diagram. The maximum
scale has to be set also
free : A free concentration is displayed. The measured conductivity is transformed into a
concentration value via a stored calculation diagram, this diagram is set by the user ("Free
Cond. Curve", see below).


Cond. Scale max.
1: 2000 mS

The maximum scale of the sensor (analogue input 1) is set in a range from 1 to 2000 S / mS. This is the conductivity
necessary to produce 20mA output current by the sensor.


Cond. Free Curve
1-1:0500mS=00,0%


Cond. Free Curve
1-1:0500mS=07,5%

If the conductivity has to be displayed in terms of a user specific characteristic, data of a concentration characteristic
can be set. For up to 8 points of a characteristic (called 1-1...1-8) the conductivity in S / mS and the corresponding
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 12

concentration have to be set. If a conductivity value has been set to the desired value the ENTER-key has to be pressed
to switch to concentration. If a concentration value has been set to the desired value the ENTER-key has to be pressed
to switch to the conductivity of the next point.
The relationship between concentration and conductivity has to be a monotonous rising function. Therefore the default
values for the first point are "0 S / mS" and "0%". Setting the following points the minimum values for both
concentration and conductivity will be the corresponding value of the previous point. The default values for these points
are the values of the previous point.
That is, if an additional data point for a characteristic has to be entered, some points will have to be shifted.

It is possible to see all the data points by pressing ENTER multiple times.

Configuration of direct display of input signal
This step in configuration can be left by pressing the SELECT-key. In this case DOS-Controller-2C switches back to
the screen "Select sensor / 1: ...".

Direct Display
1: (mA/%) mA

If the input current has to be displayed directly, the option "mA" has to be selected.
of sensors. Press the down arrow key, to toggle between the following choices:
mA : Input current will be displayed in mA with a resolution of 0,02 mA. The maximum scale
is 20mA.
% : Input current will be displayed as % of full scale with a resolution of 0,1 %. Full scale may
be 0-20mA or 4-20mA depending on "Current min."-setting.
A current of 8 mA will be displayed as 40,0% (4-20mA) or 25,0% (0-20mA)

Equipment Configuration
The second screen in the Configuration Mode is:

Equipment Config
Enter

Equipment Configuration Flow Chart

All of the parameters which define the specific operation of the equipment (dosing pumps) will now be configured.

Referring to the Equipment Configuration flow chart (Appendix A), use the keys on the control panel to respond to the
information on the LCD display (see System Flow Charts and Control Panel Keys).

The first screen in Equipment Configuration is:

Equipm. : 1 2 3 4
Mode: R D R F

This screen displays the current configuration of each of the four pump outputs. The different operation modes of the
dosing pumps have the following abbreviations:
R analogue Regulator (Equipment 1,3)
F volume Fix (Equipment 1-4)
D Dependant (Equipment 2,4 only)
0 Off (Equipment 1-4)

JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 13

Before the system has been configured for the first time, all pump configurations will be set to 0. Press the Select key
to proceed to the next screen.


Select Equipment
(1-4): 1

The cursor will be located in the digit field on the LCD display. Press the down arrow key, until 1 appears in the digit
field, to program the first piece of equipment (pump). Press the Enter key to proceed.
Setting Equipment Mode

Equipment Mode
1: (P/V/O) = I

Every piece of equipment may be activated or deactivated. The operation mode of each individual piece of equipment
(pump or valve) has to be set according to the system set-up. Details of the operating mode will be configured later.
Rotate between the three choices, using the Select key.

If you do not want to use a pump, you may disable it by selecting O. When a pump is disabled, a 0 will occupy that
pumps corresponding position in the Equ. Mode display.

Depending on operation mode, the equipment may be set as "Valve". See application scheme and the chapter on
"Network operation" for details on the necessary set-up.

When you have made your choice, press the Enter key to confirm this screen.

Note: If a network of a Master and a Slave is to be configured, care must be taken during configuration of the
master:
All the equipment that is used by the network has to be configured at the Master, even if not used by the
Master. Only the Master has information about pump type and flow meter data.
If any equipment is not used by the Master but used by the Slave, act as follows:
Set equipment to be on, define its data as necessary and to disable it at the Master set the "Operation
Mode = Volume Fix (F)" and "Fixed Volume = 0,0 kg" or "Interval Time = 0 sec. With these settings, the
equipment is defined completely but is not dosing at the Master Control himself.
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 14


Select flow meter


Prod. Flow meter
1: (Y/N) = Y

An additional flow meter may be activated or deactivated. The operation mode of each piece of individual equipment
will be configured later. Rotate between the two choices, using the Select key.

Select pump type

Select Pump Type
1: (S/P) : S

For all equipment (pump 1-4) the pump type can be selected between "Permanent" and "Stroke". When you have made
your choice, press the Enter key to confirm this screen.

If the pump type is selected to be "Stroke", two additional times have to be set:

Stroke Time
1: 9,9 sec

"Stroke time" defines the length of the stroke impulse necessary to drive the pump according to its specifications.

Pause Time
1: 9,9 sec

"Pause Time" defines the pause between two stroke pulses to produce the specified product flow rate (see parameter
"Stroke Pump Product").
Flow Rate Input / Teach In

Use Teach In
1: (Y/N): N

Without use of a flow meter the discharge capacity (Mass Flow) of the pumps (kg/hr) can be set either by entering the
flow rate of the pump (timed, l/hr or stroked, p/l) and the density of the product (kg/l), or by using a Teach-in method.
To choose between Yes / No, toggle with the down arrow key. If a flow meter is used, its calibration is done
simultaneously during 'Teach-in'.

Without flow meter one of the following parameters is set, depending on selected pump type: "Timed Pump Prod" in
case of a permanent pump and "Stroke Pump Prod." in case of a stroked dosing pump.

Timed Pump Prod.
1: 999,9 l/h


Stroke Pump Prod.
1: 9999 p/l
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 15


If a flow meter is used without Teach-in the parameter " Flow meter Product" has to be set always (equipment 1-3)
instead of the pump parameter.
Product density will only appear with equipment 1 (2) as equipment 3 (4) use the same product and flow meter as
equipment 1 (2).


Flow meter Prod.
1: 9999 p/l


Product Density
1: 1,999 kg/ l


To use the Teach-in method, weigh the product drum and switch the pump on (Fill Test Volume, 1: Start = Enter)
long enough so that a reasonable amount of product is taken out of the container - enough so that the weight can be
measured.


Fill Test Volume
1: Start=Enter

Switch the pump off again (Fill Test Volume, 1: Stop = Enter).

Fill Test Volume
1: Stop =Enter

Weigh the drum, and subtract the current weight from the previous weight. Enter the weight of the pumped product into
the system using the arrow keys, when the entry screen is again available.

Enter weight
1: 999,999 kg

The system will then calculate and display the Mass Flow capacity of the equipment.

Prod. Flow Rate=
1: 9999,9 kg/h


Control of product flow
If a flow meter is used then a minimum and maximum product flow rate can be set. During dosing product flow is
measured and compared with these limits. Whenever a flow outside these limits is measured, an alarm will be released,
as defective equipment is possible.

Min. Prod. Flow
1: 9999,9 kg/h


Max. Prod. Flow
1: 9999,9 kg/h

JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 16

Operation Mode
Select Operation Mode
The screen displays the configuration choices of the selected equipment. It appears different for equipment 1,3 and
equipment 2,4 as the choices is different.
The choices for equipment 1,3 are the following:

Operation Mode
1: (R/F) R

R. analogue Regulator
F volume Fix

The choices for equipment 2,4 are as follows:

Operation Mode
2: (F/D) F

F volume Fix
D Dependant

For explanation of the different modes see the following chapters.

Analogue regulator
The measured value from the input is compared to the set point. If the measured value is lower than "Set point" - "Dead
band" dosing of product will be started. If the measured value is higher than "Set point" dosing of product will be
stopped.
If the measured value is below the alarm level "Min. Alarm" a warning message is released and the automatic dosing
process continues. If the measured value is above the alarm level "Max. Alarm. " an alarm is released and the automatic
dosing process is stopped.
Dosing of product is done in portions defined by the parameters "Dose Time" and "Wait Time". If a dosing process is
running, it will be stopped after "Dose Time". DOS-Controller-2C will wait until the end of "Wait Time". If the dosing
condition is still valid, dosing will be continued then.
The consumption of product is controlled via flow meter if possible else the calculation of the consumption is done via
time and the set product flow rates of the equipments. The consumption counters are updated regularly.


Dose Time
1: 9.999 sec


Wait Time
1: 9.999 sec


Set point and Dead band are set in same units and scale as defined by the scale of input. For example if input 1 is
defined as conductivity with a range of 0....800 S then the possible range for Set point and Dead band is the same.

Set point
1: 2000 S


JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 17


Dead band
1: 2000 S

If the Set point cannot be reached within this time, an alarm is released and the automatic dosing process is stopped.
If the measured value reaches the Set point during Initial Charge or Start-Up, these modes are stopped and a warning
message is released.


Timeout Set point
1: 9.999 sec


As with Set point and Dead band the alarm levels are set in same units and scale as defined by the scale of input 1. For
example if input 1 is defined as conductivity with a range of 0....800 S then the possible range for Min./ Max. Alarm is
the same.

Min. Alarm
1: 2000 S


Max. Alarm
1: 2000 S

The alarm warning level (Min. Alarm) is not active during Initial Charge or Start-Up.

Volume fix
A Volume Fix mode is dosing an amount of product per time independent of any measured values. Two parameters are
necessary: volume and interval time. When an interval starts, a dosing process is started. If the set amount of product
has been dosed, the dosing is stopped until the end of the interval time. Then another interval starts.


Fixed Volume
1: 999,999 kg


Interval Time
1: 9.999 sec

The consumption of product is controlled via flow meter if possible else the calculation of the consumption is done via
time and the set product flow rates of the equipments.


Dependant
In dependant mode, the amount of additive in relationship to product. If, for example, a value of 0,200 is entered for the
relationship, the equipment will dose, on average, 20% of the mass of his product compared to the mass of product.
To prevent the equipment being started too often, a minimum volume is defined. If the need for additive exceeds this
limit, a dosing process is started dosing the complete necessary amount of product.

min. Volume
2: 999,999 kg
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 18



Vol. Ratio
2: 1,000

The consumption of product is controlled via flow meter if possible else the calculation of the consumption is done via
time and the set product flow rates of the equipments.


Set points for Init. Charge and Start-Up
For all equipment the amount of product necessary for an initial charge has to be set here. During Initial Charge and
Start-Up the measured value at the analogue input is controlled.

Setpt. Init. Ch.
1: 999,999 kg


Setpt. Start-Up
1: 999,999 kg

The dosing of the configured Initial Charge/Start-up volumes can be manually activated within the Operation Menu or
externally triggered through the hardware input for Start-Up (see Control System Configuration).

Return to Configuration Menu

Return to Config
Start = Enter

To exit Equipment Configuration, and return to the Configuration Menu, press the Enter key at this screen.


Reading / Resetting Total Consumption
Press ENTER to get into the part of the menu allowing resetting total consumption counters

Reset Consumpt.
Enter

After the system has displayed the total consumption amount for equipment 1-4, you may reset the total product
consumption amount for each pump to zero, after entry of the password.

Consumption/tot.
1: 99999,9 kg

......

Consumption/tot.
4: 99999,9 kg

JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 19

Although the total consumption is displayed separately for each equipment, resetting will be done simultaneously for all
three equipments (= products).

Reset Consumpt.
Enter


Enter Password
xxxx

If a false password is entered, the "Reset Consumption" screen will be shown again.

Network setting
If a CAN-Bus interface is equipped, this option appears in the menu.

Network setting
Enter

The type of operation in the network has to be selected first.

Use Network
(M/S/N): M

Three selections are available:
M Master This DOS-Controller-2C is a Master to another DOS-Controller-2Cs within the same
network.
S Slave This DOS-Controller-2C is Slave to another DOS-Controller-2C within the same network
N None The CAN-Bus interface will not be used in conjunction with other DOS-Controller-2Cs


Network ID
32

The address within the CAN-Bus has to be set.
If the DOS-Controller-2C is selected to be a "Master" then the address has to be a multiple of 2. This master will regard
all DOS-Controller-2Cs as slave if their address is higher by 1 compared to his address.
Note: If another address is set, it will be reduced to the next lowest multiple of 2. Any address below 3 will not be
accepted
Example: If the address is set to be 19 it will be changed automatically to 18 if ENTER is pressed.

If a DOS-Controller-2C is selected to be a "Slave" its address must not be a multiple of two. This slave will regard a
DOS-Controller-2C as Master if his address is the next lowest multiple of two compared with his own address. Care
must be taken not to assign two slaves to the same address.
Note: If a multiple of four is set, the address will be incremented by one.
Example: If the address is set to be 20 it will be changed automatically to 21 if ENTER is pressed.

Example: Master = 32, Slave = 33
Changing the Password

Change Password
Enter
JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 20


The four-digit password can be changed when a new code is entered twice in a row. When the two entries dont match,
the new password will not be accepted.


Repeat Password
xxxx

After entering a false code the system switches back to entry of the password.

Note: System is delivered with password 9999, which can be modified!


Input / Output Test

I/O - Test
Enter

The reliability of the digital input and output channels of the DOS-Controller-2C system can be tested here (refer to
Appendix A for flow chart).

Analogue Input
1: 06,44 mA


Analogue Input
2: 08,28 mA

The input current into both analogue inputs will be displayed first.

Flow sensor 1-8
x x x x x P P P

The status of the flow sensors will be displayed next with 1 indicating a high, 'P' indicating pulses at the input and
0 indicating a low signal level.

Dig. Input 1-8
x x 0 1 0 1 0 0

The status of all digital inputs will be displayed, with 1 indicating a high, and 0 indicating a low signal level.

Set Output 1-8
0 0 0 1 0 1 0 0


Set Output 9-16
x x x x x x 0 0

All digital outputs for the 4 pumps, 4 stroke signals to the pumps and the output for the alarm and the running message
can be individually set or reset by toggling between 1 and 0 using the down arrow key. After exiting the Input /
Output Test, all previous output signal levels will be restored.

JohnsonDiversey DOS-Controller 2C


Configuring the System

Page 21

Resume Operation

Resume Operation
Enter

To exit the Configuration Mode and resume operation in the Automatic Mode, press the Enter key. Immediately upon
exiting the Configuration Mode, the system will begin sequencing in Automatic Mode, using the configuration
parameters which were last entered.

JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 22

Operating instructions
Operation of DOS-Controller-2C

The DOS-Controller-2C starts to operate automatically after power up. Power supply is indicated by an activated
LCD-display. No user interaction is necessary after configuration of the DOS-Controller-2C.

Conduct. No Rel.
0234 mS 0225 mS

(Example: DOS-Controller-2C waiting for release trigger)

The display always shows the configured input type, the operation mode and the values at both analogue inputs.

If the display shows "Automatic" a dosing process is running. A release trigger signal is necessary for automatic
operation.

Cond. Autom.
0234 mS 0225 mS

(Example: DOS-Controller-2C dosing automatically)
The display may be switched at any time to display of the set point by pressing the ""-key. The display is
restored if the key is released.

Set point
0250 mS 0250 mS

The display may be switched at any time to display of the status of all equipments by pressing the ""-key. The
display is restored if the key is released.

Eq1 Eq2 Eq3 Eq4
R:1 D:0 R:1 F:1

The top line shows all 4 equipments. Below each equipment the operation mode is shown and the actual state of
the output: 1 = on, 0 = off. The operation mode is shown with the same abbreviations as used during
configuration, for example "R" denotes "regulator mode". The state of the output shows the state of the power
output, in case of stroked equipment a "1" will be shown as longs as the output will be active. An individual
stroke output will not be shown. For a TD-Control running as master within a network an output will be
displayed as "1" (active) if dosing for the master, outputs requested by slaves will not be shown as active here.
These will be displayed as active by the slave.


If the display shows "Initial Charge", "Start-Up" or "Manual", an additional dosing process is running. A release
trigger signal is necessary for automatic operation. To start an Initial Charge or a Start-Up dosing an additional
input signal (Initial Charge or Start-Up) is necessary. These modes may be triggered manually too (see below).
The configuration can be changed at any time (refer to "Programming the DOS-Controller-2C").

Condi. Init.Ch.
0234 mS 0225 mS

(Example: DOS-Controller-2C dosing an Initial Charge)


JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 23


Condi. Start-Up
0234 mS 0225 mS

(Example: DOS-Controller-2C dosing in Start-Up mode)

Manual dosing can only be started manually.

Manual Equip.1
0234 mS 0225 mS

(Example: DOS-Controller-2C dosing manually by equipment 1)
During all these three modes, the display may be switched at any time to display of the set point and the
remaining volume by pressing the ""-key. The display is restored if the key is released.


Set point Volume
022,5kg 065,9kg

(Example: DOS-Controller-2C dosing in Initial Charge/ Start-Up/ Manual Mode with a remaining volume of
22,5 kg and 65,9 kg to be dosed)
The display may be switched at any time to display of the status of all equipments by pressing the ""-key. The
display is restored if the key is released.

Eq1 Eq2 Eq3 Eq4
R:1 D:0 F:1 I:1

(For explanation see text above)

Automatic dosing
During automatic dosing the operation depends on the selected operation mode, see chapter "Equipment
Configuration", and on the configuration of the equipment.

Equipment 1 and 3 (main product) can be configured as "Analogue Regulator" or "Volume Fix", see below for
details of these modes.
Equipment 2 and 4 (additive) is used simultaneously to Equipment 1, these may be in "Volume Fix" or
"Dependant" mode.
Analogue regulator
The measured value from input 1 (2) is compared to the set point. Depending on the selected Regulator Control
Mode the following happens:
Reg.Crtl. Mode = pos.: If the measured value is higher than "Set point" + "Dead band" dosing of product 1
will be started. If the measured value is lower than "Set point" dosing of product 1
will be stopped.
If the measured value is below the alarm level "Min. Alarm" an alarm is released and
the automatic dosing process is stopped. If the measured value is above the alarm
level "Max. Alarm" a warning message is released and the automatic dosing process
continues.
Reg.Crtl. Mode = neg.: If the measured value is lower than "Set point" - "Dead band" dosing of product 1 will
be started. If the measured value is higher than "Set point" dosing of product 1 will be
stopped.
If the measured value is below the alarm level "Min. Alarm" a warning message is
released and the automatic dosing process continues. If the measured value is above
JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 24

the alarm level "Max. Alarm. " an alarm is released and the automatic dosing process
is stopped.
Dosing of product 1 is done in portions defined by the parameters "Dose Time" and "Wait Time". If a dosing
process is running, it will be stopped after "Dose Time". DOS-Controller-2C will wait until the end of "Wait
Time". If the dosing condition is still valid, dosing will be continued then.
The consumption of product is controlled via flow meter if possible else the calculation of the
consumption is done via time and the set product flow rates of the equipments. The consumption
counters are updated regularly.
If the set point cannot be reached within this time, an alarm is released and the automatic dosing process is
stopped.
Volume fix
A Volume Fix mode is dosing an amount of product per time independent of any measured values. Two
parameters are necessary: volume and interval time. When an interval starts, a dosing process is started. If the set
amount of product has been dosed, the dosing is stopped until the end of the interval time. Then another interval
starts.
The consumption of product is controlled via flow meter if possible else the calculation of the consumption is
done via time and the set product flow rates of the equipments.
Dependant
In dependant mode, the amount of product 2 is set in relationship to product 1. If, for example, a value of 0,200
is entered for the relationship, the equipment will dose, on average, 20% of the mass of his product compared to
the mass of product 1.
To prevent the equipment being started too often, a minimum volume is defined. If the need for product 2
exceeds this limit, a dosing process is started dosing the complete necessary amount of product.
The consumption of product is controlled via flow meter if possible else the calculation of the consumption is
done via time and the set product flow rates of the equipments.
Dosing an Initial Charge/ Start-Up
During Initial Charge/ Start-Up a pre-set volume is dosed, it is possible to dose with Equipment 1-4. The
equipments will be running with maximum speed.

To start an Initial Charge or a Start-Up dosing two input signals (Release Trigger plus Initial Charge or Start-Up)
are necessary.

If an Initial Charge or a Start-Up dosing is running, the one of following screens will appear in the menu.

Initial Charge
ENTER


Start-Up Mode
ENTER

Pressing the ENTER-key will lead to a screen allowing stopping the Initial Charge/ Start-Up Mode manually

Initial Charge
Stop = Select


Start-Up Mode
Stop = Select

JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 25

These states can be left without stopping Initial Charge / Start-Up by pressing the ENTER-key

These modes may be triggered manually too. If the release trigger is active, both following screens will appear in
the menu.

Initial Charge
ENTER


Start-Up Mode
ENTER

Pressing the ENTER-key will lead to a screen allowing starting the Initial Charge/ Start-Up Mode manually

Initial Charge
Start = Enter


Start-Up Mode
Start = Enter

The volumes to be dosed and the selected equipments have to be set in Configuration Mode.

In these modes the warning level is deactivated (either Min. Alarm" or "Max. Alarm" depending on Regulator
Control Mode) only the Alarm level may be active (see chapter "Equipment Configuration").

If the Operation Mode is "Analogue Regulator" these modes are stopped once the set point is reached, DOS-
Controller-2C will continue in automatic mode. In this case a warning message will be released.

If the Operation Mode is "Volume fix " no Alarm level is activated.

Initial Charge/ Start-Up Mode are finished once the defined volumes of all products have been dosed.
Manual dosing
During Manual Mode a pre-set volume is dosed, it is possible to choose between Equipment 1, 2, 3 and 4. The
equipment will be running with maximum speed. The volume is set while starting the Manual Mode
In this modes the warning level is deactivated (either Min. Alarm" or "Max. Alarm" depending on Regulator
Control Mode) only the Alarm level may be active (see chapter "Equipment Configuration").

The following screen will appear in the menu after viewing the consumption:

Manual Mode
ENTER

Pressing the ENTER-key will lead to a screen allowing doing the necessary settings for the Manual Mode:
The equipment and the necessary volume have to be selected respectively set:

Manual Mode
Equipm. (1..4):2


Manual Volume
2: 999,9kg

JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 26

The Manual Mode has to be started by pressing the ENTER-key.

Manual Mode
2: Start = Enter


While dosing manually, the remaining time can be displayed by pressing the ""-key during normal display. If
the Manual Mode is already running, a different screen will appear when selecting this mode.
It can be stopped then by pressing the SELECT-key


Manual Mode
2: Stop = Select

Pressing "ENTER" returns to normal operation continuing manual dosing.
Pressing "SELECT" returns to normal operation without manual dosing.
JohnsonDiversey DOS-Controller 2C


Operating instructions

Page 27

Network operation
A DOS-Controller-2C can be run using the CAN-Network in two different modes: In stand-alone mode, the
DOS-Controller-2C is exchanging data with a host-PC running the network. Configuration can be done via the
network also.

Two DOS-Controller-2Cs may be coupled together using the CAN-network to form a "Master-Slave"-network.
In this case some rules of operation are necessary:
Every slave will send a request of product to his master if product is needed. The Master will do the same
(internally).
The unit to be serviced first is the unit that sent the first request (FIFO-principle: first in - first out).
During Wait Time (Regulator Mode) another unit may be serviced.
An Initial Charge or a Start-Up Dosing may not be interrupted by another unit.

Operation as "Master"
If a DOS-Controller-2C is used as Master the following differences in operation will occur:
The Master will control the pumps via the configuration of equipment 1 and 2.
Sensor input 1 will not be used, as the master will only be able to control one bath via equipment 3 and 4. A
Master will display only the measured value of channel 2 on the right side of the display. Only sensor 2 can
be configured in sensor configuration.
Flow sensors will only be used with equipment 1 and 2; the same applies to the level inputs.
The equipment 3, 4 will always be "permanent, as valves will be controlled and not dosing pumps.
The valves 3-4 corresponding to equipment 3-4 has to be connected to the power outputs, the stroke outputs
will be inactive.

Operation as "Slave"
If a DOS-Controller-2C is used as Slave the following differences in operation will occur:

The equipment 1-4 will always be "permanent, as valves will be controlled and not dosing pumps.
The valves 1-4 corresponding to equipment 1-4 has to be connected to the power outputs, the stroke outputs
will be inactive.
Level alarm, data of equipment and flow sensor inputs will not be used, these are only necessary for the
Master. If the network address of a DOS-Controller-2C is set to a Slave-Address, these items will be skipped
during configuration.



JohnsonDiversey DOS-Controller 2C


Troubleshooting

Page 28

Troubleshooting
Alarms and Warnings
There are two types of alarm messages: Alarm and Warning.
Alarm: The dosing process will be stopped until the alarm is acknowledged by pressing the ENTER-key
Warning: DOS-Controller-2C continues with normal operation. The warning message will stay on the until it
is acknowledged by pressing the ENTER-key

An alarm/ warning will always be signaled in the top line of the display. If possible, the bottom line will
continue to show the measured values at both inputs.

The last alarm or warning that occurred will be displayed. If an alarm is activated, no warning message will
override this display.

Alarm messages

E3 broken wire 1
- - - - - ??? ???? ??


E3 broken wire 2
- - - - - ??? ???? ??

The input current at input 1 or 2 is lower than 2 mA. This is possible if the input has been defined as 4-20mA
input.

E5 Condi. min.
????? ??? ???? ??

The measured value is below the low Alarm threshold (Regulator Control Mode = positive

E5 Condi. max.
????? ??? ???? ??

The measured value is above the high Alarm threshold (Regulator Control Mode = negative)


Setting reached
????? ??? ???? ??

The set point could not be reached within the set time-out limit (Analogue regulator Mode, equipment 1,3 only).

Vol.nt reached X
????? ??? ???? ??

The pre-set volume could not be dosed within the set interval time. (Volume fix Mode).
The demand for volume is higher then ten times the pre-set minimum volume (Dependant Mode).
"X" denotes the equipment generating this error


JohnsonDiversey DOS-Controller 2C


Troubleshooting

Page 29


E7 Level Alarm X
????? ??? ???? ??

The level alarm input of product "X" has been activated (X=1, 2). An alarm is generated if the level alarm input
is activated and the related equipment/ product are needed.

Warning messages

W1 Low Flow Pr.X
????? ??? ???? ??

The flow of product "X" has been measured and is below the set minimum flow, the warning has been activated
(X=1, 2).

W2 High Flow Pr.X
????? ??? ???? ??

The flow of product "X" has been measured and is above the set maximum flow, the warning has been activated
(X=1, 2).

W5 Cond. min.
????? ??? ???? ??

The measured value is below the low warning threshold (Regulator Control Mode = negative).

W5 Cond. max.
????? ??? ???? ??

The measured value is above the high warning threshold (Regulator Control Mode = positive)


W7 Level Alarm X
????? ??? ???? ??

The level alarm input of product "X" has been activated (X=1, 2). A warning is generated if the level alarm input
is activated and the related equipment/ product are not needed. This error exists as warning and alarm. As longs,
as a product is not demanded, no alarm is generated because a Master not needing this product should not be
stopped by a level alarm of this product. In case of a product rarely needed, the equipment may continue working
as long as no actual demand appears.



JohnsonDiversey DOS-Controller 2C


Troubleshooting

Page 30

System Not Functional
If no display appears on the LCD screen when the system is switched on:

check all electrical connections

ensure that all fuses are functioning

ensure that the power supply has not been disrupted

If the system still does not function, please contact the service department.


If the display is working, check inputs and the reaction of the outputs with the integrated "I/O-Test" function


JohnsonDiversey DOS-Controller 2C


Example

Page 31

Example
System-configuration in stand-alone-mode
The following example shows the possible configurations to control two baths with a DOS-Controller-2C. All
types of dosing pumps and all dosing types, which can be used, are also shown.

Controler
Eq.3
(Valve)
Eq.1
(Valve)
Eq.1
(Pump)
Flow1
LA1
mA
Eq.2
(Valve)
Eq.2
(Pump)
Flow2
LA2
mA
Eq.4
(Valve)
CAUSTIC
ADDITIVE
Tank 1 Tank 2
Eq.3
(Pump)
Flow3
Eq.1
(Pump)
Flow1
LA1
mA
Eq.2
(Valve)
Eq.2
(Pump)
Flow2
LA2
mA
Eq.4
(Valve)
CAUSTIC
ADDITIVE
Tank 1 Tank 2
Eq.3
(Pump)
Flow3
Eq.1
(Pump)
Flow1
LA1
mA
Eq.2
(Pump)
Flow2
LA2
mA
Eq.4
(Pump)
CAUSTIC
ADDITIVE
1
Tank 1 Tank 2
Eq.3
(Valve)
Flow3
Eq.1
(Valve)
Eq.1
(Pump)
Flow1
LA1
mA
Eq.2
(Pump)
Flow2
LA2
mA
Eq.4
(Pump)
CAUSTIC
ADDITIVE
1
Tank 1 Tank 2
Controler
Controler Controler
System 1
"Two pumps
for two tanks"
System 2
"Twin caustic pumps,
one additive"
System 4
"Four pumps "
System 3
"One caustic pump
two additive pumps "


JohnsonDiversey DOS-Controller 2C


Example

Page 32

System-configuration in Master-Slave-Mode
The following example shows the possible configurations to control three baths with two DOS-Controller-2C's
All types of dosing pumps and all dosing types, which can be used, are also shown.

Eq.3
(Valve)
Eq.1
(Pump)
Flow1
LA1
Eq.2
(Pump)
Flow2
LA2
mA
Eq.4
(Valve)
CAUSTIC
ADDITIVE
Tank 1
System "Master-Slave"
"Two pumps, two tanks
and ring connection"
Eq.3
(Valve)
Eq.1
(Valve)
mA
Eq.2
(Valve)
mA
Eq.4
(Valve)
Tank 2 Tank 3
Master-
Controler
Slave-
Controler
CAN-Network
Eq.3
(Valve)
Eq.1
(Pump)
Flow1
LA1
Eq.2
(Pump)
Flow2
LA2
mA
CAUSTIC
ADDITIVE
Tank 1
System "Master-Slave-2"
"Common caustic pump;
seoarate pumps for additive"
Eq.3
(Valve)
Eq.1
(Valve)
mA mA
Tank 2 Tank 3
Master-
Controler
Slave-
Controler
CAN-Network
Eq.1
(Pump)
Flow1
Eq.2
(Pump)
Flow2

JohnsonDiversey DOS-Controller 2C


Example

Page 33


There is the prerequisite that the dosing pumps are gauged the capacity by litres. (Please refer to manual). Let us
assume the following values:
Equipment No.: chemical name: dosing type: dosing capacity:
1 caustic timed dosing 260l/h
2 additive timed dosing 3l/h


This leads to the following configuration:
Equipment parameters:
description 1 description 2 equipment
1
equipment 2 equipment
3
equipment
4
equipment description caustic additive caustic additive
chemical name for the
dosed liquid:

NaOH

Divo Ultra

NaOH

Divo Ultra
equipment mode (I/O) P P V V
product flow meter (Y/N) Y Y N N
pump type STROKE DOSING
PERMAN. DOSING

X
X


pulse/pause timers for
stroke dosing
On time:
Off time:
s
s
0.2
0.2

timed pump capacity l/h 260.0
stroke pump capacity p/l 3,0
flow meter product p/l 50
density kg/l 1.33 1.33
product flow min flow
max flow
kg/h
kg/h
150.0
600.0

operation mode: R/C/F/D R D R F
regulated dosing time
wait time
set point
dead band
timeout set point
reg. mode (pos/neg)
min alarm
max alarm
s
s


s
20
60
110mS
10mS
1800
neg.
70mS
130mS
10
60
050mS
05mS
1800
neg.
35mS
65mS
volume fix fixed volume
interval time
kg
s
0.1
900
dependent min volume
volume ratio
kg 0.005
0.100

initial charge set point kg 1.5 0.2 1,0 0.1
start up set point kg 1.0 0.1 0,7 0.1

Explanation of the configuration above:

Bath1, Product 1
Automatic: Dosage is analogue-controlled and has its set point at 110 mS. Due to the dead band of 10 mS and
the negative sense of control, dosage is started at actual value < 100 mS and is finished at actual value >
110 mS. Dosage runs with pulse/pause steps of 20/60 sec. A prerequisite is that releases are given, i.e. have
high-signal. A warning min - message is given out on the display if the actual value is below 70 mS, but
dosing doesnt stop. The dosing process will be stopped if actual value is higher than 130 mS.
Initial charge: in order to be able to start an initial charge, release must be given. Then the desired volume of 1,5
kg is directly dosed.
Start up: the same behavior as initial charge, but only a volume of 1,0 kg is dosed.
Manual: at manual dosage, a fixed volume of caustic, which have to be written to the controller, would be dosed
in the bath via equipment 1 (260l/h).
JohnsonDiversey DOS-Controller 2C


Example

Page 34


Bath 1, Product 2
Automatic: for this process, depending dosage is selected. A ratio of 10% is desired to be controlled to process 1.
This means, caustic/additive = 10/1. Additive dosage will only begin, if a volume to be dosed is more than
5g, calculated via the set ratio. This is controlled by the min volume function. If, e.g. during a dosing
process, a volume of 40g caustic has been dosed, the dosage of the additive will still be suppressed. As soon
as the 50g limit will be exceeded due to a further dosage and the ratio is 10%, the dosage of 5g additive will
be carried out.
Initial charge: At an initial charge, the maintenance-dosing pump (equipment 2) would deliver the demanded
volume of 0,2 kg.
Start up: the maintenance-dosing pump (equipment 2) doses the same behavior as initial charge, but only a
volume of 0,1 kg.
Manual: At manual dosage a free volume additive would be dosed in the bath via equipment 2.

Bath2, Product 1
Automatic: Dosage is analogue-controlled and has its set point at 55 mS. Due to the dead band of 5 mS and the
negative sense of control, dosage is started at actual value < 50 mS and is finished at actual value > 55
mS. Dosage runs with pulse/pause steps of 10/60 sec. A prerequisite is that releases are given, i.e. have high
signal. A warning min - message is given out on the display if the actual value is below 35 mS, but dosing
doesnt stop. The dosing process will be stopped if actual value is higher than 65 mS.
Initial charge: in order to be able to start an initial charge, release must be given. Then the desired volume of 1,0
kg is directly dosed.
Start up: the same behavior as initial charge, but only a volume of 0,7 kg is dosed.
Manual: at manual dosage, a fixed volume of caustic, which have to be written to the controller, would be dosed
in the bath via equipment 1 (260l/h).

Bath 2, Product 2
Automatic: This process is done independent from another process with Timed Fixed dosage. This means, as
soon as release signal is given, it will be dosed continuously every 3600 sec a volume of 0,1 kg. During
dosage, the DOS-Controller-2C sends pulse/pause signals with a length of 0,2/0,and 2s to the stroke pump.
Initial charge: An initial charge, 0,1 kg here, will only be started with release and done with dosing pump 2.
Again, strokes for the pump are used.
Start up: the dosing pump doses the same behavior as initial charge, 0,1 kg.
Manual: At manual dosage a free volume additive would be dosed in bath 2 via equipment 2.


JohnsonDiversey DOS-Controller 2C


Appendix

Page 35

Appendix A: Specifications

Supply Voltage : 115 V, 50...60 Hz or
230 V, 50...60 Hz (selectable by jumper J1)

Output to equipment (power) : Relays with two contacts,
Contacts may be connected to 24V/DC or supply voltage
Max. output current (power) : 3 A (8A peak) per contact
Output to equipment (stroke) : Opt-coupler, may be connected to 24V DC
Max. output current : 0,1 A

Output voltage ("Alarm, Running"): Relays with one contact,
Contact may be connected to 24V/DC or supply voltage
Max. output current (power) : 3 A (8A peak) per contact

Output voltage to flow sensor : 24V DC stabilized
Max. output current : 30 mA
Input voltage : 5V.. 24V

Output voltage to analogue sensor : 24V DC, stabilized
Max. output current : 30 mA

Inputs (ext. Trigger, Init. Charge : internal pull-up resistor (6,8 kohl) to +24V DC
Level Alarm)

Internal voltages : 24 V, DC (accessible)
: 5 V, DC (accessible)

Timing range : 1 ... 9999 seconds
Timing tolerance : 0,1 %

Operator interface : Integrated LCD-display (2 lines with 16 characters)
: 4 keys

Connectors : spring loaded terminals, max. 1,5 m
m2


Weight : 2,5 kg
Size : L 255 mm x W 323 mm x H 85 mm
Box : ABS
Insulation protection : IP 65
Temperature range : -10C ... +60C


JohnsonDiversey DOS-Controller 2C


Appendix

Page 36

Appendix B: Electrical Connections

The DOS-Controller-2C system should be connected, as the diagram below:

Note: Input Level Alarm 3 is not used by DOS-Controller 2C


C
_
L
P
E
C
_
H
C
_
L
P
E
C
_
H
G
N
D
A
I
1
+
+
2
4
V
G
N
D
A
I
2
+
+
2
4
V
G
N
D
F
l
o
w
1
+
2
4
V
G
N
D
F
l
o
w
2
+
2
4
V
G
N
D
F
l
o
w
3
+
2
4
V
0
V
L
A
1
0
V
L
A
2
0
V
L
A
3
0
V
S
t
a
r
t
-
U
p
0
V
I
n
i
t
.
C
h
.
0
V
e
x
t
.

R
e
l
.
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
P
E
G
N
D
G
N
D
G
N
D
G
N
D
+
2
4
V
+
2
4
V
+
2
4
V
+
2
4
V
A
l
m
_
A
A
l
m
_
B
R
u
n
_
A
R
u
n
_
B
S
1
E
S
1
C
S
2
E
S
2
C
S
3
E
S
3
C
S
4
E
S
4
C
P
_
1
A
P
_
1
A
P
1
_
B
P
_
1
B
P
_
2
A
P
_
2
A
P
_
2
B
P
_
2
B
P
_
3
A
P
_
3
A
P
_
3
B
P
_
3
B
P
_
4
A
P
_
4
A
P
_
4
B
P
_
4
B
N
L
N
L
N
L
N
L
N
L
1
C
A
N
-
B
u
s
4
-
2
0
m
A
-
I
n
p
u
t

S
e
n
s
o
r

1
4
-
2
0
m
A
-
I
n
p
u
t

S
e
n
s
o
r

2
I
n
p
u
t

F
l
o
w
s
e
n
s
o
r

1
I
n
p
u
t

F
l
o
w
s
e
n
s
o
r

3
I
n
p
u
t

F
l
o
w
s
e
n
s
o
r

2
I
n
p
u
t

L
e
v
e
l

A
l
a
r
m

1
I
n
p
u
t

L
e
v
e
l

A
l
a
r
m

1
I
n
p
u
t

L
e
v
e
l

A
l
a
r
m

1
I
n
p
u
t

"
S
t
a
r
t
-
U
p
"
I
n
p
u
t

"
I
n
i
t
i
a
l

C
h
a
r
g
e
"
I
n
p
u
t

"
e
x
t
e
r
n
a
l

R
e
l
e
a
s
e

T
r
i
g
g
e
r
"
O
u
t
p
u
t

c
o
n
t
a
c
t

"
A
l
a
r
m
"
O
u
t
p
u
t

c
o
n
t
a
c
t

"
R
u
n
n
i
n
g
"
S
t
r
o
k
e

o
u
t
p
u
t

t
o

p
u
m
p

1
S
t
r
o
k
e

o
u
t
p
u
t

t
o

p
u
m
p

4
S
t
r
o
k
e

o
u
t
p
u
t

t
o

p
u
m
p

3
S
t
r
o
k
e

o
u
t
p
u
t

t
o

p
u
m
p

2
2
4
V
/
D
C

t
e
r
m
i
n
a
l
s

(
o
u
t
p
u
t
)
M
a
i
n
s

t
e
r
m
i
n
a
l
s

(
o
u
t
p
u
t
)
M
a
i
n
s

s
u
p
p
l
y

(
i
n
p
u
t
)
O
u
t
p
u
t

c
o
n
t
a
c
t
s

(
2
)

t
o

p
u
m
p

1
O
u
t
p
u
t

c
o
n
t
a
c
t
s

(
2
)

t
o

p
u
m
p

4
O
u
t
p
u
t

c
o
n
t
a
c
t
s

(
2
)

t
o

p
u
m
p

3
O
u
t
p
u
t

c
o
n
t
a
c
t
s

(
2
)

t
o

p
u
m
p

1


Electrical connection of analogue inputs

2-wire
Sensor
2-wire
Display
+24V
AIx+
3-wire
Sensor
+24V
AIx+
2-wire sensors are connected between 24V and Aix
(analogue input no. X).
Direct input with an internal resistance of 270 Ohm (to
ground), this gives a voltage drop of 5.4 Volt at 20mA
input current.
Never connect more than 12V to this input!
A second passive 2-wire unit (e.g. a display) may be
connected in series as shown. In this case check the
power requirements (minimum voltage necessary for
operation) of both sensor and display.
3-wire sensors have to connect to GND as well.
Check the maximum supply current of the sensor,
it should be below 30mA.
A 2-wire (e.g. a display) may be connected
between sensor output and Alx. In this case check
the power requirements (max. output voltage of
sensor vs. minimum supply voltage of display).

JohnsonDiversey DOS-Controller 2C


Appendix

Page 37

Electrical connection of Level Alarm inputs

2-wire=
contact
4-wire=
Optocoupler
+24V
flowx
flowx
3-wire=
Hall-Sensor
+24V
flowx
2-wire=
Output
flowx
2.7k
2.7k
2.7k
2.7k
+24V
+24V
Direct connection of passive 2-wire
sensor (mechanical contact e.g. reed
relays, switch)
An active 2-wire output may be connected as
well. In this case check for the maximum
output voltage, it should be below 24V/DC
3-wire sensors (like Hall sensors or some
opto-couplers) can be powered by the
internal 24V/DC source.
The maximum supply current should be
below 30mA.
4-wire sensors (like opto-couplers) can be
connected as shown. Two connections two
Grounds are necessary.
Note: It may be necessary to add a series
resistor to limit the current through the internal
LED of the opto-coupler (see data sheet of the
sensor) if the sensor is not designed to be driven
with 24V/DC.

The flow sensor inputs are designed to be driven by positive voltage pulses. The sensor has to connect the input
flow with ground. A current of 9mA will have to be drained by the sensor then.
Maximum input frequency is 1kHz. Take care to keep cables away from high power cables in order to prevent
picking up of electromagnetic noise.

JohnsonDiversey DOS-Controller 2C


Appendix

Page 38

Electrical connection of Status inputs

Direct connection of passive 2-wire sensors
(relays, mechanical contacts) or outputs from a
PLC.

Input resistance 2,7kOhm to 24V/DC
Input current: 9mA (L), 0mA (H)
Input voltage 8..24V/DC

Approx. 15V will be measured at on open contact
d t i t l i it
LAx
Start-Up+
Init.Ch.+
ext.Trigger+
contact/
PLC
GND (...-)
2.7k
+24V

The input signal must be static; any pulsation will lead to error messages (Level Alarm) or may stop automatic
operation (ext. Release Trigger).


Electrical connection of Status outputs
+24V
AlmA
AlmB
GND
N
RunB
RunB
N
Lamp (24V/DC)
inside D-Determinator
Lamp (230V/ac)

The output is a relay with 1 contact (normally open), it may be connected to mains or 24V/DC or any external
voltage (max. 230V/ac)
The lifetime of the contact depends on the current to be switched.
The status outputs may be connected to different voltages
If a DC-voltage is switched, it is recommended to use a freewheeling diode to reduce spikes an electromagnetic
noise. The lifetime of the contact is extended by this diode. This diode is essential if inductive loads are stitched
(e.g. valves or relays).

JohnsonDiversey DOS-Controller 2C


Appendix

Page 39

Electrical connection of Equipment and Stroke outputs

+24V
P_xA
P_xA
GND
N
P_xB
P_xB
N
SxC
SxE
Lamp
or
Solenoid valve
Permanent dosing pump
or
solenoid valve/ relay
(without stroke signal)
or
Pulsed dosing pump
(with stroke signal)

The output is a relay with 2 contacts (normally open), they may be connected individually to mains or 24V/DC
or any external voltage (max. 230V/ac)
The lifetime of the contact depends on the current to be switched.
The status outputs may be connected to different voltages
If a DC-voltage is switched, it is recommended to use a freewheeling diode to reduce spikes an electromagnetic
noise. The lifetime of the contact is extended by this diode. This diode is essential if inductive loads are stitched
(e.g. valves or relays).
!!! Stroke-Outputs are 24V/ 0,05A!!

Electrical connection of CAN-Bus

The two cables of the CAN-Bus have to be connected to CAN_H and CAN_L. Both input clamps are identical
and may be used as input or as output. If a DOS-Controller is physically the last device within a network, the
jumper next to the CAN-Clamps has to be set. It activates the termination resistors. Wrong setting of this jumper
may lead to malfunction of the communication.
JohnsonDiversey DOS-Controller 2C


Appendix

Page 40


Appendix C: Menu Schemes
Operation Menu

From configuration
from any screen when no key was pressed for 60s
Status or Alarm
display
Do Automatic Mode
View Consumption
Enter
Select Equipment
(1-4): 2
Consumption/tot.
2: 99999,9 kg
Consumption/day
2: 999,999 kg
Manual Mode
Enter
Manual Mode
Equipm. (1..4): 2
Manual Vol.=123,4
2:Stop = Select
when Manual Mode is
already active
Initial charge
Enter
Configuration
Enter
Enter Password
xxxx
correct code
false code
S
S
S
E E
E E E
S/E
E
if alarm: E
S
S
E
E E E
System start when not configured
Goto configuration
Automatic
Operation
Consumption
Manual Mode
Diversey\dd_light\dd_menu1.drw 320.03.1998 2
Consumption/day
2: Reset = Enter
Do reset
consumption/day
E E
Go Offline
Initial Charge
Stop = Select
E
Initial Charge
only if Initial Charge is activated
S
Manual Volume
2: 999,9 kg
Manual Mode
2: Start = Enter
E
Equip.>3 Equipment+1
S
S
S
S
S S
Stop Initial Charge
Start-Up
Enter
Start-Up
Stop = Select
E
Start-Up
only if Start-Up is activated
S
Stop Start-Up
For Status and Alarm display types see table below
only if Initial Charge is not activated
only if Start-Up is not activated
Start-Up
Start = Enter
E E
Start Start-Up
Initial Charge
Start = Enter
E E
Start Initial Charge

JohnsonDiversey DOS-Controller 2C


Appendix

Page 41

Configuration Menu

To Operation
from any screen when
no key was pressed for 60s
Reset Cons.
Enter
Consumption/tot.
1: 9999,9 kg
Change Password
Enter
I/O-Test
Enter
S
S
S
E E
E
From Operation menu
Reset Consumption
diversey\dd_light\dd_conf1.drw 15.07.98 4
Enter Password
xxxx
Repeat Password
xxxx
Do Change Password
E
E E
Change Password
S
S
Analog Input 1
06,44 mA
Set Output 1 - 8
0 0 1 0 1 1 1 1
E
E
I/O-Test
S
Resume Operation
Start = Enter
S
Enter Password
xxxx
Do Reset Consumption/tot
for product 1, 2, 3, 4
E
E
Consumption/ tot.
3: 9999,9 kg
Set Output 9 -16
x x x x x x 0 0
E
E
S
Flow Sensor 1-8
x x x x x P P P
E
S
Analog Input 2
03,63 mA
Dig.Input 1-8
x x 0 0 1 1 0 0
E
S S
S
S
Consumption/tot.
Reset = Enter
E
S
Equipment Config
Enter
S
Sensor Config.
Enter
S
Equipment Configuration
E
Goto Automatic Mode
(Operation menu)
(false code)
(false code)
Language Setting
Enter
Sel. Language
(E/D/F/Sp/P): E
D-Determinator2C
Version 1.0
E
E S/E
Language Settings
S
S
Consumption/ tot.
4: 9999,9 kg
S
Consumption/ tot.
2: 9999,9 kg
Sensor Configuration
E
Network Setting
Enter
S
E
This menu appears only if the
CAN-Interface is equipped
Use Network
(M/S/N): M
Network ID
1234
E E
Network Settings
S S/ false Code

JohnsonDiversey DOS-Controller 2C


Appendix

Page 42

Input Configuration, Submenu to Configuration

Both sensor inputs will be configured according to the same scheme.

Select Sensor
1: Conduct.
E
S E
From Configuration
Conductvity
Sensor
diversey\dd_light\menu_se1.drw 30.03.1998 1
Cond.-Scale max.
1: 2000 mS
Cond. sel. Unit
1: mS
E
E
Free Cond. Curve
1-1:0500mS=07,5%
only if "free curve"
is selected
Direct display of sensor signal
Direct Display
1: (mA/%): mA
E E
"Conduct."
"direct"
Sel. Current Min.
1: (0/4mA): 4
S
E
E
Select Sensor
2: Conduct.
S E
To Configuration

JohnsonDiversey DOS-Controller 2C


Appendix

Page 43

Equipment Configuration (stand alone mode)

DOS-Controller 2C in stand-alone-mode (without network or Network-usage = N)

Select equipment
(1-4): 1
"Stroke"
S
From Configuration
switch off equipment E
"OFF"
To Configuration
Product Density
1: 1,999 kg/l
Prod. Flow Rate
1: T. I. (Y/N):Y
Fill Test Volume
1: Start=Enter
Enter Weight
1: 999,999 kg
Fill Test Volume
1: Stop =Enter
Yes
No
Setpoint
1: 1999 mS
Wait Time
1: 9999 sec
Timeout - Setpt.
1: 9999 sec
Deadband
1: 1999 mS
Interval Time
1: 9999 sec
fixed Volume
1: 999,999 kg
"Analog Regulator"
(Equip.1/3 only)
Dose Time
1: 9999 sec
Setpt. Init.Ch.
1: 999,999 kg
Max. Alarm
1: 1999 mS
Min. Alarm
1: 1999 mS
Equipm.: 1 2 3 4
Mode: R D R F
S
Vol. Ratio
2: 1,000
"dependant"
(Equip. 2/4)
min. Volume
2: 999,999 kg
Return to Config.
Start = Enter
Stroke time Eq.1
1: 9,9 sec
diversey\dd_light\equip_1.drw 30.03.98 2
Pause time Eq.1
1: 9,9 sec
Equipment Mode
1: (P/V/O): P
S
"Permanent"
Select Pump Type
1: (S/P): S
Timed PumpProd.
1: 999,9 l/h
Stroke PumpProd.
1: 9999 p/l
Flowmeter Prod..
1: 9999 p/l
only for timed
dosing pump
only for stroked
dosing pump
only for product
flow meter
"Volume fix"
(Equip. 1-4)
Equipment Number+1
Prod. Flowmeter
1: (Y/N):Y
Prod. Flow Rate=
1: 9999,9 kg/h
Operation Mode
1:(R/F/D): R
not Equip.3
Max. Prod. Flow
1: 999,9 kg/h
Min. Prod. Flow
1: 999,9 kg/h
only when
flow meter = Yes
S E
if Equip.3/4
= V (Valve)
Setpt. Start-Up
1: 999,999 kg

JohnsonDiversey DOS-Controller 2C


Appendix

Page 44

Equipment Configuration (Master)
DOS-Controller 2C as Master (with network, Network-usage = M)
!! Equip.4 : V/O !!

Select equipment
(1-4): 1
"Stroke"
S
From Configuration
switch off equipment E
"OFF"
To Configuration
Product Density
1: 1,999 kg/l
Prod. Flow Rate
1: T. I. (Y/N):Y
Fill Test Volume
1: Start=Enter
Enter Weight
1: 999,999 kg
Fill Test Volume
1: Stop =Enter
Yes
No
Setpoint
3: 1999 mS
Wait Time
3: 9999 sec
Timeout - Setpt.
3: 9999 sec
Deadband
3: 1999 mS
Interval Time
3: 9999 sec
fixed Volume
3: 999,999 kg
"Analog Regulator"
(Equip.3 )
Dose Time
3: 9999 sec
Setpt. Init.Ch.
3: 999,999 kg
Max. Alarm
3: 1999 mS
Min. Alarm
3: 1999 mS
Equipm.: 1 2 3 4
Mode: P P R F
S
Vol. Ratio
4: 1,000
"dependant"
(Equip. 4)
min. Volume
4: 999,999 kg
Return to Config.
Start = Enter
Stroke time Eq.1
1: 9,9 sec
diversey\dd_light\equip_2.drw 03.04.98 1
Pause time Eq.1
1: 9,9 sec
Equipment Mode
1: (P/V/O): P
S
"Permanent"
Select Pump Type
1: (S/P): S
Timed PumpProd.
1: 999,9 l/h
Stroke PumpProd.
1: 9999 p/l
Flowmeter Prod..
1: 9999 p/l
only for timed
dosing pump
only for stroked
dosing pump
only for product
flow meter
"Volume fix"
(Equip. 3/4)
Equipment Number+1
Prod. Flowmeter
1: (Y/N):Y
Prod. Flow Rate=
1: 9999,9 kg/h
Operation Mode
1:(R/F/D): R
Equip.1/2
Max. Prod. Flow
1: 999,9 kg/h
Min. Prod. Flow
1: 999,9 kg/h
only when
flow meter = Yes
S E
if Equip.mode
= V (Valve)
Setpt. Start-Up
3: 999,999 kg
if of Equip.mode=P (Pump)
Equip.3/4
Equip.1: P
Equip.2: P/O
Equip.3:V/O
Equip.4: P/V/O


JohnsonDiversey DOS-Controller 2C


Appendix

Page 45

Equipment Configuration (Slave)
DOS-Controller 2C as Slave (with network, Network-usage = S)

Select equipment
(1-4): 1
"Stroke"
S
From Configuration
switch off equipment E
"OFF"
To Configuration
Product Density
2: 1,999 kg/l
Prod. Flow Rate
2: T. I. (Y/N):Y
Fill Test Volume
2: Start=Enter
Enter Weight
2: 999,999 kg
Fill Test Volume
2: Stop =Enter
Yes
No
Setpoint
3: 1999 mS
Wait Time
3: 9999 sec
Timeout - Setpt.
3: 9999 sec
Deadband
3: 1999 mS
Interval Time
3: 9999 sec
fixed Volume
3: 999,999 kg
"Analog Regulator"
(Equip.1/3 )
Dose Time
3: 9999 sec
Setpt. Init.Ch.
3: 999,999 kg
Max. Alarm
3: 1999 mS
Min. Alarm
3: 1999 mS
Equipm.: 1 2 3 4
Mode: R D R F
S
Vol. Ratio
4: 1,000
"dependant"
(Equip. 2/4)
min. Volume
4: 999,999 kg
Return to Config.
Start = Enter
Stroke time Eq.1
2: 9,9 sec
diversey\dd_light\equip_3.drw 03.04.98 1
Pause time Eq.1
2: 9,9 sec
Equipment Mode
1: (P/V/O): P
S
"Permanent"
Select Pump Type
2: (S/P): S
Timed PumpProd.
2: 999,9 l/h
Stroke PumpProd.
2: 9999 p/l
Flowmeter Prod..
2: 9999 p/l
only for timed
dosing pump
only for stroked
dosing pump
only for product
flow meter
"Volume fix"
(Equip. 1-4)
Equipment Number+1
Prod. Flowmeter
2: (Y/N):Y
Prod. Flow Rate=
2: 9999,9 kg/h
Operation Mode
1:(R/F/D): R
Max. Prod. Flow
2: 999,9 kg/h
Min. Prod. Flow
2: 999,9 kg/h
only when
flow meter = Yes
S E
if Equip.mode
= V (Valve)
Setpt. Start-Up
3: 999,999 kg
if of Equip.mode=P (Pump)
Equip.1: V/O
Equip.2: P/V/O
Equip.3:V/O
Equip.4: P/V/O

JohnsonDiversey DOS-Controller 2C


Appendix

Page 46

Appendix D: Parameter List
Display Description Range Physical
unit
Alarm Delay Time Time Delay until a alarm is released if deviation
between primary and secondary sensor exceeds
pre-set values
0... 9,999 sec
Analogue Input X Input current to analogue input "X" (X=1,2)
during I/O-Test
0... 20 mA
Cond. Free curve
1-x:____mS=__,_%
A custom specific characteristic to display
conductivity has been chosen. Every point "x" of
this curve can be set independent of each other. A
total of 7 points can be set. The conductivity has
to be set first.
0... 9999
0... 9999
S
mS
Cond. Free curve
1-x:____mS=_,_%
A custom specific characteristic to display
conductivity has been chosen. The concentration
of product has to be set second.
0... 99,9 %
Cond. Scale max. Conductivity (or concentration) necessary at
sensor to give 20mA output current.
0... 9999
0... 9999
0... 99,9
S
mS
%
Cond. Sel. Unit
Conductivity can be displayed as "mS", "S" or as
a choice of different product concentrations (e.g.
NaOH). A custom specific characteristic can be
selected too ("free")
mS, NaOH,...,
free
-
Consumption/day One daily consumption counter for each product,
these counters can be reset individually in main
menu
0... 9.999,9 kg
Consumption/tot. One total consumption counter for each product,
these counters can be together in configuration
menu
0... 99.999,9 kg
Deadband Difference between stopping the equipment 1 and
restart of dosing.
0... 100 %
Dig. Input 1-8 The actual state of up to 8 digital inputs is
displayed. As DOS-Controller-2C uses only 5
inputs, the upper 3 inputs are denoted as "X". A
high-Level input signal will be displayed as "1", a
low level input signal will be displayed as "0".
0/1 -
Direct Display If no physical value is related to the sensor signal
the value can be displayed as "0/4-20 mA" or as
"0-99,9 %"
mA, % -
Enter weight The amount of product (weight not volume) that
has been pumped during Teach-In Mode.
0...999,999 kg
Equipm.: 1 2 3 4 Operating mode of all 4 equipments displayed
together.
R (Equip. 1,3): Analogue regulator
F (Equip. 1-4): Volume fix
D (Equip. 2,4): dependant
R, F, D -
JohnsonDiversey DOS-Controller 2C


Appendix

Page 47

Equipment Mode This is the pump type of the selected equipment:
S: stroked
P: permanent
S/ P -
Fixed Volume This is the volume that has to be delivered during
one interval in "volume fix" mode
0... 999,999 kg
Flow Sensor 1-8 The actual state of up to 8 flow sensor inputs is
displayed. As DOS-Controller-2C uses only 2
flow sensors, the upper 6 inputs are denoted as
"X". A high-level input signal will be displayed as
"1", a low level input signal will be displayed as
"0" and a pulsing signal at the flow meter input
will be displayed as "P"
0/ P/ 1 -
Flowmeter Prod. The number of pulses per litre produced by the
flow meter taken from flow meter data sheet
0... 9999 Imp./litre
Interval Time This is the interval length in "Volume fix" mode.
In this mode the pump is delivering the set "Fixed
Volume" within every interval and then will be
stopped for remaining time.
0... 9.999 sec
Manual Vol=___,_ The remaining volume in "manual" mode. This is
a read-only value.
0... 999,999 kg
Manual Volume This is the volume that has to be delivered during
"manual" mode. This value is entered while
manual mode is started
0... 999,999 kg
Max. Alarm This is the alarm threshold for the controlled
value. If the value stays above this level longer
than the set delay time, an alarm is released.
See sensor scale
max.
Same as
setpoint
Max. Prod. Flow If a flow meter is used the product flow is
controlled to stay within limits. This is the
maximum flow. Outside these limits an alarm is
released.
0... 999,9 kg/h
Min. Alarm This is the alarm threshold for the controlled
value. If the value stays below this level longer
than the set delay time, an alarm is released.
See sensor scale
max.
Same as
setpoint
Min. Prod. Flow If a flow meter is used the product flow is
controlled to stay within limits. This is the
minimum flow. Outside these limits an alarm is
released.
0... 999,9 kg/h
min. Volume This is the minimum volume in "dependant"
mode. In this mode the pump is running for the set
"Pulse Time" and then will be stopped for "Pause
Time".
0... 999,999 kg
Min.-Max.-Alarm This is a selection activates/ deactivates the
additional minimum-maximum alarm feature
Y/ N -
Network ID This is the address of this DOS-Controller-2C
within the CAN-Network
0... 99 -
Operation Mode This is the operating mode of the equipment:
R. analogue regulator
F: volume fix
D: dependant
R/ C/ F/ D -
JohnsonDiversey DOS-Controller 2C


Appendix

Page 48

Pause Time Eq. X This is the minimum pause time between two
strokes pulses if the equipment (pump) is in
"stroked" mode.
0... 9.999 sec
Pause Time This is the pause in "analogue regulator" mode. In
this mode the pump shall not run permanently if
the setpoint is not reached
0... 9.999 sec
Prod. Flowmeter This is a selection whether a flow meter for
product is used
Y/ N -
Prod. Flow Rate
X: T.I.(Y/N):
This is a selection if a flow data is entered
manually or if a teach-in has to be made.
Y/ N -
Product Density The density of the used product, this parameter is
not necessary if a teach-in is made.
0... 1,999 kg/l
Pulse Time This is the pulse length in "analogue regulator"
mode. In this mode the pump is running for the set
"Pulse Time" and then will be stopped for "Pause
Time".
0... 9.999 sec
Sel. Current min. The minimum current produced by the sensor can
be chosen between 0 and 4 mA. In case of a 4-20
mA-Sensor an automatic control for broken wire
is activated.
0/4 mA
Select Equipment The equipment to be configured can be selected. 1.. 4 -
Select Pump Type The type of pump used can be selected between
"stroke" and "permanent"
S/ P -
Set Output 1-8 The actual state of 8 digital outputs is displayed
and set. A high-Level output signal will be
displayed as "1", a low level output signal will be
displayed as "0".
0/1 -
Set Output 9-16 The actual state of up to 8 digital outputs is
displayed and set. As DOS-Controller-2C uses
only 8+2 inputs, the upper 6 inputs are denoted as
"X". A high-Level output signal will be displayed
as "1", a low level output signal will be displayed
as "0".
0/1 -
Setpoint This is the setpoint for the controlled value. If the
value does not reach this level within the set
timeout delay, an alarm is released.
See sensor scale
max.
Same as
setpoint
Setpt. Init. Ch. This is the volume to be delivered during initial
charge mode. If the value reaches the alarm within
this limit, an alarm is released.
0... 999,999 kg
Setpt. Start-Up This is the volume to be delivered during initial
charge mode. If the value reaches the alarm within
this limit, an alarm is released.
0... 999,999 kg
Stroke Pump Prod The number of pulses necessary to pump one litre
of product by the dosing pump taken from dosing
pump data sheet
0... 9999 Imp./litre
Stroke Time Eq.X This is the stroke pulse length if the equipment
(pump) is in stroked mode.
0... 9.999 sec
JohnsonDiversey DOS-Controller 2C


Appendix

Page 49

Timed Pump Prod. The flow of product by the dosing pump at full
speed taken from dosing pump data sheet
0... 999,9 Litre/h
Timeout Setpt. If the setpoint is not reached within this time, a
warning is released.
0... 9.999 sec
Volume Ratio The ratio between product delivered by equipment
1 and equipment 2/4 in "dependant" mode
0... 1,000 -




JohnsonDiversey DOS-Controller 2C

Appendix E: Mounting Diagram
To open the case, put a large screwdriver into the gap on the right side of the front panel. Snap the closing flap to
the right. Now the front panel can be opened to the left side.




Hinge Opening side


JohnsonDiversey DOS-Controller 2C

Appendix F: Specific conductivity diagrams

Concentr. % NaOH % KOH % H3PO4 % H2SO4 % HNO3
0% 0,0 mS/cm 0,0 mS/cm 0,0 mS/cm 0,0 mS/cm 0,0 mS/cm
1% 45,0 mS/cm 33,8 mS/cm 9,4 mS/cm 40,6 mS/cm 54,0 mS/cm
2% 89,0 mS/cm 63,6 mS/cm 15,2 mS/cm 71,8 mS/cm 108,0 mS/cm
3% 125,0 mS/cm 83,4 mS/cm 20,3 mS/cm 98,4 mS/cm 158,4 mS/cm
4% 157,0 mS/cm 101,3 mS/cm 24,2 mS/cm 130,0 mS/cm 212,4 mS/cm



0
50
100
150
200
0% 1% 2% 3% 4%
Concentration (%)
C
o
n
d
i
c
t
i
v
i
t
y

(
m
S
/
c
m
)
% NaOH
% KOH
% H3PO4
% H2SO4
% HNO3




Data taken at 20C, measuring frequency 40 Hz
JohnsonDiversey DOS-Controller 2C

JohnsonDiversey DOS-Controller 2C
Glossary

You might also like