Technical Manual of

YTONG Autoclaved Aerated Concrete Block

Formation DescriptionDesign
Design Explanation
Explanation

Contents

.. Formation Reference
Based on current national specifications, local standards of Shanghai and related product testing results of YTONG blocks, combining our engineering practical experience
of the past several years according, this collective drawing is prepared according to the industrial standard Technical Specifications of Autoclaved Aerated Concrete
Application JGJ17 (to be approved) and related information from Germany, Japan, Taiwan provided by Shanghai YTONG Co., Ltd.

.. Quality Standards
YTONG blocks are produced and processed according to the national quality standard of Autoclaved Aerated Concrete Building Block (GB/T11968) and YTONG block
enterprise standard (Q/QJCG-07-2002) of Shanghai YTONG Co., Ltd. The enterprise standard is stricter in product precision, strength coecient of variation than the
national standard.

. Performances
With the main production raw materials of fine ground quartz sand, cement, lime, gypsum and the foaming agent of aluminium powder, YTONG block is a kind of light
autoclaved aerated concrete product produced according to the production techniques of German YTONG patents.
YTONG block has the following features:
1. Light density, which is about 1/3 of the d brick and 1/4 of concrete. It can reduce the dead load of the building eectively and lower the total construction cost of the
building.
2. Good heat insulation performance. The coecient of heat conductivity of YTONG block is 0.11~0.16W/m.K, which is only 1/10 of concrete and a kind of good
internal and external heat insulation material.

Contents....................................................... ............................................................................................Page

Contents.........................................................................................................................................................................Page

Formation Description......................................................................................................................S1~S8
Arrangement Description of YTONG Block.........................................................................................S9
Painting and Facing Method Description of YTONG
Block Internal and External Wall.........................................................................................................S10
Plan of Non-loadbearing Block Wall and Related Cutlines..............................................................1
Plan Arrangement of Blocks of External Covering Column of External Wall..............................2
Plan Arrangement of Blocks of External Flat Column of External Wall.......................................3
Plan Arrangement of Block of the Internal Wall..................................................................................4
Arrangement of Vertical Blocks of Non-loadbearing External Wall (Frame Structure External
Flat) (1)..............................................................................................................................................................5
Arrangement of Vertical Blocks of Non-loadbearing External Wall (Wall Type Frame Structure)
(2)........................................................................................................................................................................6
Arrangement of Vertical Blocks of Non-loadbearing External Wall (External Covering Frame
Structure) (3)...................................................................................................................................................7
Arrangement of Vertical Blocks of Non-loadbearing External Wall (External Covering Frame
Structure) (4)...................................................................................................................................................8
Wall Doors and Windows Installation
Structure..........................................................................................................................................................9
Internal Wall Foaming Structure Adhesive Fixed Wood Door Installation
Structure.........................................................................................................................................................10

Installation Structure of External Wall Doors and Windows............................................................................11


Vertical Gap and Horizontal Gap of the Connection of Non-loadbearing Filled
Block Wall and Reinforced Concrete wall column or Beam Panel................................................................12
Structure of Dierent Parts of the Wall...................................................................................................................13
Structure of Expansion Joint......................................................................................................................................14
Production Method of Non-loadbearing Lintel (1)...............................................................................................15
Production Method of Non-loadbearing Lintel (2)...............................................................................................16
Sample of Non-loadbearing Wall Anchoring (1)..................................................................................................17
Sample of Non-loadbearing Wall Anchoring (2)..................................................................................................18
External Covering Anchoring of External Wall.....................................................................................................19
Usage and Features of Supporting Materials of YTONG Block.......................................................................20

3. Good fire-resistant and fire-proof performance. The fire endurance of 150mm thickness YTONG block is longer than 4 hours. YTONG blcok is inorganic
silicate material, which is non-flammable and does not produce poisonous gases.
4. High accuracy, which can guarantee the application of thin layer construction techniques. With good processing performances, it can be cut, sawed, engraved slots.,
etc.
5. The strength grading and density grading shall meet the requirements of the following table. The dry density of YTONG block is 425~625kg/m.

Formation Description

Drawing No.
Page

2012HU J/T--105
05
S1

Contents

Drawing No.
Page

2012HU J/T--105
05

Formation DescriptionDesign
Design Explanation
Explanation

Contents

.. Formation Reference
Based on current national specifications, local standards of Shanghai and related product testing results of YTONG blocks, combining our engineering practical experience
of the past several years according, this collective drawing is prepared according to the industrial standard Technical Specifications of Autoclaved Aerated Concrete
Application JGJ17 (to be approved) and related information from Germany, Japan, Taiwan provided by Shanghai YTONG Co., Ltd.

.. Quality Standards
YTONG blocks are produced and processed according to the national quality standard of Autoclaved Aerated Concrete Building Block (GB/T11968) and YTONG block
enterprise standard (Q/QJCG-07-2002) of Shanghai YTONG Co., Ltd. The enterprise standard is stricter in product precision, strength coecient of variation than the
national standard.

. Performances
With the main production raw materials of fine ground quartz sand, cement, lime, gypsum and the foaming agent of aluminium powder, YTONG block is a kind of light
autoclaved aerated concrete product produced according to the production techniques of German YTONG patents.
YTONG block has the following features:
1. Light density, which is about 1/3 of the d brick and 1/4 of concrete. It can reduce the dead load of the building eectively and lower the total construction cost of the
building.
2. Good heat insulation performance. The coecient of heat conductivity of YTONG block is 0.11~0.16W/m.K, which is only 1/10 of concrete and a kind of good
internal and external heat insulation material.

Contents....................................................... ............................................................................................Page

Contents.........................................................................................................................................................................Page

Formation Description......................................................................................................................S1~S8
Arrangement Description of YTONG Block.........................................................................................S9
Painting and Facing Method Description of YTONG
Block Internal and External Wall.........................................................................................................S10
Plan of Non-loadbearing Block Wall and Related Cutlines..............................................................1
Plan Arrangement of Blocks of External Covering Column of External Wall..............................2
Plan Arrangement of Blocks of External Flat Column of External Wall.......................................3
Plan Arrangement of Block of the Internal Wall..................................................................................4
Arrangement of Vertical Blocks of Non-loadbearing External Wall (Frame Structure External
Flat) (1)..............................................................................................................................................................5
Arrangement of Vertical Blocks of Non-loadbearing External Wall (Wall Type Frame Structure)
(2)........................................................................................................................................................................6
Arrangement of Vertical Blocks of Non-loadbearing External Wall (External Covering Frame
Structure) (3)...................................................................................................................................................7
Arrangement of Vertical Blocks of Non-loadbearing External Wall (External Covering Frame
Structure) (4)...................................................................................................................................................8
Wall Doors and Windows Installation
Structure..........................................................................................................................................................9
Internal Wall Foaming Structure Adhesive Fixed Wood Door Installation
Structure.........................................................................................................................................................10

Installation Structure of External Wall Doors and Windows............................................................................11


Vertical Gap and Horizontal Gap of the Connection of Non-loadbearing Filled
Block Wall and Reinforced Concrete wall column or Beam Panel................................................................12
Structure of Dierent Parts of the Wall...................................................................................................................13
Structure of Expansion Joint......................................................................................................................................14
Production Method of Non-loadbearing Lintel (1)...............................................................................................15
Production Method of Non-loadbearing Lintel (2)...............................................................................................16
Sample of Non-loadbearing Wall Anchoring (1)..................................................................................................17
Sample of Non-loadbearing Wall Anchoring (2)..................................................................................................18
External Covering Anchoring of External Wall.....................................................................................................19
Usage and Features of Supporting Materials of YTONG Block.......................................................................20

3. Good fire-resistant and fire-proof performance. The fire endurance of 150mm thickness YTONG block is longer than 4 hours. YTONG blcok is inorganic
silicate material, which is non-flammable and does not produce poisonous gases.
4. High accuracy, which can guarantee the application of thin layer construction techniques. With good processing performances, it can be cut, sawed, engraved slots.,
etc.
5. The strength grading and density grading shall meet the requirements of the following table. The dry density of YTONG block is 425~625kg/m.

Formation Description

Drawing No.
Page

2012HU J/T--105
05
S1

Contents

Drawing No.
Page

2012HU J/T--105
05

.. Common Specifications and Dimensions of Block

Coecient of Heat Conductivity, Compression Strength and Dry Density of Block

Strength

Density

grading

grading

A2.0

B04

A2.5

A3.5
A5.0

Coecient of heat
conductivity (dry) W/m.
m.K

Cubic compressive strength (MPa)


Average
e value no less than

Monoblock minimum
no less than

2.1

1.7

2.5

2.0

2.7

2.2

3.6

2.8

3.7

3.0

5.1

4.1

0.11

B04
B05

0.13

B05
B06

0.16

B06

The average dry density no greater


than kg/m3
425
525
625

Dry Shrinkage, Freezing Resistance


Common Specifications and Dimensions of Block

Unit: mm

Item
Dimensions

block tongue & groove

blockk flat

Length (L)

600

600

Thickness (B)

150,200,240,250,300
00

50,75,100,120

Height (H)

250

250

Dry shrinka ge
value
Freezing
resistance

Note: YTONG can also produce customized products.

Unit

Standard method
Express method
Quality loss
Strength aer freezing

mm/m

Index
0.50
0.80

0.50

MPa

Greater than 80% of the average value of three -dimensional compression


strength mentioned in the above table

6. Good sound insulation performance. The average sound insulation volume can reach 30~50dB. The weighting sound insulation volume is
48dB of 200mm thickness unpainted wall. The weighting sound insulation volume is 50dB of 240mm thickness double sided painted wall.

Formation Description

Drawing No.
Page

2012HU J/T--105
S3

Formation Description

Drawing No.
Page

2012HU J/T--105
S2

.. Common Specifications and Dimensions of Block

Coecient of Heat Conductivity, Compression Strength and Dry Density of Block

Strength

Density

grading

grading

A2.0

B04

A2.5

A3.5
A5.0

Coecient of heat
conductivity (dry) W/m.
m.K

Cubic compressive strength (MPa)


Average
e value no less than

Monoblock minimum
no less than

2.1

1.7

2.5

2.0

2.7

2.2

3.6

2.8

3.7

3.0

5.1

4.1

0.11

B04
B05

0.13

B05
B06

0.16

B06

The average dry density no greater


than kg/m3
425
525
625

Dry Shrinkage, Freezing Resistance


Common Specifications and Dimensions of Block

Unit: mm

Item
Dimensions

block tongue & groove

blockk flat

Length (L)

600

600

Thickness (B)

150,200,240,250,300
00

50,75,100,120

Height (H)

250

250

Dry shrinka ge
value
Freezing
resistance

Note: YTONG can also produce customized products.

Unit

Standard method
Express method
Quality loss
Strength aer freezing

mm/m

Index
0.50
0.80

0.50

MPa

Greater than 80% of the average value of three -dimensional compression


strength mentioned in the above table

6. Good sound insulation performance. The average sound insulation volume can reach 30~50dB. The weighting sound insulation volume is
48dB of 200mm thickness unpainted wall. The weighting sound insulation volume is 50dB of 240mm thickness double sided painted wall.

Formation Description

Drawing No.
Page

2012HU J/T--105
S3

Formation Description

Drawing No.
Page

2012HU J/T--105
S2

The connection between YTONG block and accessaries (such as door, windows, water heater, wall-attached pipe of range hood, pipe support and sanitary fixture) shall be
reliable and firm.
Bolts and other adapting pieces which are corresponding to the features of YTONG block shall be adopted. When the iron pieces are embedded in or pass through YTONG
blocks, antirust measures shall be made.
2. Facing protective layer shall be made on the outside surface of YTONG block external wall. The facing shall prevent the alaternation of freezing and thawing, circulation of
dry and wet, natural carbonization and wearing. The facing shall be well adhesive to the basic layer without cracks. Flashing and drain shall be made on the concave-convex parts
(such as architrave, appentice, eaves and windowsill, etc.) along the horizontal direction of the external wall of YTONG block to prevent ponding.
3. Facing materials with good breathability shall be adopted for the facing of the internal side of external wall and any side of the internal wall of YTONG block.
4. When YTONG block is used as internal wall and does basic treatment, its surface evenness shall meet related requirements in Quality Acceptance Specifications of Building
Decoration Project (GB50210). If required, wall painting interior facing method can also be adopted (refer to the painting facing method description of YTONG block internal
and external wall).
5. The connection between YTONG block wall and dierent materials shall adopt reliable technical measures during the surface treatment to prevent the wall surface from
cracking, such as pasting alkali-resisting fiber glass mesh (hereinaer referred to as alkali-resisting mesh). The thickness of alkali-resisting mesh is 0.25mm and the mesh size
is 9 units per inch. The width shall be 200mm.
6. The following methods can be adopted during the installation of internal and external doors and windows:
(1) When wood doors and windows (without pocket) are installed on the internal block wall, door and window opening can be reserved on the block wall. When
the wall thickness is 200mm, Fischertechnik nylon expansion bolt can be adopted; when the block thickness is 200mm,
200mm, C15 fine stone concrete block shall be embedded
in both two sides of the door and window opening. The installation method is the same with installing wood doors and windows on common brickwork,. See the picture on Page 9.
(2) Door opening can be le on the brickwork wall when installation special decorative doors and windows with pocket on internal wall. Refer to the construction and installation
method of foaming structure fixed doorframe (97 HU J/T-602HL). See the picture on Page 10.
(3) When installing plastic, aluminium alloy doors and windows on external wall, door and window opening shall be le on the brickwork wall. Aer pre-embedding C15 fine concrete
block, the installation method is the same as installing plastic, aluminium alloy doors and windows on common brickwork. See the picture on Page 11.

.. Scope of Application and Regulations


1. This collective drawing can be applied to non-loadbearing wall built by YTONG block according to thin layer masonry techniques, which can be used in the external wall, internal
wall and infilled wall, etc.
2. YTONG block wall cannot be used in the following parts:
(1) Under building 0.000. (Except non-loadbearing internal wall of the basement)
(2) Parts which are soaked for long term or always suer alternation of dry and wet (The method of bathroom and toilet shall be referred to the picture on Page 13).
(3) Environment etching by chemicals such as strong acid, strong base or high concentration carbon dioxide, etc.
(4) High temperature environment in which block is always above 80.
(5) Parapet wall of the roof.
3. The strength grading of YTONG block shall be above A2.0. YTONG block shall be built by YTONG special adhesive (hereinaer referred to as YTONG adhesive). (See
the appendix)
4. The internal and external wall thickness of YTONG block shall be confirmed according to the technical, economical and building construction requirements, which shall not
be less than the minimum thickness confirmed by heat engineering specifications and building sound insulation requirements in Energy Conservation Design Standards of Civil
Building, Energy Conservation Design Standards of Residential Building in Hot-summer and Cold-winter Areas, Technical Specifications of Energy Conservation Application of
Building Envelope of Residential Building, Heat Engineering Design Specifications of Civil Building and Energy Conservation Design Standards of Public Building. The thickness of
internal wall shall be 100mm and external wall shall be 200mm in Shanghai (when the installation of sound insulation and doors and windows meets the national standards, the
external wall thickness can be 150mm).
5. All the iron materials shall be antirust treated before use.
6. Refer to Technical Specifications of YTONG Building Heat Preservation Project (DBJ/CT018) when YTONG block is used for heat preservation.
7. What is le unmentioned in this collective drawing shall be executed according to the existing national specifications.
8. This collective drawing shall be used together with recommended standard of building products of Shanghai - YTONG Block Construction and Acceptance Specification
(DBJ/CT002).

.. Matters Need Attention in Architectural Design:


1. Waterproof measures shall be made in the partition of the bathroom to prevent the wall suering alternation of wet and dry or damage of freeze thawing.

Formation Description

Drawing No.
Page

2012HU J/T--105
S5

Formation Description

Drawing No.
Page

2012HU J/T--105
S4

The connection between YTONG block and accessaries (such as door, windows, water heater, wall-attached pipe of range hood, pipe support and sanitary fixture) shall be
reliable and firm.
Bolts and other adapting pieces which are corresponding to the features of YTONG block shall be adopted. When the iron pieces are embedded in or pass through YTONG
blocks, antirust measures shall be made.
2. Facing protective layer shall be made on the outside surface of YTONG block external wall. The facing shall prevent the alaternation of freezing and thawing, circulation of
dry and wet, natural carbonization and wearing. The facing shall be well adhesive to the basic layer without cracks. Flashing and drain shall be made on the concave-convex parts
(such as architrave, appentice, eaves and windowsill, etc.) along the horizontal direction of the external wall of YTONG block to prevent ponding.
3. Facing materials with good breathability shall be adopted for the facing of the internal side of external wall and any side of the internal wall of YTONG block.
4. When YTONG block is used as internal wall and does basic treatment, its surface evenness shall meet related requirements in Quality Acceptance Specifications of Building
Decoration Project (GB50210). If required, wall painting interior facing method can also be adopted (refer to the painting facing method description of YTONG block internal
and external wall).
5. The connection between YTONG block wall and dierent materials shall adopt reliable technical measures during the surface treatment to prevent the wall surface from
cracking, such as pasting alkali-resisting fiber glass mesh (hereinaer referred to as alkali-resisting mesh). The thickness of alkali-resisting mesh is 0.25mm and the mesh size
is 9 units per inch. The width shall be 200mm.
6. The following methods can be adopted during the installation of internal and external doors and windows:
(1) When wood doors and windows (without pocket) are installed on the internal block wall, door and window opening can be reserved on the block wall. When
the wall thickness is 200mm, Fischertechnik nylon expansion bolt can be adopted; when the block thickness is 200mm,
200mm, C15 fine stone concrete block shall be embedded
in both two sides of the door and window opening. The installation method is the same with installing wood doors and windows on common brickwork,. See the picture on Page 9.
(2) Door opening can be le on the brickwork wall when installation special decorative doors and windows with pocket on internal wall. Refer to the construction and installation
method of foaming structure fixed doorframe (97 HU J/T-602HL). See the picture on Page 10.
(3) When installing plastic, aluminium alloy doors and windows on external wall, door and window opening shall be le on the brickwork wall. Aer pre-embedding C15 fine concrete
block, the installation method is the same as installing plastic, aluminium alloy doors and windows on common brickwork. See the picture on Page 11.

.. Scope of Application and Regulations


1. This collective drawing can be applied to non-loadbearing wall built by YTONG block according to thin layer masonry techniques, which can be used in the external wall, internal
wall and infilled wall, etc.
2. YTONG block wall cannot be used in the following parts:
(1) Under building 0.000. (Except non-loadbearing internal wall of the basement)
(2) Parts which are soaked for long term or always suer alternation of dry and wet (The method of bathroom and toilet shall be referred to the picture on Page 13).
(3) Environment etching by chemicals such as strong acid, strong base or high concentration carbon dioxide, etc.
(4) High temperature environment in which block is always above 80.
(5) Parapet wall of the roof.
3. The strength grading of YTONG block shall be above A2.0. YTONG block shall be built by YTONG special adhesive (hereinaer referred to as YTONG adhesive). (See
the appendix)
4. The internal and external wall thickness of YTONG block shall be confirmed according to the technical, economical and building construction requirements, which shall not
be less than the minimum thickness confirmed by heat engineering specifications and building sound insulation requirements in Energy Conservation Design Standards of Civil
Building, Energy Conservation Design Standards of Residential Building in Hot-summer and Cold-winter Areas, Technical Specifications of Energy Conservation Application of
Building Envelope of Residential Building, Heat Engineering Design Specifications of Civil Building and Energy Conservation Design Standards of Public Building. The thickness of
internal wall shall be 100mm and external wall shall be 200mm in Shanghai (when the installation of sound insulation and doors and windows meets the national standards, the
external wall thickness can be 150mm).
5. All the iron materials shall be antirust treated before use.
6. Refer to Technical Specifications of YTONG Building Heat Preservation Project (DBJ/CT018) when YTONG block is used for heat preservation.
7. What is le unmentioned in this collective drawing shall be executed according to the existing national specifications.
8. This collective drawing shall be used together with recommended standard of building products of Shanghai - YTONG Block Construction and Acceptance Specification
(DBJ/CT002).

.. Matters Need Attention in Architectural Design:


1. Waterproof measures shall be made in the partition of the bathroom to prevent the wall suering alternation of wet and dry or damage of freeze thawing.

Formation Description

Drawing No.
Page

2012HU J/T--105
S5

Formation Description

Drawing No.
Page

2012HU J/T--105
S4

3. Construction Method of Wall Lintel


(1) The two construction methods of lintel of door and window opening are as follows:
A For opening with the width less than 1000mm, YTONG blocks with the same strength grading shall be cut as the lintel. See the picture on Page 15.
B For opening with the width of 1000~2100mm, YTONG special reinforcement lintel shall be adopted. See the picture on Page 16.
(2) For punching on the block wall, when the opening is 400mm,
400mm, the lintel shall be set according to the requirements of Article (1).
4. Horizontal reinforcing belt shall be set under the windowsill for YTONG internal wall or external wall. See the second picture on Page 13.
5. When YTONG block is used as the external wall material of high-rise, the bending strength and tensile strength of the brickwork shall be check calculated according to the sawtooth
joint failure, straight ling joint failure and continuous seam joint failure of the single project.
6. Proper construction measures shall be adopted on small wall column and cantilever wall to guarantee the stability of the wall.
7. Projects under special wind load shall be in accordance with the design requirements of single project.

Formation Description

Drawing No.
Page

2012HU J/T--105
S7

. Attentions in Structure Design:


1. When confirming the thickness of block, the ratio of height to thickness of the wall shall be calculated according to the following formula:
=Ho/h 1 2 [ ]
In the formula, Ho is the calculated height of the wall, which is from the indoor elevation of the ground floor to the beam or panel bottom, from elevation of the floor to
the height of horizontal fulcrum.
h--is the thickness of block wall.
Note: when the wall height is greater than or equal to the distance S between the adjacent cross wall and pilaster, the ratio of height to thickness shall been check
calculated as Ho=0.6S
1 is the correction factor of allowed ratio of height to thickness of Non-loadbearing wall, which is 1.35.
2 is the correction factor of allowed ratio of height to thickness of opening with doors and windows.
2 = 1-0.4bs/S, when 2 0.7
0.7 2 shall be 0.7.
bs is the width of door and window opening within the range of the wall width S.
S-- is the distance between the adjacent windows or pilaster.
[ ] -- the allowed ratio of height to thickness of YTONG block. When the strength of YTONG adhesive is 5MPa, [] is 24.
Except for the non-punching and slotted wall with the adjacent cross wall distance less than the storey height, YTONG blocks with the thickness greater than 100mm shall be adopted.
As for slotted and hidden pipe embedded wall, the total depth of horizontal slot shall be less than 1/4 of the wall thickness and the depth of vertical slot shall be less than 1/3 of the
wall thickness. Reliable measures shall be taken to allow the horizontal slot depth to be less than 1/3. The slotting method shall be in accordance with the construction and acceptance
specifications of YTONG block. 1:4 cement mortar shall be used to fill in the gap aer slotting. Cross and double faced slotting shall be avoided as far as possible. If necessary, the
distance between two double faced slotting shall be more than 600mm. Water pipes which pass through the wall shall prevent water seepage.
2. Constructional column and ring beam shall be set on the wall according to Design Specification of Brickwork Structure, Design Specification of Building Seismic Resistance. Each
two layers blocks of YTONG block wall adopts L iron piece or 26 rebar to connect with the vertical components of the main structure. When the wall height is greater than 4m and
the length is greater than 5m, the top of the wall shall be connected with the beam bottom or panel bottom by L iron piece; when the length of wall is more than 2 times of the storey
height, reinforced concrete constructional column shall be set; when the wall height is greater than 4m, the wall shall be connected with column at the half height position and
reinforced concrete horizontal reinforcing bars shall be set along the whole wall. See the picture on Page 17~18. The L iron pieces must be antirust treated.

Formation Description

Drawing No.
Page

2012HU J/T--105
S6

3. Construction Method of Wall Lintel


(1) The two construction methods of lintel of door and window opening are as follows:
A For opening with the width less than 1000mm, YTONG blocks with the same strength grading shall be cut as the lintel. See the picture on Page 15.
B For opening with the width of 1000~2100mm, YTONG special reinforcement lintel shall be adopted. See the picture on Page 16.
(2) For punching on the block wall, when the opening is 400mm,
400mm, the lintel shall be set according to the requirements of Article (1).
4. Horizontal reinforcing belt shall be set under the windowsill for YTONG internal wall or external wall. See the second picture on Page 13.
5. When YTONG block is used as the external wall material of high-rise, the bending strength and tensile strength of the brickwork shall be check calculated according to the sawtooth
joint failure, straight ling joint failure and continuous seam joint failure of the single project.
6. Proper construction measures shall be adopted on small wall column and cantilever wall to guarantee the stability of the wall.
7. Projects under special wind load shall be in accordance with the design requirements of single project.

Formation Description

Drawing No.
Page

2012HU J/T--105
S7

. Attentions in Structure Design:


1. When confirming the thickness of block, the ratio of height to thickness of the wall shall be calculated according to the following formula:
=Ho/h 1 2 [ ]
In the formula, Ho is the calculated height of the wall, which is from the indoor elevation of the ground floor to the beam or panel bottom, from elevation of the floor to
the height of horizontal fulcrum.
h--is the thickness of block wall.
Note: when the wall height is greater than or equal to the distance S between the adjacent cross wall and pilaster, the ratio of height to thickness shall been check
calculated as Ho=0.6S
1 is the correction factor of allowed ratio of height to thickness of Non-loadbearing wall, which is 1.35.
2 is the correction factor of allowed ratio of height to thickness of opening with doors and windows.
2 = 1-0.4bs/S, when 2 0.7
0.7 2 shall be 0.7.
bs is the width of door and window opening within the range of the wall width S.
S-- is the distance between the adjacent windows or pilaster.
[ ] -- the allowed ratio of height to thickness of YTONG block. When the strength of YTONG adhesive is 5MPa, [] is 24.
Except for the non-punching and slotted wall with the adjacent cross wall distance less than the storey height, YTONG blocks with the thickness greater than 100mm shall be adopted.
As for slotted and hidden pipe embedded wall, the total depth of horizontal slot shall be less than 1/4 of the wall thickness and the depth of vertical slot shall be less than 1/3 of the
wall thickness. Reliable measures shall be taken to allow the horizontal slot depth to be less than 1/3. The slotting method shall be in accordance with the construction and acceptance
specifications of YTONG block. 1:4 cement mortar shall be used to fill in the gap aer slotting. Cross and double faced slotting shall be avoided as far as possible. If necessary, the
distance between two double faced slotting shall be more than 600mm. Water pipes which pass through the wall shall prevent water seepage.
2. Constructional column and ring beam shall be set on the wall according to Design Specification of Brickwork Structure, Design Specification of Building Seismic Resistance. Each
two layers blocks of YTONG block wall adopts L iron piece or 26 rebar to connect with the vertical components of the main structure. When the wall height is greater than 4m and
the length is greater than 5m, the top of the wall shall be connected with the beam bottom or panel bottom by L iron piece; when the length of wall is more than 2 times of the storey
height, reinforced concrete constructional column shall be set; when the wall height is greater than 4m, the wall shall be connected with column at the half height position and
reinforced concrete horizontal reinforcing bars shall be set along the whole wall. See the picture on Page 17~18. The L iron pieces must be antirust treated.

Formation Description

Drawing No.
Page

2012HU J/T--105
S6

Common Wall and Rendering Dead Load

Arrangement Descriptions of YTONG Blocks


.. The arrangement of blocks shall be designed before the construction for the convenience of burdening and reducing the on-site cutting workload during the construction.

Density grading

.. The basic length of block of arrangement design is 600mm. Customized specifications can be processed and produced aer discussing with the manufacturer or cut on
the construction site.
.. The arrangement of blocks shall be o set joints. The lap joint length shall be no less than 1/3 of the length of over lapped block. The minimum lap joint length shall
be no less than 100mm.

B04

.. Wall between windows with the width less than 600mm (including 600mm) shall be avoided in the arrangement design. When the width is less than or equal to 600mm,
supporting L iron piece shall be used to connect the block and concrete column, or continuous window lintel (ring beam, connecting beam) shall be set to connect with it.
.. Mortar joint dimensions during block arrangement:
The blocks shall be built by YTONG special adhesive. Its common vertical and horizontal mortar joint shall be controlled within 2~3mm.
The thickness of the first piece of block on the structure (floor and beam) shall be10~45mm. 1:3 cement mortar shall be used as toweling course. The bottom of block shall be
built by YTONG adhesive.

Density grading

.. The plane block arrangement of this collective drawing is designed according to the wall between windows of Non-loadbearing system. The elevation arrangement design
adopts two kinds of windowsill height (0.9m, 1m) and two kinds of window height (1.4m, 1.5m). Special conditions can be adjusted according to the practical conditions.
B05

Arrangement Description
of YTONG Block

Drawing No.
Page

2012HU J/T--105
S9

Thickness and rendering

Dead load

Density

KN/m2

grading

Thickness and rendering

Dead load KN/m2

100 thickness

0.56

100 thickness

0.84

150 thickness
ss

0.84

150 thickness

1.26

240 thickness

1.34

240 thickness

2.02

100 thickness+ double faced 5 thickness YTONG plaster

0.73

100 thickness+ double faced 5 thickness YTONG plaster

1.01

150 thickness+ double faced 5 thickness YTONG plaster

1.01

150 thickness+ double faced 5 thickness YTONG plaster

1.43
2.19

B06

240 thickness+ double faced 5 thickness YTONG plaster

1.51

240 thickness+ double faced 5 thickness YTONG plaster

100 thickness + double faced 20 thickness mixed mortar

1.24

1000 thickness + double faced 20 thickness mixed mortar

1.52

150 thickness + double faced 20 thickness mixed mortar

1.52

150 thickness + double faced 20 thickness mixed mortar

1.94

240 thickness + double faced 20 thickness mixed mortar

2.02

240 thickness + double faced 20 thickness mixed mortar

2.70

Thickness and rendering

Dead load KN/m2

100 thickness

0.70

1500 thickness

1.05

240 thickness

1.68

100 thickness+ double faced 5 thickness YTONG plaster

0.87

150 thickness+ double faced 5 thickness YTONG plaster

1.22

240 thickness+ double faced 5 thickness YTONG plaster

1.85

100 thickness + double faced 20 thickness mixed mortar

1.38

150 thickness + double faced 20 thickness mixed mortar

1.73

240 thickness + double faced 20 thickness mixed mortar

2.36

Formation Description

Drawing No.
Page

2012HU J/T--105
S8

Common Wall and Rendering Dead Load

Arrangement Descriptions of YTONG Blocks


.. The arrangement of blocks shall be designed before the construction for the convenience of burdening and reducing the on-site cutting workload during the construction.

Density grading

.. The basic length of block of arrangement design is 600mm. Customized specifications can be processed and produced aer discussing with the manufacturer or cut on
the construction site.
.. The arrangement of blocks shall be o set joints. The lap joint length shall be no less than 1/3 of the length of over lapped block. The minimum lap joint length shall
be no less than 100mm.

B04

.. Wall between windows with the width less than 600mm (including 600mm) shall be avoided in the arrangement design. When the width is less than or equal to 600mm,
supporting L iron piece shall be used to connect the block and concrete column, or continuous window lintel (ring beam, connecting beam) shall be set to connect with it.
.. Mortar joint dimensions during block arrangement:
The blocks shall be built by YTONG special adhesive. Its common vertical and horizontal mortar joint shall be controlled within 2~3mm.
The thickness of the first piece of block on the structure (floor and beam) shall be10~45mm. 1:3 cement mortar shall be used as toweling course. The bottom of block shall be
built by YTONG adhesive.

Density grading

.. The plane block arrangement of this collective drawing is designed according to the wall between windows of Non-loadbearing system. The elevation arrangement design
adopts two kinds of windowsill height (0.9m, 1m) and two kinds of window height (1.4m, 1.5m). Special conditions can be adjusted according to the practical conditions.
B05

Arrangement Description
of YTONG Block

Drawing No.
Page

2012HU J/T--105
S9

Thickness and rendering

Dead load

Density

KN/m2

grading

Thickness and rendering

Dead load KN/m2

100 thickness

0.56

100 thickness

0.84

150 thickness
ss

0.84

150 thickness

1.26

240 thickness

1.34

240 thickness

2.02

100 thickness+ double faced 5 thickness YTONG plaster

0.73

100 thickness+ double faced 5 thickness YTONG plaster

1.01

150 thickness+ double faced 5 thickness YTONG plaster

1.01

150 thickness+ double faced 5 thickness YTONG plaster

1.43
2.19

B06

240 thickness+ double faced 5 thickness YTONG plaster

1.51

240 thickness+ double faced 5 thickness YTONG plaster

100 thickness + double faced 20 thickness mixed mortar

1.24

1000 thickness + double faced 20 thickness mixed mortar

1.52

150 thickness + double faced 20 thickness mixed mortar

1.52

150 thickness + double faced 20 thickness mixed mortar

1.94

240 thickness + double faced 20 thickness mixed mortar

2.02

240 thickness + double faced 20 thickness mixed mortar

2.70

Thickness and rendering

Dead load KN/m2

100 thickness

0.70

1500 thickness

1.05

240 thickness

1.68

100 thickness+ double faced 5 thickness YTONG plaster

0.87

150 thickness+ double faced 5 thickness YTONG plaster

1.22

240 thickness+ double faced 5 thickness YTONG plaster

1.85

100 thickness + double faced 20 thickness mixed mortar

1.38

150 thickness + double faced 20 thickness mixed mortar

1.73

240 thickness + double faced 20 thickness mixed mortar

2.36

Formation Description

Drawing No.
Page

2012HU J/T--105
S8

Rendering and Facing Method Description of YTONG Block Internal and External Wall
.. Internal Wall
1. Basic treatment: YTONG block shall use YTONG special base plaster to make one layer of basic treatment with the thickness of 2~3mm. One layer of finish plaster with the
thickness of 1~2mm. Decoration construction of coating or wall paper facing shall be made aer that. Dull polish panel shall be used to polish the surface before basic treatment.
2. Rendering method:
1) Common mortar: YTONG special interface agent shall be painted on YTONG block wall. Then use 1:1:6 layering power and mixed mortar or 1:3 cement mortar with the total
thickness of less than 15mm. Coating shall be painted or wall paper shall be pasted.
2) Paint gypsum: except in humid environment, YTONG block wall shall use special painting gypsum. When the painting gypsum does not have water-retaining property,
YTONG special interface agent shall be used to treat the wall before painting. The total thickness shall be less than 15mm and greater than 4mm. Coating shall be painted or wall
paper shall be pasted.
3) Tile fixing: Tiles can be fixed directly on YTONG block wall with ceramic adhesive. Tiles can also be fixed on 1:3 cement mortar levelling layer by ceramic adhesive.
.. External Wall
1. Dry wall or decorative wall: Transparent permeability resistant agent or external wall waterproof paint shall be painted on YTONG block wall.
2. Basic treatment method: YTONG special plaster shall be used on YTONG block wall to do basic treatment with the thickness of 5mm. external wall coating shall be painted later.
3. YTONG special interface agent shall be painted on YTONG block wall. Level out the wall with 1:1:6 mixed mortar or 1:3 cement mortar, the total thickness of which shall be
no greater than 20mm. The surface shall paint coating.
4. Hanging board facing: YTONG block wall shall adopt keel dry hanging method, which shall be confirmed by single design.

YTONG

Reinforced concrete

External

External

covering

flat

column

column

PU foaming agent

Sealant

Cement mortar

Note: Places where have special requirements on waterproof or permeability resistance, no matter it is external wall or internal wall, YTONG special waterproof interface agent or
other waterproof or permeability resistant measures shall be adopted.

Foaming
g structure glue

1. See Page 2 for external wall covering column.


2. See Page 3 for external wall is paralleled with column.
3. See Page 3 and 4 for internal wall.

Plan of Non-load
n-loadbearing Block Wall
Plan of Non-loadbearing
Block Wall and Related
Cutlines

Drawing No.
Page

2012HU J/T--105
1

Painting and Facing Method


Description of YTONG Building
Block Internal and External Wall

Drawing No.
Page

2012HU J/T--105
S10

Rendering and Facing Method Description of YTONG Block Internal and External Wall
.. Internal Wall
1. Basic treatment: YTONG block shall use YTONG special base plaster to make one layer of basic treatment with the thickness of 2~3mm. One layer of finish plaster with the
thickness of 1~2mm. Decoration construction of coating or wall paper facing shall be made aer that. Dull polish panel shall be used to polish the surface before basic treatment.
2. Rendering method:
1) Common mortar: YTONG special interface agent shall be painted on YTONG block wall. Then use 1:1:6 layering power and mixed mortar or 1:3 cement mortar with the total
thickness of less than 15mm. Coating shall be painted or wall paper shall be pasted.
2) Paint gypsum: except in humid environment, YTONG block wall shall use special painting gypsum. When the painting gypsum does not have water-retaining property,
YTONG special interface agent shall be used to treat the wall before painting. The total thickness shall be less than 15mm and greater than 4mm. Coating shall be painted or wall
paper shall be pasted.
3) Tile fixing: Tiles can be fixed directly on YTONG block wall with ceramic adhesive. Tiles can also be fixed on 1:3 cement mortar levelling layer by ceramic adhesive.
.. External Wall
1. Dry wall or decorative wall: Transparent permeability resistant agent or external wall waterproof paint shall be painted on YTONG block wall.
2. Basic treatment method: YTONG special plaster shall be used on YTONG block wall to do basic treatment with the thickness of 5mm. external wall coating shall be painted later.
3. YTONG special interface agent shall be painted on YTONG block wall. Level out the wall with 1:1:6 mixed mortar or 1:3 cement mortar, the total thickness of which shall be
no greater than 20mm. The surface shall paint coating.
4. Hanging board facing: YTONG block wall shall adopt keel dry hanging method, which shall be confirmed by single design.

YTONG

Reinforced concrete

External

External

covering

flat

column

column

PU foaming agent

Sealant

Cement mortar

Note: Places where have special requirements on waterproof or permeability resistance, no matter it is external wall or internal wall, YTONG special waterproof interface agent or
other waterproof or permeability resistant measures shall be adopted.

Foaming
g structure glue

1. See Page 2 for external wall covering column.


2. See Page 3 for external wall is paralleled with column.
3. See Page 3 and 4 for internal wall.

Plan of Non-load
n-loadbearing Block Wall
Plan of Non-loadbearing
Block Wall and Related
Cutlines

Drawing No.
Page

2012HU J/T--105
1

Painting and Facing Method


Description of YTONG Building
Block Internal and External Wall

Drawing No.
Page

2012HU J/T--105
S10

600

600

600

Wall under windows

900mm width wall


between windows

500
400
300

150
200
250

600

1200
Wall under windows

600

1200mm width wall


between windows

600

300

500
400
300
500
400
300

200
250
300

200

Wall under windows

600
Lower layer

Corner
Note: 1. See detailed picture for the strengthen connection of building block wall

Wall between windows

and concrete column.

1500mm width wall


between windows

600

Corner

600

200

1500

200
250
300

600

200

600

300

300

Lower layer

1200mm width wall


between windows

500
400
300
500
550
600

Corner

1200

Upper layer

200

200

500
400
300

600

1200

300

Wall between windows

500
550
600

600

Upper layer

Upper layer
Corner
200

600

150
200
250

Lower layer

600

600

350
400
450

900mm width wall


between windows

600

200

200

500
400
300

600
900

Upper layer
500
400
300

350
400
450

300

200

Wall between windows

300
900

200

500
400
300

200

600

200
250
300

500
400
300

500
400
300
900

200

200

200

200
250
300

600

600

300

300

600

600

1500

1500

Upper layer

Lower layer

2. Same as page 4 note 2.

1500mm width wall


between windows
Plan Arrangement of Blocks
of External wall is paralleled
with the column

Drawing No.
Page

2012HU J/T--105
3

Note: See detailed picture for the connection between


block wall and column.

Plan Arrangement of Covering


column Blocks of External
Wall

Drawing No.
Page

2012HU J/T--105
2

600

600

600

Wall under windows

900mm width wall


between windows

500
400
300

150
200
250

600

1200
Wall under windows

600

1200mm width wall


between windows

600

300

500
400
300
500
400
300

200
250
300

200

Wall under windows

600
Lower layer

Corner
Note: 1. See detailed picture for the strengthen connection of building block wall

Wall between windows

and concrete column.

1500mm width wall


between windows

600

Corner

600

200

1500

200
250
300

600

200

600

300

300

Lower layer

1200mm width wall


between windows

500
400
300
500
550
600

Corner

1200

Upper layer

200

200

500
400
300

600

1200

300

Wall between windows

500
550
600

600

Upper layer

Upper layer
Corner
200

600

150
200
250

Lower layer

600

600

350
400
450

900mm width wall


between windows

600

200

200

500
400
300

600
900

Upper layer
500
400
300

350
400
450

300

200

Wall between windows

300
900

200

500
400
300

200

600

200
250
300

500
400
300

500
400
300
900

200

200

200

200
250
300

600

600

300

300

600

600

1500

1500

Upper layer

Lower layer

2. Same as page 4 note 2.

1500mm width wall


between windows
Plan Arrangement of Blocks
of External wall is paralleled
with the column

Drawing No.
Page

2012HU J/T--105
3

Note: See detailed picture for the connection between


block wall and column.

Plan Arrangement of Covering


column Blocks of External
Wall

Drawing No.
Page

2012HU J/T--105
2

Elevation of blocks
(window height 1.5m, windowsill 1m)

600

600

250 100 250


225 150 225
200 200 200

150
200

2
13

600

550
525
500

300

550
525
500

100
150
200
1200

600

600
1200

100
150
200

Upper layer

2-2 profile

Lower layer

600
1500

450

2012HU J/T--105
5

100
150
200

600
Upper layer
250

1500mm width wall


between windows

Elevation of blocks
(window height 1.4m, windowsill 1m)

600

1200mm width wall


between windows
600

Floor
elevation

100
150
200

450

Drawing No.

Cross-intersected

100
150
200

1-1
18
600

1000

300

Page

Lower layer

Upper layer

600
150
200

Precast reinforced concrete


windowsill or other precast
windowsills

1
13

Elevation of Blocks of
Non-loadbearing External Wall
(parallel with structure frame) (1)

400
375
350

Lower layer

Upper layer

1:3 cement mortar


Laying
YTONG adhesive

1-1 profile

100
150
200
900

100
150
200

1:3 cement mortar


Laying
YTONG adhesive

250 100 250


225 150 225
200 200 200

900mm width wall


between windows

200

700

400
375
350

450
900

50

1-1
18

Lower layer

1400

140 100 3 250 3 250 3 250 3 250 3 250 100


10
3 32
26
6

Upper layer

450

2
13

1
13

Floor elevation

100
150
200

Structure beam height


(confirmed by single project

1500
Precast reinforced concrete
windowsill or other precast
windowsills

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 250

700

4
12

1000

26
6

Floor elevation

50

Structure beam height

4
12

(confirmed by single project


3
41 250 3 250 3 250 140 100 3 250 3 250 3 250 3 250 3 250 3 200
10
32

1:3 cement mortar


Laying
YTONG adhesive

450
425
400

100
150
200
1500

450
425
400

Corner

600

Lower layer

250
Note:
1. The above plans are just reference of principles
2. The structural column is designed by single project.

Plan Arrangement of
Block of the Internal Wall

Drawing No.
Page

2012HU J/T--105
4

Elevation of blocks
(window height 1.5m, windowsill 1m)

600

600

250 100 250


225 150 225
200 200 200

150
200

2
13

600

550
525
500

300

550
525
500

100
150
200
1200

600

600
1200

100
150
200

Upper layer

2-2 profile

Lower layer

600
1500

450

2012HU J/T--105
5

100
150
200

600
Upper layer
250

1500mm width wall


between windows

Elevation of blocks
(window height 1.4m, windowsill 1m)

600

1200mm width wall


between windows
600

Floor
elevation

100
150
200

450

Drawing No.

Cross-intersected

100
150
200

1-1
18
600

1000

300

Page

Lower layer

Upper layer

600
150
200

Precast reinforced concrete


windowsill or other precast
windowsills

1
13

Elevation of Blocks of
Non-loadbearing External Wall
(parallel with structure frame) (1)

400
375
350

Lower layer

Upper layer

1:3 cement mortar


Laying
YTONG adhesive

1-1 profile

100
150
200
900

100
150
200

1:3 cement mortar


Laying
YTONG adhesive

250 100 250


225 150 225
200 200 200

900mm width wall


between windows

200

700

400
375
350

450
900

50

1-1
18

Lower layer

1400

140 100 3 250 3 250 3 250 3 250 3 250 100


10
3 32
26
6

Upper layer

450

2
13

1
13

Floor elevation

100
150
200

Structure beam height


(confirmed by single project

1500
Precast reinforced concrete
windowsill or other precast
windowsills

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 250

700

4
12

1000

26
6

Floor elevation

50

Structure beam height

4
12

(confirmed by single project


3
41 250 3 250 3 250 140 100 3 250 3 250 3 250 3 250 3 250 3 200
10
32

1:3 cement mortar


Laying
YTONG adhesive

450
425
400

100
150
200
1500

450
425
400

Corner

600

Lower layer

250
Note:
1. The above plans are just reference of principles
2. The structural column is designed by single project.

Plan Arrangement of
Block of the Internal Wall

Drawing No.
Page

2012HU J/T--105
4

1-1profile
Elevation of blocks
(storey height 2.8m, window height 1.5m, windowsill 0.9m)

700

1:3 cement mortar


Laying
YTONG adhesive

26
6

Elevation of Blocks of Non-loadbearing


External Wall (external covering
the structure frame) (3)

Drawing No.

Page

Structure beam height


(confirmed by single project

1400

1500
Floor
elevation

Elevation of blocks
(window height 1.5m, windowsill 0.9m)

1-1
18
Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

2
3-3profile

2012HU J/T--105
7

700

2
13

1:3 cement mortar


Laying
YTONG adhesive

2-2profile
Elevation of blocks
(storey height 2.8m, window height 1.4m, windowsill 0.9m)

1-1
18

26
6

Precast reinforced concrete


windowsill or other precast
windowsills

900

Floor
elevation

2
13

Floor elevation

50

1-1
18

Precast reinforced concrete


windowsill or other precast
windowsills

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 200 3 9010100 3 250 3 250 3 250 3 200 3 200 3 200 32

2
13

4
12

900

1400

Precast reinforced concrete


windowsill or other precast
windowsills

Floor elevation

50

Floor
elevation

4
12

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 200 90 100 3 250 3 250 3 250 3 250 3 250 3 200
32
3 10

700

1:3 cement mortar


Laying
YTONG adhesive

1000

900
50

100 28 250 3 250 3 250

26
6

1-1
18

50

2
13

1:3 cement mortar


Laying
YTONG adhesive

2800

Precast reinforced concrete


windowsill or other precast
windowsills

100 28 250 3 250 3 250 3 250 3 10100 3 250 3 250 3 250 3 250 3 250 100 100 28 250 3
150
3 32

4
12

1500

200 100 100 3 250 3 250 3 250 3 250 3 250 3 200 32100 28 250 3
3 10

1:3 cement mortar


Laying
YTONG adhesive

2800
26
6

700

Floor
elevation

Floor elevation

4
12

Structure beam height


(confirmed by single project

Elevation of blocks
(window height 1.4m, windowsill 0.9m)

Elevation of Blocks of
Non-loadbearing External Wall
(parallel with structure frame) (2)

4-4profile

Drawing No.
Page

2012HU J/T--105
6

1-1profile
Elevation of blocks
(storey height 2.8m, window height 1.5m, windowsill 0.9m)

700

1:3 cement mortar


Laying
YTONG adhesive

26
6

Elevation of Blocks of Non-loadbearing


External Wall (external covering
the structure frame) (3)

Drawing No.

Page

Structure beam height


(confirmed by single project

1400

1500
Floor
elevation

Elevation of blocks
(window height 1.5m, windowsill 0.9m)

1-1
18
Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

2
3-3profile

2012HU J/T--105
7

700

2
13

1:3 cement mortar


Laying
YTONG adhesive

2-2profile
Elevation of blocks
(storey height 2.8m, window height 1.4m, windowsill 0.9m)

1-1
18

26
6

Precast reinforced concrete


windowsill or other precast
windowsills

900

Floor
elevation

2
13

Floor elevation

50

1-1
18

Precast reinforced concrete


windowsill or other precast
windowsills

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 200 3 9010100 3 250 3 250 3 250 3 200 3 200 3 200 32

2
13

4
12

900

1400

Precast reinforced concrete


windowsill or other precast
windowsills

Floor elevation

50

Floor
elevation

4
12

1:3 cement mortar


Laying
YTONG adhesive

41 250 3 250 3 200 90 100 3 250 3 250 3 250 3 250 3 250 3 200
32
3 10

700

1:3 cement mortar


Laying
YTONG adhesive

1000

900
50

100 28 250 3 250 3 250

26
6

1-1
18

50

2
13

1:3 cement mortar


Laying
YTONG adhesive

2800

Precast reinforced concrete


windowsill or other precast
windowsills

100 28 250 3 250 3 250 3 250 3 10100 3 250 3 250 3 250 3 250 3 250 100 100 28 250 3
150
3 32

4
12

1500

200 100 100 3 250 3 250 3 250 3 250 3 250 3 200 32100 28 250 3
3 10

1:3 cement mortar


Laying
YTONG adhesive

2800
26
6

700

Floor
elevation

Floor elevation

4
12

Structure beam height


(confirmed by single project

Elevation of blocks
(window height 1.4m, windowsill 0.9m)

Elevation of Blocks of
Non-loadbearing External Wall
(parallel with structure frame) (2)

4-4profile

Drawing No.
Page

2012HU J/T--105
6

200xHxh Fine stone concrete precast block


15~20
PU foaming joint filling

200xHxh Fine stone concrete precast block


PU foaming joint filling
Expansion bolt

700

100-200

100-200

50

Expansion bolt

M6 expansion bolt

plastic door frame application


1-1<200mm thickness wall with wood door
(with rendering)

1-1<200mm thickness wall with wood door


(only plastering)

Doors and Windows


Installation details

Notes:
1. The above details can also be applied to the
installation of wood window.
2. H is the height of YTONG block. h is the thickness of
YTONG block.

Drawing No.
Page

2012HU J/T--105
9

700

10

3
26
6

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

1400

1500
2
13
1-1
18

2
13
1-1
18

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

2
2-2profile

1-1profile
Elevation of blocks
(storey height 3.0m, window height 1.5m, windowsill 1m)

Precast reinforced concrete


windowsill or other precast
windowsills

1000

26
6

Steel plate

1:3 cement mortar


Laying
YTONG adhesive

50

200xHxh Fine stone


concrete precast block

Precast reinforced concrete


windowsill or other precast
windowsills

100 35 250 3 250 3 250 3 250 3 250 3 90 100

Elevation of concrete block pre-embedding on door

4
11

1000

3000

1:3 cement mortar


Laying
YTONG adhesive

50

100

200

4
11

250 3 250 3 250 3 250 3 250 3 100 35100 35 250 3

200Hh
C15
15 fine stone concrete precast block shall
be no less than 3 blocks on each side,
which shall be connected with the
block wall by YTONG adhesive.

PU foaming agent
10 20 wood brick
1020

wood door on or above 200mm thickness wall

Floor
elevation

Floor
elevation

100 38 250 3 250 3 250 3 250 3 240 10100 3 250 3 250 3 250 3 250 3 250 3 200 32100 38 250

10

Lintel

100

Alkali-resisting mesh
Basic treatment facing
Rendering facing

Fischertechnik nylon anchor bolt


S10RT100 frame nylon anchor
bolt (each 500 mid-range)

Elevation of blocks
(storey height 3.0m, window height 1.4m, windowsill 1m)

Elevation of Blocks of Non-loadbearing


External Wall (external covering
the structure frame) (4)

Drawing No.
Page

2012HU J/T--105
8

200xHxh Fine stone concrete precast block


15~20
PU foaming joint filling

200xHxh Fine stone concrete precast block


PU foaming joint filling
Expansion bolt

700

100-200

100-200

50

Expansion bolt

M6 expansion bolt

plastic door frame application


1-1<200mm thickness wall with wood door
(with rendering)

1-1<200mm thickness wall with wood door


(only plastering)

Doors and Windows


Installation details

Notes:
1. The above details can also be applied to the
installation of wood window.
2. H is the height of YTONG block. h is the thickness of
YTONG block.

Drawing No.
Page

2012HU J/T--105
9

700

10

3
26
6

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

1400

1500
2
13
1-1
18

2
13
1-1
18

Floor
elevation

1:3 cement mortar


Laying
YTONG adhesive

2
2-2profile

1-1profile
Elevation of blocks
(storey height 3.0m, window height 1.5m, windowsill 1m)

Precast reinforced concrete


windowsill or other precast
windowsills

1000

26
6

Steel plate

1:3 cement mortar


Laying
YTONG adhesive

50

200xHxh Fine stone


concrete precast block

Precast reinforced concrete


windowsill or other precast
windowsills

100 35 250 3 250 3 250 3 250 3 250 3 90 100

Elevation of concrete block pre-embedding on door

4
11

1000

3000

1:3 cement mortar


Laying
YTONG adhesive

50

100

200

4
11

250 3 250 3 250 3 250 3 250 3 100 35100 35 250 3

200Hh
C15
15 fine stone concrete precast block shall
be no less than 3 blocks on each side,
which shall be connected with the
block wall by YTONG adhesive.

PU foaming agent
10 20 wood brick
1020

wood door on or above 200mm thickness wall

Floor
elevation

Floor
elevation

100 38 250 3 250 3 250 3 250 3 240 10100 3 250 3 250 3 250 3 250 3 250 3 200 32100 38 250

10

Lintel

100

Alkali-resisting mesh
Basic treatment facing
Rendering facing

Fischertechnik nylon anchor bolt


S10RT100 frame nylon anchor
bolt (each 500 mid-range)

Elevation of blocks
(storey height 3.0m, window height 1.4m, windowsill 1m)

Elevation of Blocks of Non-loadbearing


External Wall (external covering
the structure frame) (4)

Drawing No.
Page

2012HU J/T--105
8

50
10

2400

15 185 500

500

500 185 15

500

Lintel for YTONG block

200xHxh

Foaming structure glue

The distance @ between iron feet of doors and


windows is 500. The edge is 200 or in
accordance with the standard drawing.

35x32

Foaming structure glue

Fill PU foaming

Fischertechnik S8R80 frame nylon anchor bolt

Door and
window frame

35x32

15

200xHxh
C15 fine stone concrete
precast block

Elevation of window

Lintel for YTONG block

Construction
sealant

Fill PU foaming

Foaming structure glue


120

Fischertechnik S8R80 frame nylon anchor bolt


Reinforced concrete ring beam or lintel

50

YTONG block wall

50

Panel thickness
1.5mm

Iron feet of
doors and
windows

50

585

200

15

200 485

1500

C15 fine stone concrete precast block shall be no


less than 3 blocks on each side, which shall be
connected with the block wall with
YTONG adhesive.

YTONG block wall

65
10

Fischertechnik S8R80 frame nylon anchor bolt

35x32

2
15
20

Construction sealant

35x32

1-1

Iron feet of doors and windows

2-2

Foaming structure glue


65

3
Notes:
1. The connection of doorframe and wall can also be in accordance with the same method.
2. H is the height of YTONG block. h is the thickness of YTONG block

Installation details of External


Wall Doors and Windows

Drawing No.
Page

2012HU J/T--105
11

2
Notes:
1. The wood door installation details selects 97HU J/T-602 HL Collective
Drawing of Decorative Wood Door.
2. YTONG block internal wall can adopt foaming structure glue to fix
the wood door frame and structure.
3. The structure of door leaf has two types, which are T type and and groove
and tongue type and ,, which will be confirmed by single project.

Internal Wall Foaming Structure glue


Fixed Wood Door

Drawing No.
Page

2012HU J/T--105
10

50
10

2400

15 185 500

500

500 185 15

500

Lintel for YTONG block

200xHxh

Foaming structure glue

The distance @ between iron feet of doors and


windows is 500. The edge is 200 or in
accordance with the standard drawing.

35x32

Foaming structure glue

Fill PU foaming

Fischertechnik S8R80 frame nylon anchor bolt

Door and
window frame

35x32

15

200xHxh
C15 fine stone concrete
precast block

Elevation of window

Lintel for YTONG block

Construction
sealant

Fill PU foaming

Foaming structure glue


120

Fischertechnik S8R80 frame nylon anchor bolt


Reinforced concrete ring beam or lintel

50

YTONG block wall

50

Panel thickness
1.5mm

Iron feet of
doors and
windows

50

585

200

15

200 485

1500

C15 fine stone concrete precast block shall be no


less than 3 blocks on each side, which shall be
connected with the block wall with
YTONG adhesive.

YTONG block wall

65
10

Fischertechnik S8R80 frame nylon anchor bolt

35x32

2
15
20

Construction sealant

35x32

1-1

Iron feet of doors and windows

2-2

Foaming structure glue


65

3
Notes:
1. The connection of doorframe and wall can also be in accordance with the same method.
2. H is the height of YTONG block. h is the thickness of YTONG block

Installation details of External


Wall Doors and Windows

Drawing No.
Page

2012HU J/T--105
11

2
Notes:
1. The wood door installation details selects 97HU J/T-602 HL Collective
Drawing of Decorative Wood Door.
2. YTONG block internal wall can adopt foaming structure glue to fix
the wood door frame and structure.
3. The structure of door leaf has two types, which are T type and and groove
and tongue type and ,, which will be confirmed by single project.

Internal Wall Foaming Structure glue


Fixed Wood Door

Drawing No.
Page

2012HU J/T--105
10

40~50
YTONG block wall
Waterproofing agent
Ceramic brick adhesive
Facing surface by single project design

Skirting board material by single


project design
C 20 pure concrete temporary wall

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

40~50
Balcony floor

Isolation interface aget(middle part),


interface agent(both sides)
Elastic putty
So putty

YTONG adhesive (3mm) or


PU foaming (10mm-15mm)

Bathroom

Balcony

(internal)

Reinforced concrete
column or wall

10

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
2~3mm thickness concrete bonding agent

Waterproofing agent can adopt: 1. YTONG special waterproofing interface agent


2. permeability resistant agent

15~20mm thickness basic layer priming


Facing project (confirmed by single project)

Details of Dierent
Parts of the Wall

Drawing No.
Page

2012HU J/T--105
13

10~15

15~25

Chute treatment
(only for rendering)

YTONG special plaster


Basic layer priming
Facing project (confirmed by single project)

YTONG block outer wall


PE stick
PU foaming
Outer elastic putty (external)

Vertical joint (external wall)

YTONG block internal wall


Chute treatment
(only for rendering)

Horizontal joint (internal wall)

(external)

Reinforced
concrete beam or
panel

Storey floor

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

45

Bathroom and moist room floor

Isolation interface aget(middle part),


interface agent(both sides)
Elastic putty
So putty

Vertical joint (internal wall)

45

200

C 20 pure concrete temporary wall

Windowsill

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster
(or rendering)

40~50

YTONG block wall


Waterproofing agent
Ceramic brick adhesive
Facing surface by single project design

Skirting board material by single


project design

15~20mm thickness basic layer priming


(slick with the block face)

PE stick in the middle and PU foaming agent on both sides


200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
Chute treatment (map with 1 nodes)
YTONG special plaster (or rendering)

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

PE stick
PU foaming
Outer elastic putty
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
2~3mm thickness concrete bonding agent
15~20mm thickness basic layer priming
Facing project (confirmed by single project)

10~25

Wall footing

200

1-1
18

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
(slick with the block face)
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster
(or rendering)

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)
PE stick
Isolation interface aget(middle part),
PU foaming
interface agent(both sides)
Chute treatment
Elastic putty
(only for rendering)
So putty

2~3mm thickness concrete interface agent

40~50

10mm thickness M7.5 cement mortar, lay YTONG adhesive on the


surface under the windowsill

50~70

40~50

Precast reinforced concrete windowsill, or


refer to single project design for other
precast windowsills

45

Indoor ground

45

Construction
sealant

15~20

Window board by single project design

40~50

45

Skirting board material


(single project design)

5%

Storey floor

YTONG block internal wall


YTONG adhesive

reinforced concrete or wall

1:3 cement mortar bedding cushion


200mm width alkali-resisting mesh (or
(or 200mm width steel wire gauze piece)
2~3mm thickness concrete interface agent
Facing project (confirmed by single project)

Outdoor ground

45

YTONG block external wall

Paint YTONG adhesive on the bottom of the block and bed mortar
1:3 cement mortar bedding cushion
Floor (baseboard)

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

15~20
45
50~70

40~50

2~3mm thickness concrete interface agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
Reinforced
Chute treatment (only for painting facing)
concrete beam or
YTONG special plaster
panel

40~50

(internal)
Isolation interface aget(middle part),
interface agent(both sides)
Elastic putty
So putty

Chute treatment
(only for rendering)

Horizontal joint (external wall )

YTONG block outer wall


200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

Notes: 1. Refer to other pictures for the connection of vertical and horizontal joints and rebar or L iron piece.
2. The connection with other walls can adopt M5 mortar.
3. YTONG special interface agent shall be used in rendering of YTONG wall.

Vertical Joint and Horizontal Joint of


the Connection of Non-loadbearing
Filled Block Wall and Reinforced
Concrete wall column or Beam Panel

Drawing No.
Page

2012HU J/T--105
12

40~50
YTONG block wall
Waterproofing agent
Ceramic brick adhesive
Facing surface by single project design

Skirting board material by single


project design
C 20 pure concrete temporary wall

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

40~50
Balcony floor

Isolation interface aget(middle part),


interface agent(both sides)
Elastic putty
So putty

YTONG adhesive (3mm) or


PU foaming (10mm-15mm)

Bathroom

Balcony

(internal)

Reinforced concrete
column or wall

10

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
2~3mm thickness concrete bonding agent

Waterproofing agent can adopt: 1. YTONG special waterproofing interface agent


2. permeability resistant agent

15~20mm thickness basic layer priming


Facing project (confirmed by single project)

Details of Dierent
Parts of the Wall

Drawing No.
Page

2012HU J/T--105
13

10~15

15~25

Chute treatment
(only for rendering)

YTONG special plaster


Basic layer priming
Facing project (confirmed by single project)

YTONG block outer wall


PE stick
PU foaming
Outer elastic putty (external)

Vertical joint (external wall)

YTONG block internal wall


Chute treatment
(only for rendering)

Horizontal joint (internal wall)

(external)

Reinforced
concrete beam or
panel

Storey floor

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

45

Bathroom and moist room floor

Isolation interface aget(middle part),


interface agent(both sides)
Elastic putty
So putty

Vertical joint (internal wall)

45

200

C 20 pure concrete temporary wall

Windowsill

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster
(or rendering)

40~50

YTONG block wall


Waterproofing agent
Ceramic brick adhesive
Facing surface by single project design

Skirting board material by single


project design

15~20mm thickness basic layer priming


(slick with the block face)

PE stick in the middle and PU foaming agent on both sides


200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
Chute treatment (map with 1 nodes)
YTONG special plaster (or rendering)

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

PE stick
PU foaming
Outer elastic putty
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
2~3mm thickness concrete bonding agent
15~20mm thickness basic layer priming
Facing project (confirmed by single project)

10~25

Wall footing

200

1-1
18

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
(slick with the block face)
200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster
(or rendering)

200mm width alkali-resisting mesh


(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)
PE stick
Isolation interface aget(middle part),
PU foaming
interface agent(both sides)
Chute treatment
Elastic putty
(only for rendering)
So putty

2~3mm thickness concrete interface agent

40~50

10mm thickness M7.5 cement mortar, lay YTONG adhesive on the


surface under the windowsill

50~70

40~50

Precast reinforced concrete windowsill, or


refer to single project design for other
precast windowsills

45

Indoor ground

45

Construction
sealant

15~20

Window board by single project design

40~50

45

Skirting board material


(single project design)

5%

Storey floor

YTONG block internal wall


YTONG adhesive

reinforced concrete or wall

1:3 cement mortar bedding cushion


200mm width alkali-resisting mesh (or
(or 200mm width steel wire gauze piece)
2~3mm thickness concrete interface agent
Facing project (confirmed by single project)

Outdoor ground

45

YTONG block external wall

Paint YTONG adhesive on the bottom of the block and bed mortar
1:3 cement mortar bedding cushion
Floor (baseboard)

2~3mm thickness concrete bonding agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

15~20
45
50~70

40~50

2~3mm thickness concrete interface agent


15~20mm thickness basic layer priming
200mm width alkali-resisting mesh (or 200mm width steel wire gauze piece)
Reinforced
Chute treatment (only for painting facing)
concrete beam or
YTONG special plaster
panel

40~50

(internal)
Isolation interface aget(middle part),
interface agent(both sides)
Elastic putty
So putty

Chute treatment
(only for rendering)

Horizontal joint (external wall )

YTONG block outer wall


200mm width alkali-resisting mesh
(or 200mm width steel wire gauze piece)
YTONG special plaster (or rendering)

Notes: 1. Refer to other pictures for the connection of vertical and horizontal joints and rebar or L iron piece.
2. The connection with other walls can adopt M5 mortar.
3. YTONG special interface agent shall be used in rendering of YTONG wall.

Vertical Joint and Horizontal Joint of


the Connection of Non-loadbearing
Filled Block Wall and Reinforced
Concrete wall column or Beam Panel

Drawing No.
Page

2012HU J/T--105
12

150

Connection of
pre-embedded part

1
Reinforced
concrete
component

L=400~1000

or downward

Connection of expansion bolt

(when the wall thickness is 150mm,


150mm, L iron piece
can be fixed on the concrete component by nail)

Fischertechnik
S6R35@250

150

4@300
28

150

20 b-40 20

400~900

400~900

L=400~1000

250

100~200

Note:
1. The lintel in the picture is cut from block.
2. The method of iron (1) (2) can refer to Page 17. The pre-embedded part can refer to single design.
3. The slotting of pre-embedded rebar can be finished on the ground. The rabbet can face the upward
during production. When the mortar strength reaches 100%, it can be installed.

Asphalt hemp
thread

b Width of block

Page

Punch slot hole on galvanized


iron (bore diameter cooperates
with the bolt)

S6R35@250

2012HU J/T--105
15

24# galvanized
iron
Nail

Iron piece sample

L style wall (outdoors)


Asphalt hemp
thread

Fischertechnik bolt S-H-R series


@400

Flat wall (indoors)

M10 cement mortar

Drawing No.

100

Nail
100 width galvanized
wire netting

1-1

Production Method of
Non-loadbearing Lintel (1)

Nail
100mm width galvanized
wire netting

80(150<b<200)

300

250

15

250
150

50(b150)

300
150

24# galvanized
iron

Set one iron piece each <500


height

Flat wall (outdoors)

Plaster

250

100

100

Fix the iron plate on the concrete


component by expansion bolt 8

Iron piece (1) (2)

40

A
L50 5 welded in the embedding
L505
piece, the welding line is 5mm
L=wall width-10mm

Asphalt hemp thread or confirmed by


single project

nail

L=400~800

40 30

40

Fix the iron panel on the concrete component


by expansion bolt 8.

250

150

100

300
150

40 30

40

Height of
block

Asphalt hemp
thread
Set one iron piece each <500
30 40
height

80

250

L50 5 welded in the embedding piece, the welding


L50
line is 5mm
L=wall width-10mm

Notes:
1. a is the width of deformation joint, which is confirmed by single project.
2. One layer of antirusting paint shall be brushed on both sides of galvanized iron. Two layers of flat
paint shall be painted on exposed surface. The material and color of the paint shall be confirmed
by the designer.
3. Two layers of antirusting paint shall be brushed on the surface of iron piece, which shall be
knocked in the building block when building YTONG blocks.
4. The connection of iron sheet and iron piece can adopt electric drill and screw the bolt.
5. Other decoration methods of the internal wall shall be confirmed by single project.
6. Fixed piece can adopt Fischertechnik S-H-R series bolt or other bolts whose tensile, shear
resisting and pull resisting performances meet the requirements of national detection units.

Plaster
Fischertechnik bolt S-H-R series
@400
Plaster

L style wall (indoors)

Details of Expansion
Joint

Drawing No.
Page

2012HU J/T--105
14

150

Connection of
pre-embedded part

1
Reinforced
concrete
component

L=400~1000

or downward

Connection of expansion bolt

(when the wall thickness is 150mm,


150mm, L iron piece
can be fixed on the concrete component by nail)

Fischertechnik
S6R35@250

150

4@300
28

150

20 b-40 20

400~900

400~900

L=400~1000

250

100~200

Note:
1. The lintel in the picture is cut from block.
2. The method of iron (1) (2) can refer to Page 17. The pre-embedded part can refer to single design.
3. The slotting of pre-embedded rebar can be finished on the ground. The rabbet can face the upward
during production. When the mortar strength reaches 100%, it can be installed.

Asphalt hemp
thread

b Width of block

Page

Punch slot hole on galvanized


iron (bore diameter cooperates
with the bolt)

S6R35@250

2012HU J/T--105
15

24# galvanized
iron
Nail

Iron piece sample

L style wall (outdoors)


Asphalt hemp
thread

Fischertechnik bolt S-H-R series


@400

Flat wall (indoors)

M10 cement mortar

Drawing No.

100

Nail
100 width galvanized
wire netting

1-1

Production Method of
Non-loadbearing Lintel (1)

Nail
100mm width galvanized
wire netting

80(150<b<200)

300

250

15

250
150

50(b150)

300
150

24# galvanized
iron

Set one iron piece each <500


height

Flat wall (outdoors)

Plaster

250

100

100

Fix the iron plate on the concrete


component by expansion bolt 8

Iron piece (1) (2)

40

A
L50 5 welded in the embedding
L505
piece, the welding line is 5mm
L=wall width-10mm

Asphalt hemp thread or confirmed by


single project

nail

L=400~800

40 30

40

Fix the iron panel on the concrete component


by expansion bolt 8.

250

150

100

300
150

40 30

40

Height of
block

Asphalt hemp
thread
Set one iron piece each <500
30 40
height

80

250

L50 5 welded in the embedding piece, the welding


L50
line is 5mm
L=wall width-10mm

Notes:
1. a is the width of deformation joint, which is confirmed by single project.
2. One layer of antirusting paint shall be brushed on both sides of galvanized iron. Two layers of flat
paint shall be painted on exposed surface. The material and color of the paint shall be confirmed
by the designer.
3. Two layers of antirusting paint shall be brushed on the surface of iron piece, which shall be
knocked in the building block when building YTONG blocks.
4. The connection of iron sheet and iron piece can adopt electric drill and screw the bolt.
5. Other decoration methods of the internal wall shall be confirmed by single project.
6. Fixed piece can adopt Fischertechnik S-H-R series bolt or other bolts whose tensile, shear
resisting and pull resisting performances meet the requirements of national detection units.

Plaster
Fischertechnik bolt S-H-R series
@400
Plaster

L style wall (indoors)

Details of Expansion
Joint

Drawing No.
Page

2012HU J/T--105
14

Concrete component

25

b,Width of wall
25

Expansion bolt M8 or nail

Mortar joint
elevation-15
50

h4000

50

25 25

Concrete component

Space no greater
than 2 layers

Iron
piece

L iron
uses on

Detail drawing of
connecting rebar

30~50

700

20

26
6 wall connecting
rebar (welded with
iron piece)

L iron piece
connection
(welded with iron piece)

b-40

1000~2100

20

Selection table of lintel


Selection table of linSelection table of lintel

A
#
1

No.

Selection table of L iron piece


Name
1 #

L(mm)

A(mm)

B(mm)

h(mm)

100

40

15

1.0

Used on block with the


120
thickness 120

2 #

125

60

50

1.5

Used on block with the


thickness of 150

1.5

Used on block with


the thickness 200

3 #

>500

50(b150)
80(150<b200)

15

b,Width of block
YTONG adhesive

300

YTONG lintel B

1000~2100

1000~2100

The infilled wall is beside the


concrete column (wall)

L style iron piece

1-1

Iron nail 2 inch

300

YTONG lintel A

700

40
A
# #
2 3

Concrete component
Expansion bolt
M8 or nail

300

20

M10 cement
mortar

4@300
4@300
26
6 wall connecting
rebar (welded with iron piece)

Concrete
column

Wall space line

b-40

Iron piece (2)

20

6
The span shall be no longer than 2 layers

block wall connecting rebar


Note:
When the quake-proof intensity is 6o and 7o, the length of
connecting rebar l is 700 and L/5. When the quake-proof
intensity is 8o and 9o, full length connecting rebar shall be set.

(75) 50 50 (75)
h

L5000
b,Width of block

Iron piece (2)

Expansion bolt M8 or
nail
50 100 50
200

Mortar joint
elevation-15

The infilled wall is in the middle of


the concrete column (wall).

700

Iron piece (1)

Wall space line

b+100

30
20 20

Space no greater
than 2 layers

1.2

50

Iron piece (1)

6
The span shall be no greater than 2 layers

50 50
100

Concrete column

150

80

63

Remarks

Section dimension width heightmm


mm

Remarks

YGL-1A

240 200/250
240

Applicable to wall width=240mm

YGL-2A

200 200/250

Applicable to wall width=200mm

YGL-3A

150 200/250

Applicable to wall width=150mm

YGL-4A

100 200/250

Applicable to wall width=100mm

Notes:
1. Protective layer is 20mm. L is the width of door and window.
2. Please consult the manufacture for special specifications.

YTONG lintel A

300

15

Reinforced concrete component

1000~2100

Notes: 1. The iron panel adopts A3.


2. The height of weld joint is 4mm.
3. L iron pieces and other exposed iron pieces shall be antirust treated.

Sample of Non-loadbearing
Wall Anchoring (1)

Drawing No.
Page

2012HU J/T--105
17

Production Method of
Non-loadbearing Lintel (2)

Drawing No.
Page

2012HU J/T--105
16

Concrete component

25

b,Width of wall
25

Expansion bolt M8 or nail

Mortar joint
elevation-15
50

h4000

50

25 25

Concrete component

Space no greater
than 2 layers

Iron
piece

L iron
uses on

Detail drawing of
connecting rebar

30~50

700

20

26
6 wall connecting
rebar (welded with
iron piece)

L iron piece
connection
(welded with iron piece)

b-40

1000~2100

20

Selection table of lintel


Selection table of linSelection table of lintel

A
#
1

No.

Selection table of L iron piece


Name
1 #

L(mm)

A(mm)

B(mm)

h(mm)

100

40

15

1.0

Used on block with the


120
thickness 120

2 #

125

60

50

1.5

Used on block with the


thickness of 150

1.5

Used on block with


the thickness 200

3 #

>500

50(b150)
80(150<b200)

15

b,Width of block
YTONG adhesive

300

YTONG lintel B

1000~2100

1000~2100

The infilled wall is beside the


concrete column (wall)

L style iron piece

1-1

Iron nail 2 inch

300

YTONG lintel A

700

40
A
# #
2 3

Concrete component
Expansion bolt
M8 or nail

300

20

M10 cement
mortar

4@300
4@300
26
6 wall connecting
rebar (welded with iron piece)

Concrete
column

Wall space line

b-40

Iron piece (2)

20

6
The span shall be no longer than 2 layers

block wall connecting rebar


Note:
When the quake-proof intensity is 6o and 7o, the length of
connecting rebar l is 700 and L/5. When the quake-proof
intensity is 8o and 9o, full length connecting rebar shall be set.

(75) 50 50 (75)
h

L5000
b,Width of block

Iron piece (2)

Expansion bolt M8 or
nail
50 100 50
200

Mortar joint
elevation-15

The infilled wall is in the middle of


the concrete column (wall).

700

Iron piece (1)

Wall space line

b+100

30
20 20

Space no greater
than 2 layers

1.2

50

Iron piece (1)

6
The span shall be no greater than 2 layers

50 50
100

Concrete column

150

80

63

Remarks

Section dimension width heightmm


mm

Remarks

YGL-1A

240 200/250
240

Applicable to wall width=240mm

YGL-2A

200 200/250

Applicable to wall width=200mm

YGL-3A

150 200/250

Applicable to wall width=150mm

YGL-4A

100 200/250

Applicable to wall width=100mm

Notes:
1. Protective layer is 20mm. L is the width of door and window.
2. Please consult the manufacture for special specifications.

YTONG lintel A

300

15

Reinforced concrete component

1000~2100

Notes: 1. The iron panel adopts A3.


2. The height of weld joint is 4mm.
3. L iron pieces and other exposed iron pieces shall be antirust treated.

Sample of Non-loadbearing
Wall Anchoring (1)

Drawing No.
Page

2012HU J/T--105
17

Production Method of
Non-loadbearing Lintel (2)

Drawing No.
Page

2012HU J/T--105
16

Concrete component

Refer to Page 17 for L iron

L iron piece

Upper layer

600

L iron piece

200

200

L iron piece

300

1200mm width wall between windows

600
1200

The infilled wall is in the middle of


the concrete column (wall)

Wall space line

L 5000 (according to single project design)


b,Width of block
20 b-40 20

300
1

Lower layer

200

600

Lower layer

200

200

600

600

300

300

600

1500

1500

Lower layer

Iron piece

Drawing No.
Page

2012HU J/T--105
19

50

26 wall connecting
26
rebar (welded with iron piece)

Iron nail 2 inch

External Covering
Anchoring of External Wall

Expansion bolt M8 or nail

Concrete component

600

Upper layer

1500mm width wall between windows

Notes:
1. This picture can be applied to reinforced concrete column.
2. L iron is arranged on the top of block.
3. L iron can be fixed on the reinforced concrete component by nail.
4. Refer to Page 17 Selection Table of L Iron for specifications of L iron.

3
16

25

Expansion bolt M8 or nail

25

Elevation of mortar
joint-15

30~50

L iron piece

b,Width of block
25

4@300
26
6
YTONG adhesive

L iron piece

Wall top connection and mortar rebar belt

M10 cement mortar

Refer to detailed drawing


for mortar rebar

The infilled wall is beside


the concrete column (wall)

Concrete component

600

600
1200
Upper layer

Corner

Wall space line

b+100

50

25

Elevation of mortar
joint-15

700

Expansion bolt M8 or nail

(75) 50 50 (75)

Iron piece(3)

8
The interval is no greater
than 2 layers

50

900mm width wall between windows

600

( according to single project design


design

900
Lower layer

50 50
100

900
Upper layer

L iron piece

600

80

300

15

300

1200

Iron piece (4)

200

600

600

200

200

600
Iron piece (3)

50 100
200

L iron piece

( according to single project design


design

Concrete column

h4000
4000 (according to single project design)

Concrete
component

700

Iron piece (4)

1-1
Notes:
1. When the length of wall is >5000 and the height is >4000, slot and set
mortar rebar belt on 1/2 height of the wall (no greater than 2500).
Connection piece shall be set on the top of the wall.
2. The production method of A shall refer to Page 15.

Sample of Non-loadbearing
Wall Anchoring (2)

Drawing No.
Page

2012HU J/T--105
18

Concrete component

Refer to Page 17 for L iron

L iron piece

Upper layer

600

L iron piece

200

200

L iron piece

300

1200mm width wall between windows

600
1200

The infilled wall is in the middle of


the concrete column (wall)

Wall space line

L 5000 (according to single project design)


b,Width of block
20 b-40 20

300
1

Lower layer

200

600

Lower layer

200

200

600

600

300

300

600

1500

1500

Lower layer

Iron piece

Drawing No.
Page

2012HU J/T--105
19

50

26 wall connecting
26
rebar (welded with iron piece)

Iron nail 2 inch

External Covering
Anchoring of External Wall

Expansion bolt M8 or nail

Concrete component

600

Upper layer

1500mm width wall between windows

Notes:
1. This picture can be applied to reinforced concrete column.
2. L iron is arranged on the top of block.
3. L iron can be fixed on the reinforced concrete component by nail.
4. Refer to Page 17 Selection Table of L Iron for specifications of L iron.

3
16

25

Expansion bolt M8 or nail

25

Elevation of mortar
joint-15

30~50

L iron piece

b,Width of block
25

4@300
26
6
YTONG adhesive

L iron piece

Wall top connection and mortar rebar belt

M10 cement mortar

Refer to detailed drawing


for mortar rebar

The infilled wall is beside


the concrete column (wall)

Concrete component

600

600
1200
Upper layer

Corner

Wall space line

b+100

50

25

Elevation of mortar
joint-15

700

Expansion bolt M8 or nail

(75) 50 50 (75)

Iron piece(3)

8
The interval is no greater
than 2 layers

50

900mm width wall between windows

600

( according to single project design


design

900
Lower layer

50 50
100

900
Upper layer

L iron piece

600

80

300

15

300

1200

Iron piece (4)

200

600

600

200

200

600
Iron piece (3)

50 100
200

L iron piece

( according to single project design


design

Concrete column

h4000
4000 (according to single project design)

Concrete
component

700

Iron piece (4)

1-1
Notes:
1. When the length of wall is >5000 and the height is >4000, slot and set
mortar rebar belt on 1/2 height of the wall (no greater than 2500).
Connection piece shall be set on the top of the wall.
2. The production method of A shall refer to Page 15.

Sample of Non-loadbearing
Wall Anchoring (2)

Drawing No.
Page

2012HU J/T--105
18

Usage and Features of Supporting Materials of YTONG Block


Usage and Features of Supporting Materials of YTONG Block
Special adhesive for YTONG block: YQZ-111
YQZ-111112
112
It can be used in the adhesion with YTONG block, which has good matching and cohesive property with YTONG products.
YTONG special base plaster: YQZ-121
YQZ-121122
122
It can be used in the basic treatment of the surface of YTONG block and panel and wall, which has good cohesive property with the basic layer and can prevent cracks.
YTONG special finish plaster : YQZ-131
YQZ-131132
132
It is always used with YTONG special base plaster to decorate and polish the external surface. The surface can also do coating treatment.
YTONG special interface agent: YQZ-151
It can be used in basic layer treatment on the cement foundation of YTONG block and panel wall. It can close the surface pore, enhance the adhesion between the
foundation and painting material, prevent cracking.
YTONG special waterproofing interface agent: YQZ-152
As the interface agent, it also has waterproofing property, which can be applied to external wall painting and internal wall painting requiring waterproofing.
YTONG special repair mortar: YQZ-140
Repair mortar with similar performances of YTONG block and panel, which can be used in the repairs of edges and internal wall gap.
YTONG special painting gypsum (bottom): YQZ-161
It can be applied to the surface treatment of YTONG block and panel internal wall and internal side wall of the external wall, which can be basic treated or painted.
It has features such as quick condensation and hardening, firm adhesion with YTONG block and panel, expansive in water, little shrinking in later stage and good
water retention.
YTONG special painting gypsum (surface): YQZ-162
It is always used with YTONG special painting gypsum (bottom), which can be basic treated or painted. It has features such as quick condensation and hardening, firm
adhesion with YTONG block and panel, expansive in water, little shrinking in later stage and good water retention.

Usage and Features of


Supporting Materials of
YTONG Block

Drawing No.
Page

2012HU J/T--105
20