You are on page 1of 8

Inductive Voltage Transformers

Types VEOT and VEOS


2
Inductive Voltage Transformers
Introduction
Trench is a recognized w orld leader in the
design and m anufacture of high voltage
equipm ent for application on electric
utility and high energy industrial system s.
A s part of Trench's product scope, the
C om pany produces a diversified range of
Instrum ent Transform ers w hich are
installed on 69-800 kV electrical system s.
Instrum ent Transform ers include: Voltage
(Potential) Transform ers (both inductive
and capacitive type), C urrent Transform ers
and C om bined Instrum ent Transform ers
(voltage and current transform er in one
unit).
Voltage Transform ers m ust convert trans-
m ission class voltages to standardized
low and easily m easurable values, w hich
w ill be used for m etering, protection and
control of the high voltage system . A s
such, the need for accurate and reliable
voltage transform ation is essential.
This brochure w ill detail the features and
characteristics of types VEO T and VEO S
inductive type Voltage Transform ers.
Please refer to Trench brochure E210 for
additional general inform ation concerning
high voltage Instrum ent Transform ers.
Fig. 1
Type VEOT 72,5(left) and
VEOT 245(right)
oil/paper Insulated
Voltage Transformers
3
highly refined and processed
oil/paper insulation system
low w eight and m inim um oil
volum e
use of high quality m ineral oil,
PC B free, biological decom posi-
tion
excellent seism ic perform ance
as a consequence of optim ized
designs of flanges, porcelain and
their interconnection
excellent control of internal and
external insulation stresses
through the use of a proprietary
finely graded bushing system
essentially unaffected by stray
external m agnetic fields
herm etically sealed stainless steel
m etallic bellow s for units rated
123 kV and above
w elded housings sealed w ithout
screw s
Features
M eet all IEC and A N SI m etering
and protection classes
(other standards on request)
Standard therm al burden
ratings of 2000 -2500 VA
(higher on request)
Q uality A ssurance in
accordance w ith ISO 9001
stable accuracy over a long period
of tim e
perfect transient perform ance
suitable for line discharging
exclusive use of corrosion-resistant
m aterials
explosion resistant by
-insulating system w ith high
reliability
-fine graded bushing
-w eak point in the alum inium
head and tank castings and
the m etallic bellow s serving as
pressure release device
successful field experience since
the m anufacture of the first volt-
age transform er in 1926
m aintenance free during a long
life tim e of m ore than 30 years
com posite insulator available on
request
4
Trench types VEO T and VEO S
Inductive Voltage Transform ers are
designed and constructed w ith the
w ell proven, highly reliable, oil/
paper insulation system . Each
porcelain housed, herm etically
sealed Voltage Transform er is
equipped w ith stainless steel
expansion bellow s, calibrated to the
internal oil volum e and extrem es in
am bient operating tem peratures.
For voltage classes up to 300 kV,
the type VEO T is offered. For ap-
plications above 300 kV, Trench
offers the type VEO S design. The
VEO S is designed w ith a prim ary
w inding w hich is located in the
m id-point of the structure. This
feature serves to reduce the dielec-
tric stresses and
ensures optim ized
voltage distribution
w ithin the trans-
form er. Please refer
to figure Fig. 3 for
the internal
schem atic diagram
and m echanical
details for both the
VEO T and VEO S
units.
Construction
alum inum flat pad prim ary
term inal/ground term inal
Iifting lugs
bellow s position indicator
oil filling port
oil drain valve
secondary term inal box w ith
rem ovable gland plate
stud type prim ary term inal
prim ary or ground cable con-
nector
A nti-corona rings
C apacitance tap for m easure-
m ent of tan delta of bushing
or high voltage w inding
G as D etection System (contact
Trench for additional details)
Secondary fuses or circuit
breakers
Term inal box heater
C om posite insulator
Standard Equipment Optional Equipment
Fig. 2
Inductive
Voltage Transformers
VEOT
5
Prim ary term inal
M etallic expansion bellow s
O il filling screw
Porcelain insulator
Secondary term inal box
Secondary term inals
O il drain valve
G rounding term inal
G land plate
Lifting lugs
Bellow s indicator
Bushing
Secondary w inding
Prim ary w inding
Transform er head (alum inum )
Tank (alum inum )
Iron core
VEOT VEOS
12
Sectional view
A
1a 1n 2a 2n da N dn
A
N 1a 1n 2a 2n
VEOS VEOT
Fig. 3
Electrical and Mechanical
design details
3
1
15
2
4
16
14
17
13
7
10
5
6
9
8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
11
12
3
2
14
17
13
12
1
15
11
4
10
16
4
7
5
6
9
8
6
Oil /Paper-insulated
Inductive Voltage Transformers
Electrical and Mechanical Data (1)
Type M ax. continuous test voltage Im pulse Sw itching m in. Standard
operating voltage 50/60H z w ithstand im pulse test sparking creepage
phase to phase 1 m in. dry/w et 1.2/50 s voltage distance distance
kVeff kVeff kVpeak kVpeak m m m m
VEO T 72.5 H T 72.5 140 325 630 1815
VEO T 72.5 72.5 140 325 700 1815
VEO T 123 123 230 550 1200 3815
VEO T 145 145 275 650 1200 3815
VEO T 170 170 325 750 1400 4495
VEO T 245 245 395 950 2200 6300
VEO T 245 245 460 1050 2200 6300
VEO T 300 300 460 1050 850 2200 6300
VEO S 362 362 570 1300 950 2650 9050
VEO S 420 420 630 1425 1050 3200 11025
VEO S 420 420 680 1550 1050 3200 11025
VEO S 550 550 680 1550 1175 3800 13750
N otes:
(1) O ther ratings available on request
7
Fig N et w eight D im ension
W eight of oil
(approx)
h1 h2
kg m m m m kg
A 210 1515 40
B 290 2060 40
B 310 2560 43
B 320 2560 45
B 330 2760 47
C 670 3650 115
C 670 3650 115
C 670 3650 115
D 1020 5100 4765 220
D 1200 5650 5315 240
D 1200 5650 5315 240
D 1450 6300 5960 265
Fig. A
Fig. C Fig. D
Fig. B
450
600 600
h
1
h
1
h
1
h
1
h
2
450
Subject to change w ithout notice
04.2000
E211.21
www.trenchgroup.com
Trench A ustria G m bH
Paschinger Strasse 49, Postfach 13
A -4060 Linz-Leonding/A ustria
Phone +43.732.6793-0
Fax +43.732.6713 41
E-M ail sales@ TrenchA ustria.at
Trench Brasil LTD A
Via Expressa de C ontagem , 2685
C EP 32370-485
C pm tagem , M G - Brasil
Phone 55. 31. 391-5959
Fax 55. 31. 391-1828
E-M ail
trenchbrasil@ ca.trenchgroup.com
Trench Lim ited
C oil Product D ivision
71 M aybrook D rive, Scarborough
O ntario, C anada M 1V 4B6
Phone (416) 298-8108
Fax (416) 298-2209
E-M ail sales@ ca.trenchgroup.com
Trench Lim ited
Instrum ent Transform er D ivision
390 M idw est Road, Scarborough
O ntario, C anada M 1P 3B5
Phone (416) 751-8570
Fax (416) 751-6952
E-M ail sales@ ca.trenchgroup.com
Trench France S.A .
16, rue du G nral C assagnou
B.P. 70
F-68302 St-Louis C edex/France
Phone +33.3.89 70 23 23
Fax +33.3.89 67 26 63
E-M ail sales@ trench-france.com
Trench G erm any G m bH
N rnberger Strasse 199
96050 Bam berg/G erm any
Phone +49.951.1803-0
Fax +49.951.1803-224
E-M ail sales@ trench.de
Trench Sw itzerland A G
Lehenm attstrasse 353
C H -4028 Basel/Sw itzerland
Phone +41.61.315 51 11
Fax +41.61.315 59 00
E-M ail sales@ trench.ch