A loss of generator excitation during parallel operation will
result in heavy circulating currents, pole-slipping (loss of synchronisation) and torque/current surges and oscillation. The Stamford Excitation Loss Module monitors the generator AVR output and signals any sustained interruption to an integral relay to initiate an indication/alarm. The ELM, which has been specially designed for use with all the Companys AVRs, is powered independently from the engine battery at 12V or 24V. It operates by detecting the absence of the characteristic rectifier ripple in the exciter field voltage. An optical isolator used to ensure complete electrical isolation between the exciter field circuit and the engine battery system. Any loss of AVR output is recognised immediately by the monitoring circuit, and if the interruption persists for more than about a second the module output energises an integral relay. The changeover contacts can either provide remote indication of the excitation failure or operate any other relay-fed protective device. The system incorporates a time delay to prevent spurious tripping on transients and an overrideable eight-second engine-start lock- out. Robust and reliable solid-state electronics. Independently powered from engine battery. Power supply completely isolated from exciter field. Engine-start lock-out time delay. SPECIFICATION There are two versions of the ELM; one for 12V engine battery systems and one for 24V. SENSING INPUT Voltage 0-150 Vdc Input resistance 100 k ohms Sensitivity 50 v peak POWER INPUT Voltage 10-14 Vdc (ELM 12V) 20-28 Vdc (ELM 24V) Current (standby) 25 ma max all models Relay on 150 ma max (ELM 12V) 60 ma max (ELM 24V) OUTPUT Single pole changeover relay Rating 5A @ 30 Vdc 5A @ 240 Vdc Power dissipation 3 Watts maximum TIME DELAYS Response time 1.5-2 seconds Power up delay 8-15 seconds ENVIRONMENTAL Vibration 20-100 Hz 30 mm/sec 100 Hz - 2 kHz 2g Relative humidity 95% Operating temperature -40 to +70C Storage temperature -55 to +80C GENERAL ARRANGEMENT DIAGRAM Not suitable for mounting in generator terminal box. Switchboard or bedplate mounting recommended. CONNECTION DIAGRAM TD_EXC-LOSS.GB_09.02_01 PO Box 17 Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100 Website: www.newage-avkseg.com 2002 Newage International Limited. Reprinted with permission of N.I. only. Printed in England.