Professional Documents
Culture Documents
I58
MODULE
159
55
sa
4s
40
31
30
25
20
is
to
--_
.5 1
:
d
-20
-2 5
do
UN
do
40
-40
-I
-125
TRIP
PSB
UR TMRH 2 A
UY TMRH 2 B
IR TMRH 2 A
IY TMRH 2 B
UB TMRH 2 C
IBTMRH2C -
10
11
vs
UN
100
75
50
25
0
-25
-50
-75
-100
-125
TRIP
UR TMRH 2 A
UY TMRH 2 B
UB TMRH 2 C
IR TMRH 2 A
IY TMRH 2 B
I6 TMRH 2 C
I
- .
PSB
I
10
.
I
"
12
14
16
us
161
"1
"1
V. TEST RESULTS
VI. CONCLUSIONS
For the case of mho characteristic, it is observed that>for
long lines i.e. greater than lOOkm when one line is on
outage, during the disturbance the power swing blocking
element will block from 2s to 3s and from 4.5s to 7.5s and
trip when the load impedance locus stays in zone 3 during
event 5 more than the setting time of zone 3 i.e. 3 seconds
(4.5s to7.5~). However if the line is less than 100krr1, the
impedance locus does not enter zone 3 even after event 5.
As for THR the characteristic of power swing element is
that once the power swing is detected, it will block and reset
when the event is over.
Quadrilateral characteristics of numerical reIays have the
shapes that take into account the possibility of load
encroachment. Hence when testing was performed on the
500kV Jaaamanjung - Air Tawar and Air Tawar Bukit
Tarek lines the load is a distance away form the zone 3.
Another contributing factor is the C T ratio. The CT ratio
for Kenyir - Tanah Merah line is 1000/1 whereas for the
5OOkV line is 4000/1. Hence, besides the characteristics of
the relay, the CT ratio also plays an important part in
determining whether load impedance locus will encroach
zone 3 during disturbance.
162
VII.
[l]
[2] Dr. Fred Stcinhwscr, "'l'cstinp 01' tlic t'owcr Swing Illockmg in
REFERENCES
TABLE 1
DISTANCE AND CT RATIO FOR CRITICAL LMES
Notes:
CT Ratio
PGAU-TMRH
TMRH-KNYR
2OOO/L (PGAU)
120011 (TMRH)
KNYR-PAKA
1000/1 (KNYR)
1200/1 (TMRH)
1000/1 (KNYR)
1600/1 (PAKA)
163
164
m
lN
vi
r-N