Professional Documents
Culture Documents
Amca 210
Amca 210
ANSI/ASHRAE 51-07
Laboratory Methods of Testing
Fans for Certified Aerodynamic
Performance Rating
An American National Standard
Approved by ANSI on August 17, 2007
2008 by the Air Movement and Control Association International, Inc. and
the American Society of Heating, Refrigerating, and Air Conditioning Engineers
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Foreword
This edition of AMCA 210/ASHRAE 51 is the eleventh revision, spanning over eighty years of improvements in its
test methods. The major changes reflected in this revision are:
-Added requirements for checking effectiveness of the airflow settling means (Annex A)
-Added methods for testing chamber leakage (Annex B)
-Introduced usage of a Star type straightener
-Refined the conversion from in. wg to Pa, which necessitated small but important changes in the constants
used in I-P equations
Authority
ANSI/AMCA 210 - ANSI/ASHRAE 51 was approved by the membership of the Air Movement and Control
Association on July 28, 2006 and by ASHRAE on March 17, 2008. It was approved by ANSI and became an
American National Standard on August 17, 2007.
Steve Adamski
Revcor, Inc.
Peter Biermayer
Z. Patrick Chinoda
Ceilcote APC.
Waddell, Inc.
Peter G. Danos
Rad Ganesh
Paul R. Heitzmann
Richard Hext
Smiths-Aerospace
Gale Hoyer
IAP, Inc.
Vasanthi Iyer
Tim Mathson
Allen Ray
Michael Renken
J. Greg Sanchez
J. Thomas Sobieski
Retired
Mark Stevens
AMCA International
Dick Williamson
AMCA International
Disclaimer
AMCA International and ASHRAE use their best efforts to produce standards for the benefit of the industry and the
public in light of available information and accepted industry practices. However, AMCA International and ASHRAE
do not guarantee, certify or assure the safety of performance of any products, components or systems tested,
designed, installed or operated in accordance with this standard or that any tests conducted under this standard
will be non-hazardous or free from risk.
TABLE OF CONTENTS
1.
2.
Normative References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
3.
4.
5.
6.
7.
Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.1 Calibration correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.2 Density and viscosity of air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.3 Fan airflow rate at test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
7.4 Fan velocity pressure at test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Annex A.
Annex D.
2. Normative References
The following standards contain provisions that,
through specific reference in this text, constitute
provisions of this American National Standard. At the
time of publication, the editions indicated were valid.
All standards are subject to revision, and parties to
agreements based on this American National
Standard are encouraged to investigate the
possibility of applying the most recent editions of the
standards listed below.
IEEE 112-96 Standard Test Procedure for Polyphase
Induction Motors and Generators, The Institute of
Electrical and Electronic Engineers, 445 Hoes Lane,
Piscataway, NJ 08855-1331, U.S.A. (AMCA #1149)
3. Definitions/Units of Measure/Symbols
3.1 Definitions
3.1.1 Fan. A device that uses a power-driven rotating
impeller to move air or gas. The internal energy
increase imparted by a fan to air or a gas is limited to
25 kJ/kg (10.75 Btu/lbm). This limit is approximately
equivalent to a pressure of 30 kPa (120 in. wg).
(AMCA 99-0066)
absolute
4. Instruments
Measurement
and
Methods
of
DESCRIPTION
SI
A
C
D
Dh
e
E
F
f
H
Ho
Kp
L
Le
Lx,x
l
ln
M
N
n
Ps
Psx
Pt
Ptx
Pv
Pvx
pb
pe
pp
Q
Qx
R
Re
T
td
ts
tw
V
W
x
Y
y
z
s
t
ft2
m2
dimensionless
m
ft
m
ft
dimensionless
dimensionless
N
lbf
dimensionless
W
hp
W
hp
dimensionless
m
ft
m
ft
m
ft
m
in.
----m
ft
rpm
dimensionless
Pa
in. wg
Pa
in. wg
Pa
in. wg
Pa
in. wg
Pa
in. wg
Pa
in. wg
Pa
in. Hg
Pa
in. Hg
Pa
in. Hg
m3/s
cfm, ft3/min
3
m /s
cfm, ft3/min
J/kgK
ftlb/lbmR
dimensionless
Nm
lbfin.
C
F
C
F
C
F
m/s
ft/min, fpm
W
W
dimensionless
dimensionless
mm
in.
dimensionless
dimensionless
dimensionless
dimensionless
Pa
in. wg
per unit
per unit
per unit
Pas
lbm/fts
Kg/m3
lbm/ft3
3
Kg/m
lbm/ft3
IP
Description
c
r
x
0
1
2
3
4
5
6
7
8
Converted value
Reading
Plane 0,1,2 as appropriate
Plane 0 (general test area)
Plane 1 (fan inlet)
Plane 2 (fan outlet)
Plane 3 (Pitot traverse station)
Plane 4 (duct piezometer station)
Plane 5 (nozzle inlet station in chamber)
Plane 6 (nozzle discharge station)
Plane 7 (outlet chamber measurement station)
Plane 8 (inlet chamber measurement station)
4.2 Pressure
The total pressure at a point shall be measured on an
indicator such as a manometer with one leg open to
atmosphere and the other leg connected to a total
pressure sensor, such as the total pressure tube or
the impact tap of a Pitot-static tube.
The static pressure at a point shall be measured on
an indicator such as a manometer with one leg
connected to atmosphere and the other leg
connected to a static pressure sensor, such as a
static pressure tap or the static tap of a Pitot-static
tube.
The velocity pressure at a point shall be measured on
an indicator such as a manometer with one leg open
to a total pressure sensor, such as the impact tap of
a Pitot-static tube, and the other leg connected to a
static pressure sensor such as the static tap of the
same Pitot-static tube.
The differential pressure between two points shall be
measured on an indicator, such as a manometer, with
one leg connected to the upstream sensor, such as a
static pressure tap, and the other leg connected to
the downstream sensor, such as a static pressure tap.
5
5.2 Duct
A duct may be incorporated in a laboratory test setup
to provide a measurement plane or to simulate the
conditions the fan is expected to encounter in
service, or both. Dimension D3 or D4 in the test setup
figures are the inside diameter of a circular crosssection duct or equivalent diameter of a rectangular
cross-section duct with inside traverse dimensions a
and b, where:
D = 4ab /
5.2.1 Long Ducts
5.2.1.1 Airflow measurement duct. A duct with a
measurement plane for airflow determination shall be
straight and have a uniform circular cross-section. A
Pitot traverse duct shall be at least 10 diameters long
with the traverse plane located between 8.5 and 8.75
diameters from the upstream end. Such a duct may
serve as an inlet duct or an outlet duct as well as to
provide a measurement plane. A duct connected to
the upstream side of a flow nozzle shall be between
6.5 and 6.75 diameters long when used only to
provide a measurement plane or between 9.5 and
9.75 diameters long when used as an outlet duct as
well.
5.2.1.2 Pressure measurement duct. A duct with a
plane for pressure measurement shall be straight and
may have either a uniform circular or rectangular
cross-section. An outlet duct with a Piezometer ring
shall be at least 10 diameters long with the
Piezometer plane located between 8.5 and 8.75
diameters from the upstream end.
5.3 Chamber
A chamber may be incorporated in a laboratory test
setup to provide a measurement station or to
simulate the conditions the fan is expected to
encounter in service, or both. The chamber may have
either a circular or rectangular cross-sectional shape.
The dimension M in the test setup diagram is the
inside diameter of a circular chamber or the
equivalent diameter of dimensions a and b, where:
Eq. 6.3
7. Calculations
7.1 Calibration correction
Calibration correction, when required, shall be
applied to individual readings before averaging or
other calculations. Calibration correction need not be
made if the correction is smaller than one-half the
maximum allowable uncertainty, as specified in
Section 4.
Eq. 7.1 SI
t t
pp = pe pb d0 w0
1500
Eq. 7.2 SI
t t
pp = pe pb d0 w0
2700
0 =
0 =
pb 0.378 pp
R(t d0 + 273.15)
70.73( pb 0.378 pp )
R(t d0 + 459.67)
Eq. 7.3 SI
Parameter
pb
Rotational Speed
Static Pressure
Pv3r
Ps3r
Ps4
Ps5
Ps7
Total Pressure
Temperature
12 13 14 15 16
Setup Figure
7A 7B 8A 8B 9A 9B 9C 10A 10B 10C 11
x
x
Pt8
td0
tw0
td2
td3
td4
x
x
td5
tdx + 273.15 pb
t + 459.67 Psx + 13.595 pb
x = 0 d0
t dx + 459.67 13.595 pb
Eq. 7.4 SI
pb t s1 + 273.15
P + 13.595 pb t d0 + 459.67
= 0 t1
13.595 pb t s1 + 459.67
x
x
x
x
td8
Nozzle Pressure Drop
= (17.23 + 0.048t d ) 10 6
Eq. 7.6 SI
= (11.00 + 0.018t d ) 10 6
2Pv3
3
V3 = 1097.8
Eq. 7.7
V3 =
5.2014P
= 1
x R [t dx + 459.67]
Eq. 7.8 SI
Pv3
3
D6
Dx
Eq. 7.13
Eq. 7.9
2 1 ( 1) / 1 4
Y =
4 2 Eq. 7.14
1
1 1
Q3 = V3 A3
Q = Q3 3
Eq. 7.10
Ps6 + pb
Psx + pb
Ps6 + 13.595 pb
Psx + 13.595 pb
Eq. 7.11 SI
14
Eq. 7.15
n
E=
3
(Pvr 0.5 )
Eq. 7.16
Or:
P
= 1
x R [t dx + 273.15]
Eq. 7.12 SI
Re =
D6V6 6
Eq. 7.17 SI
Re =
D6V6 6
60
Re =
P x
2
CD6Y
1 E 4
Eq. 7.18 SI
Re =
P x
1097
CD6Y
60
1 E 4
Re Re
For : L / D = 0.6
Q5 = Y
2P
(CA6 )
5
Q5 = 1097.8Y
P
(CA6 )
5
Eq. 7.22 SI
Eq. 7.19
Q = Qx x
6.688 131.5
C = 0.9986
+
Re Re
For : L / D = 0.5
P
1097.8CA6Y
Q4 =
1 E 4
Eq. 7.20
Eq. 7.23
CA6Y
Q4 =
1 E 4
Eq. 7.24
15
Eq. 7.25
Q
V2 = 2
A2
Eq. 7.26
2V22
2
Eq. 7.27 SI
V2
Pv = 2
1097.8
Or:
2
Q 1
Pv =
A2 2 2
Eq. 7.28 SI
Q
1
Pv =
1097.8 A2 2
Ps3r
n
Eq. 7.30
Pv4 =
4V4 2
2
V4
Pv4 = 4
1097.8
Eq. 7.31 SI
2ab
a+b
Eq. 7.32
DhV
Eq. 7.33 SI
Re =
DhV
60
Eq. 7.29
Q
V4 =
A4 4
And:
Pv =
0.14
Re0.17
Eq. 7.34
Eq. 7.35
Pt2 = Pv2 = Pv
Eq. 7.41
s = 0.95Re-0.12
Eq. 7.42
Eq. 7.36
The value of Pv shall be as determined in Section 7.4.
Eq. 7.38
Eq. 7.39
Eq. 7.40
Eq. 7.43
Eq. 7.44
17
2TN
60
H=
2TN
33, 000 12
Eq. 7.51 SI
Eq. 7.46
Eq. 7.47
W
745.7
H=
Eq. 7.52 SI
Eq. 7.48
Ps = Pt Pv
Eq. 7.49
H=
2 FIN
60
2 FIN
33, 000 12
6343.3
Pt
Pt1 + pb
x=
Pt
Pt1 + 13.595 pb
Eq. 7.54 SI
Eq. 7.50 SI
And:
Eq. 7.50 I-P
18
QPt K p
Eq. 7.53 SI
H
1 Q
z=
Pt1 + pb
Eq. 7.55 SI
P
pb
13
.
595
+
t1
And:
ln (1 + x )
z
Kp =
ln (1 + z )
Eq. 7.56
t =
QPt K p
H
Eq. 7.57 SI
t =
QPt K p
6343.3H
P
s = t s
Pt
Eq. 7.58
Kp
K
pc
2
N K
Ptc = Pt c c p
N K pc
Eq. 7.59
Eq. 7.60
N
Pvc = Pv c c
N
Eq. 7.61
Eq. 7.62
19
tc = t
Eq. 7.63
Eq. 7.64
And:
P
sc = tc sc
Ptc
Eq. 7.65
20
8D
16D
0.8D
0.5D Radius
0.4D
D
3D Radius
90 0.1
SECTION A-A
Static Pressure
Total Pressure
Notes:
1. Surface finish shall be 0.8 micrometer (32 micro-in.) or better. The static orifices may not exceed 1 mm (0.04
in.) diameter. The minimum pitot tube stem diameter recognized under this standard shall be 2.5 mm (0.10 in.)
in no case shall the stem diameter exceed 1/30 of the test duct diameter.
2. Head shall be free from nicks and burrs
3. All dimensions shall be within 2%.
4.
Section A-A shows 8 holes equally spaced and free from burrs. Hole diameter shall be 0.13D, but not
exceeding 1 mm (0.04 in.) hole depth diameter.
Pitot-static tube with spherical head
X/D
0
0.237
0.336
0.474
0.622
0.741
0.936
1.025
1.134
1.228
1.313
1.39
1.442
1.506
1.538
1.57
8D
0.2D
V
Alternate pitot-static tube with ellipsoidal head
V/D
0.5
0.496
0.494
0.487
0.477
0.468
0.449
0.436
0.42
0.404
0.388
0.371
0.357
0.343
0.333
0.323
2.5D min.
2D min.
To Pressure Indicator
X/D
1.602
1.657
1.698
1.73
1.762
1.796
1.83
1.858
1.875
1.888
1.9
1.91
1.918
1.92
1.921
V/D
0.314
0.295
0.279
0.266
0.25
0.231
0.211
0.192
0.176
0.163
0.147
0.131
0.118
0.109
0.1
0.5D min.
8D min.
mm
in. min.
0.184D
0.117D
0.021D
60 1
0.345D
Notes:
1. D is the average of four measurements at traverse plane at 45 angles measured to accuracy of 0.2% D.
2. Traverse duct shall be round within 0.5% D at traverse plane and for a distance of 0.5D on either side of
traverse plane.
3. All pitot positions 0.005D or 4 mm (0.125 in.) whichever is greater.
Figure 3 Traverse Points in a Round Duct
23
+0.00D
-0.03D
+0.00D
D -0.03D
L
0.25D
0.667D
0.667D
Fairing radius
about 0.05D
if necessary
Fairing radius
about 0.05D
if necessary
Notes:
1. The nozzle shall have a cross-section consisting of elliptical and cylindrical portions, as shown. The cylindrical
portion is defined as the nozzle throat.
2. The cross-section of the elliptical portion is one quarter of an ellipse, having the large axis D and the small axis
0.667D. A three-radii approximation to the elliptical form that does not differ at any point in the normal direction
more than 1.5% from the elliptical form shall be used. The adjacent arcs, as well as the last arc, shall smoothly
meet and blend with the nozzle throat. The recommended approximation which meets these requirements is
shown in Figure 4B by Cermak, J., Memorandum Report to AMCA 210/ASHRAE 51P Committee, June 16,
1992.
3. The nozzle throat dimension L shall be either 0.6D +/- 0.005D (recommended), or 0.5D +/- 0.005D.
4. The nozzle throat shall be measured (to an accuracy of 0.001D) at the minor axis of the ellipse and the nozzle
exit. At each place, four diameters, approximately 45 apart, must be within +/-0.002D of the mean. At the
entrance of the throat the mean may be 0.002D greater, but no less than, the mean of the nozzle exit.
5. The nozzle surface in the direction of flow from the nozzle inlet towards the nozzle exit shall fair smoothly so
that a straight-edge may be rocked over the surface without clicking. The macro-pattern of the surface shall not
exceed 0.001D, peak-to-peak. The edge of the nozzle exit shall be square, sharp, and free of burrs, nicks or
roundings.
6. In a chamber, the use of either of the nozzle types shown above is permitted. A nozzle with throat taps shall
be used when the discharge is direct into a duct, and the nozzle outlet should be flanged.
7. A nozzle with throat taps shall have four such taps conforming to Figure 2A, located 90 +/- 2 apart. All four
taps shall be connected to a piezometer ring.
Figure 4A - Nozzles
24
D
All radii are to
this surface
1.449D
0.667D
0.850D
0.450D
34.2
34.4
21.4
7.5 max.
SECTION A-A
(CONVERGING SECTION)
3.5 max.
SECTION B-B
(DIVERGING SECTION)
DUCT
0.45D
D
y
y
0.075D
0.075D
Notes:
1. All dimensions shall be within 0.005D except y, which shall not exceed 0.005D
2. Cell sides shall be flat and straight. Where y > 3 mm (0.125 in.), the leading edge of each segment shall have
a chamfer of 1.3 mm (0.05 in.) per side. The method of joining cell segments (such as tack welds) shall be kept
to the minimum required for mechanical integrity and shall result in minimum protusion into the fluid stream.
Figure 6A - Flow Straightener - Cell Type
45
2D
The star straightener will be constructed of eight radial blades of length equal to 2D4 (with a 1% tolerance) and of
thickness not greater than 0.007D4. The blades will be arranged to be equidistant on the circumference with the
angular deviation being no greater than 5 between adjacent plates.
Figure 6B - Flow Straightener - Star Type
26
Cell
Straightener
Transition
Piece
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on the outlet indicate a diffuser cone which may be used to approach more nearly free delivery.
Pv3r
Pv3 =
n
*V3 = 2
Pv3
3
Q3 = V3 A3
Q = Q3 3
Ps3 =
Ps3r
n
A
Pv = Pv3 3 3
A2 2
Pt1 = 0
L
L
Pt2 = Ps3 + Pv3 + f 2,3 + e Pv3
Dh3 Dh3
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both SI and the I-P systems except for V3; in the I-P version, the
constant
Figure 7A - Outlet Duct Setup - Pitot Traverse in Outlet Duct with Cell Straightener
27
Star
Straightener
Transition
Piece
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on the outlet indicate a diffuser cone which may be used to approach more nearly free delivery.
Pv3r
Pv3 =
n
*V3 = 2
Pv3
3
Q3 = V3 A3
Q = Q3 3
Ps3 =
Ps3r
n
A
Pv = Pv3 3 3
A2 2
Pt1 = 0
L
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and I-P systems except for V3; in the I-P version, the
constant
Figure 7B - Outlet Duct Setup - Pitot Traverse in Outlet Duct with Star Straightener
28
Cell
Straightener
Transition
Piece
D6 Max. = 0.53D4
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. This figure may terminate at Plane 6 and interchangeable nozzles may be employed. In this case P = Ps4.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. Nozzle shall be in accordance with Figure 4A nozzle with throat taps.
1 E
P
4
4
Q = Q4 4
V4 =
A
Pv = Pv4 4 4
A2 2
Pt1 = 0
L
L
Pt2 = Ps4 + Pv4 + f 2,4 + e Pv4
D
D
h4
h4
Q4
A4
2
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q4 and Pv4; in the I-P version,
the constant
Figure 8A - Outlet Duct Setup - Nozzle on End of Outlet Duct with Cell Straightener
29
Transition
Piece
D6 Max. = 0.53D4
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. This figure may terminate at Plane 6 and interchangeable nozzles may be employed. In this case P = Ps4.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. Nozzle shall be in accordance with Figure 4A nozzle with throat taps.
P
4
1 E 4
Q = Q4 4
V4 =
A
Pv = Pv4 4 4
A2 2
Pt1 = 0
L
Q4
A4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q4 and Pv4; in the I-P version,
the constant
Figure 8B - Outlet Duct Setup - Nozzle on End of Outlet Duct with Star Straightener
30
Cell
Straightener
Transition Piece
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size including elbows may be used to connect between the chamber and the exit
of the 10D minimum test duct.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. Minimum M is determined by the requirements of Section 5.3.1 for this figure.
5. Nozzle shall be in accordance with Figure 4A nozzle with throat taps.
*Q5 = 2CA6Y
P
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
L
L
Pt2 = Ps4 + Pv4 + f 2,4 + e Pv4
D
D
h4
h4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size including elbows may be used to connect between the chamber and the exit
of the 11.5D minimum test duct.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. Minimum M is determined by the requirements of Section 5.3.1 for this figure.
5. Nozzle shall be in accordance with Figure 4A nozzle with throat taps.
*Q5 = 2CA6Y
P
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
32
Common
Part
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size including elbows may be used to connect between the chamber and the exit
of the test duct shown between the test fan and the chamber.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. Minimum M is determined by the requirements of Section 5.3.1 for this figure.
5. Nozzle shall be in accordance with Figure 4A - Nozzle with Throat Taps
P
*Q5 = 2CA6Y
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
Cell
Straightener
Transition Piece
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size, including elbows, may be used to connect between the chamber and the exit
of the 10D minimum test duct.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of
2.5 throat diameters of the largest nozzle.
5. Minimum M is determined by the requirements of Section 5.3.1 for this figure.
P
(CA6 )
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
L
L
Pt2 = Ps4 + Pv4 + f 2,4 + e Pv4
Dh4 Dh4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
Figure 10A - Outlet Duct Setup - Multiple Nozzles In Chamber with Cell Straightener
34
Transition
Piece
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size, including elbows, may be used to connect between the chamber and the exit
of the 11.5D minimum test duct.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of
2.5 throat diameters of the largest nozzle.
5. Minimum M is determined by the requirements Section of 5.3.1 for this figure.
P
(CA6 )
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
0.12
Pt2 = Ps4 + Pv4 + f 2,4 2 Pv4 + 0.95 (Re )
Pv4
D
h4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
Figure 10B - Outlet Duct Setup - Multiple Nozzles In Chamber with Star Straightener
35
Common Part
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Additional ductwork of any size including elbows may be used to connect between the chamber and the exit
of the test duct shown between the test fan and the chamber.
3. Variable exhaust system may be an auxiliary fan or a throttling device.
4. The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of
2.5 throat diameters of the largest nozzle.
5. Minimum M is determined by the requirements of Section 5.3.1 for this figure.
* Q5 = 2Y
P
(CA6 )
5
A
Pv = Pv4 4 4
A2 4
Q = Q5 5
Pt1 = 0
Q
V4 =
A4 4
V
* Pv4 = 4 4
2
Pt = Pt2 Pt1
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv4; in the I-P version,
the constant
36
min.
min.
mm
in.
mm
in.
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on fan outlet indicate a uniform duct 2 to 3 equivalent diameters long and of an area within 1%
of the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
3. The fan may be tested without outlet duct in which case it shall be mounted on the end of the chamber.
4. Variable exhaust system may be an auxiliary fan or a throttling device.
5. Dimension J shall be at least 1.0 times the fan equivalent discharge diameter for fans with axis of rotation
perpendicular to the discharge flow and at least 2.0 times the fan equivalent discharge diameter for fans with
axis of rotation parallel to the discharge flow. Warning! A small dimension J may make it difficult to meet the
criteria given in Annex A. By making dimension J at least 0.35M this condition is improved, as well as meeting
the criteria given in Section 5.3.1 for any fan.
6. Temperature td2 may be considered equal to td5.
7. For the purpose of calculating the density at Plane 5 only, Ps5 may be considered equal to Ps7.
8. Nozzle shall be in accordance with Figure 4A - Nozzle with Throat Taps
V
*Pv2 = 2 2
2
Pt2 = Ps7 + Pv
Q = Q5 5
Pv = Pv2
Pt = Pt2 Pt1
Q
V2 =
A2 2
Pt1 = 0
*Q5 = 2CA6Y
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv2; in the I-P version,
the constant
min.
mm
in.
mm
in.
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on fan outlet indicate a uniform duct 2 to 3 equivalent diameters long and of an area within 1%
of the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
3. The fan may be tested without outlet duct in which case it shall be mounted on the end of the chamber.
4. Variable exhaust system may be an auxiliary fan or a throttling device.
5. The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of
2.5 throat diameters of the largest nozzle.
6. Dimension J shall be at least 1.0 times the fan equivalent discharge diameter for fans with axis of rotation
perpendicular to the discharge flow and at least 2.0 tmes the fan equivalent discharge diameter for fans with
axis of rotation parallel to the discharge flow. Warning! A small dimension J may make it difficult to meet the
criteria given in Annex A. By making dimension J at least 0.35M this condition is improved, as well as meeting
the criteria given in section 5.3.1 for any fan.
7. Temperature td2 may be considered equal to td5.
8. For the purpose of calculating the density at Plane 5 only, Ps5 may be considered equal to Ps7.
FLOW AND PRESSURE FORMULAE
2
P
* Q5 = 2Y
(CA6 )
V2
*
P
=
5
v2
2
2
Q = Q5 5
Pv = Pv2
Q
V2 =
A2 2
Pt2 = Ps7 + Pv
Pt = Pt2 Pt1
Ps = Pt Pv
Pt1 = 0
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv2; in the I-P version,
the constant
38
min.
min.
min.
min.
min.
Transition
Piece
Cell
Straightener
min.
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on fan outlet indicate a uniform duct 2 or 3 equivalent diameters long and of an area within 1 of
the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
3. Additional ductwork of any size including elbows may be used to connect between the chamber and the exit
of the 10D minimum test duct.
4. Variable supply system may be an auxiliary fan or a throttling device.
5. In lieu of a total pressure tube, a piezometer ring can be used to measure static pressure at plane 8. If this
alternate arrangement is used, and the calculated plane 8 velocity is greater than 400 fpm then the calculated
plane 8 velocity pressure shall be added to the measured static pressure.
FLOW AND PRESSURE FORMULAE
Pv3r
Pv3 =
n
*V3 = 2
Pv3
3
A
Pv = Pv3 3 3
A2 2
Pt1 = Pt8
Q3 = V3 A3
Pt2 = Pv
Q = Q3 3
Pt = Pt2 Pt1
Ps3 =
Ps3r
n
Ps = Pt Pv
*The formulae given above are the same in both SI and I-P systems except for V3; in the I-P version, the constant
2 is replaced with the value 1097.8.
Figure 13 - Inlet Chamber Setup-Pitot Traverse in Duct
39
min.
min.
min.
min.
min.
Transition
Piece
min.
Cell
Straightener
min.
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on fan outlet indicate a uniform duct 2 to 3 equivalent diameters long and of an area within 1%
of the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
3. Duct length 7D4 may be shortened to not less than 2D4 when it can be demonstrated, by a traverse of D4 by
Pitot-static tube located a distance D4 upstream from the nozzle entrance or downstream from the straightener
or smoothing means, that the energy ratio E is less than 1.1 when the velocity is greater than 6.1 m/s (1200
fpm). Smoothing means such as screens, perforated plates, or other media may be used.
4. Variable supply system may be an auxiliary fan or a throttling device. One or more supply systems, each with
its own nozzle, may be used.
5. In lieu of a total pressure tube, a piezometer ring can be used to measure static pressure at plane 8. If this
alternate arrangement is used, and the calculated plane 8 velocity is greater than 400 fpm then the calculated
plane 8 velocity pressure shall be added to the measured static pressure.
6. Nozzle shall be in accordance with Figure 4A - Nozzle with Throat Taps
P
4
1 E 4
Q = Q4 4
Q
V2 =
A2 2
V
*PV2 = 2 2
2
Pt2 = Pv
PV = PV2
Pt = Pt2 Pt1
Pt1 = Pt8
Ps = Pt Pv
*The formulae given above are the same in both SI and I-P systems except for Q4 and Pv2; in the I-P version, the
constant
40
mm
in.
min.
mm
in.
min.
min.
min.
min.
min.
Notes:
1. Dotted lines on fan inlet indicate an inlet bell and one equivalent duct diameter which may be used for inlet duct
simulation. The duct friction shall not be considered.
2. Dotted lines on fan outlet indicate a uniform duct 2 to 3 equivalent diameters long and of an area within 1%
of the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
3. Variable supply system may be an auxiliary fan or throttling device.
4. The distance from the exit face of the largest nozzle to the downstream settling means shall be a minimum of
2.5 throat diameters of the largest nozzle.
5. For the purpose of calculating the density at Plane 5 only, Ps5 may be considered equal to (Pt8 + P).
6. In lieu of a total pressure tube, a piezometer ring can be used to measure static pressure at plane 8. If this
alternate arrangement is used, and the calculated plane 8 velocity is greater than 400 fpm, then the calculated
plane 8 velocity pressure shall be added to the measured static pressure.
V
*Pv2 = 2 2
2
Pt2 = Pv
Q = Q5 5
Pv = Pv2
Pt = Pt2 Pt1
Q
V2 =
A2 2
Pt1 = Pt8
Ps = Pt Pv
*Q5 = 2 Y
*The formulae given above are the same in both the SI and the I-P systems except for Q5 and Pv2; in the I-P version,
the constant
min.
Transition Piece
Notes
1. Dotted lines on inlet indicate an inlet bell which may be used to approach more nearly free delivery.
2. Dotted lines on fan outlet indicate a uniform duct 2 to 3 equivalent diameters long and of an area within 1%
of the fan outlet area and a shape to fit the fan outlet. This may be used to simulate an outlet duct. The outlet
duct friction shall not be considered.
Pv3r
Pv3 =
n
*V3 = 2
Pv3
3
A
Pv = Pv3 3 2
A2 3
L
Pt1 = Ps3 + Pv3 f 13, Pv3
Dh3
Q3 = V3 A3
Pt2 = Pv
Q = Q3 3
Pt = Pt2 Pt1
Ps3 =
Ps3r
n
Ps = Pt Pv
*The formulae given above are the same in both the SI and the I-P systems except for V3; in the I-P version, the
constant
42
Pressure (Pa)
43
44
2D4
2D4
D4
4
Fan on test
6D4
LT2
D4
2D4
0.95 ( D4 / D2 ) 1.07
2
D4
LT2 = D4
4
Fan on test
5D4
D4
2D4
D4
Note: The dimensions 'b' and 'h' are the width and height of a rectangular section of a duct.
Figure 20 Common Part for Rectangular Fan Outlet Where b h [21]
45
46
PV = mRT
dP dm
=
RT
dt
dt
And:
1 dm
dm
Q =
or dt = Q
dt
Eq. B.1
And:
V dP
Q =
P dt
Or:
V P
Q =
P t
Eq. B.2
Or:
V
Q=
RT
dP
dt
47
Test Chamber
Valve
P
Pressure Gage
Figure B.1 - Pressure Decay Leakage Method Setup
V P
Q = t
Pt t
P (pressure)
P0
Pt
Pt
t = From Figure B.2
Pt
t
tmin= 10 s
t (time)
Figure B.2
Test Chamber
Valve Flowmeter
Fan or Air Compressor
Pressure Gage
Figure B.3 - Leakage Test Setup, Flow Meter Method
48
Connecting Tubing
to Pressure Indicator
(6 mm (0.25 in.) ID. Min.)
Measuring Duct
Notes:
1. Static pressure taps shall be in accordance with Figure 2A.
2. Manifold tubing internal area shall be at least 4 times that of a wall tap.
3. Connecting tubing to pressure indicator shall be 6 mm (0.25 in.) or larger in ID.
4. Taps shall be within 13 mm (0.5 in.) in the longitudinal direction.
D.1 General
P
Q = Q1
P1
D.2 Symbols
In the derivations which follow, certain symbols and
notations are used in addition to those which are also
used in the standard.
SYMBOL DESCRIPTION
Hi
n
P
UNIT
Eq. D.2
Substituting:
Ho =
2
P
Q1
6343.3 1 P1
1/ n
dP
Eq.D.3
Q1P1 n P2
1
Ho =
6343.3 n 1 P1
Eq. D.4
1/ n
Pt
P2
1
P1
Eq. D.5
t =
Ho
Hi
Eq. D.6
It follows that:
Q1Pt n P2
6343.3Hi n 1 P1
t =
P2
1
P
1
( n 1) / n
Eq. D.7
Q
The fan power output (Ho) is proportional to the
shaded area which leads to:
2
Ho =
50
1
QdP
6343.3 1
Eq. D.1
t =
t =
Q1Pt K p
Hi
Q1Pt K p
6343.3Hi
Where:
Eq. D.8 SI
n P2
1
n 1 P
Kp =
P2
1
P1
t
Kp =
Eq. D.10
t
Kp =
x Hi
z Q1Pt
( 1) / t
1
(1 + x )
(1 + x ) 1
x 6343.3Hi
( 1) / t
1
(1 + x )
z Q1Pt
(1 + x ) 1
Eq. D.15 SI
(1 + z ) = (1 + x )(
1) / t
Eq. D.16
ln (1 + z )
Eq. D.17
Substituting:
Two new coefficients (x and z), may be defined in
terms of the information which is known from a fan
test:
x=
Pt
P1
Eq. D.11
And:
1 Hi
z=
Q1P1
1 6343.3Hi
z=
Q1P1
Eq. D.12 SI
Eq. D.13 SI
And:
x 6343.3Hi
=
1 z Q1Pt
Q1Pt z ln (1 + x )
t =
6343.3Hi x ln (1 + x )
Eq. D.18 SI
And:
z ln (1 + x )
Kp =
x ln (1 + z )
Eq. D.19
Manipulating algebraically:
x Hi
=
1 z Q1Pt
Q P z ln (1 + x )
t = 1 t
Hi x ln (1 + x )
Eq. D.14
51
= 13.595 in.
39.37 in. 249.089 Pa
D.7.2 The constant 1097.8 is used in Equations 7.8
I-P, 7.18 I-P, 7.21 I-P, 7.22 I-P, 7.27 I-P, 7.28 I-P, 7.31
I-P, E.23 I-P, E.25 I-P, E.27 I-P, E.28 I-P, and in
Figures 7A, 7B, 8A, 8B, 9A, 9B, 9C, 10A, 10B, 10C,
11, 12, 13 and 14. This constant is derived by
converting to the SI equivalent units:
0.3048 m 1 min.
V
=
1 ft
60 s
2Pv 249.089 Pa
1.0 lbm/ft 3
3
1.0 in.wg
16.018 kg/m
This gives: V = 1097.8 Pv /
52
1 ft
1.0 in.wg
60 s
Q Pt
1.0 hp
745
.
7
W
H
H 6343.3
D.7.4 The constant 5.2014 is used in Equation 7.12
I-P. This constant is derived by converting to the SI
equivalent units:
P 249.089 Pa
1.0 lbm/ft 3
= 1
3
1.0 in.wg
x 16.018 kg/m
53.35 ft lb/lbm R
1.8 R
R 287.1 J/kg K ( t dx + 459.67 ) 1.0 K
5.2014 P
= 1
x R ( t dx + 459.67 )
tc = t
Eq. E.1
D N
Qc = Q c c
D N
n
P
D N
Ptc = Pt c c c
D N
E.2 Symbols
SYMBOL DESCRIPTION
Eq. E.2
UNIT
Polytropic Exponent
dimensionless
Absolute Total Pressure Pa (in. wg)
Mean Flow Rate
m3/s (cfm)
' (Prime)
Incompressible Value
--------------
Eq. E.3
D N
Hc = H c c c
D N
Eq. E.4
D N
Pvc = Pv c c c
D N
Eq. E.5
53
Eq. E.6
P
Q
Eq. E.7
For the polytropic process:
Ho = Q1Pt K p
Ho =
tc = t
Q Q1Q2
Q1Pt K p
6343.1
Ho =
Eq. E.8
Eq. E.10 SI
Eq. E.11 SI
QPt
6343.3
Therefore:
Q = Q1K1 = QK p
Eq. E.12
Eq. E.13
Eq. E.9
Eq. E.14 SI
Ho =
Q1 ( P2 ' P1 )
6343.3
Eq. E.15
Hc =
Qc Ptc K pc
6343.3 tc
Therefore:
Ho = Q1Pt '
Eq. E.16 SI
Eq. E.22
Eq. E.17 SI
Q
Pv = Pv2 = 2 2
2A
Eq. E.23 SI
Q2
Pv = Pv2 =
2
1097.8 A2
Q1Pt K p
6343.3
It follows that:
2Q2 = 1Q1 = Q1
Therefore:
Pt ' = Pt K p
Eq. E.18
Pv =
QPt K p
H=
6343.3 t
tc
Eq. E.25 SI
Q1Q2
(1097.8 A2 )
Q = Q 2K p 2 Q1Q2
Eq. E.26
Eq. E.20 SI
Qc Ptc K pc
It follows that:
Or:
Hc =
2 A2
Pv =
QPt K p
Q1Q2
Eq. E.19
Eq. E.24
Q 2K p 2
2 A2
Eq. E.27 SI
Q 2K p 2
(1097.8 A2 )
Eq. E.21 SI
55
Pvc =
Pvc =
cQc K pc 2
2 A2c
Eq. E.28 SI
cQc K pc 2
(1097.8 A2c )
Eq. E.29
Eq. E.30
56
D N
Pvc = Pv c c c
D N
P
sc = tc sc
Ptc
Eq. E.31
F.2 Symbols
In the analysis which follows, certain symbols and
notations are used in addition to those which are
used in the standard.
SYMBOL
dP/dQ
ex
X
Fx
SUBSCRIPT
Q
A
b
C
d
f
g
QUANTITY
DESCRIPTION
Area
Barometric Pressure
Nozzle Discharge Coefficient
Dry-bulb Temperature
Pressure for Airflow Rate
Pressure for Fan Pressure
57
Eq. F.5
Eq. F.6
1.70
pb
Eq. F.1 SI
eb =
0.05
pb
1 .0
t d + 273.15
Eq. F.2 SI
ed =
2 .0
t d + 459.67
3
td t w
Eq. F.3 SI
Eq. F.7
2 2
Q
ef = ( 0.01) + 0.01 m
Q
Eq. F.8
2
2
2
Pm Pv
eg = ( 0.01) + 0.01 + 0.1
P P
Eq. F.9
Eq. F.4
pbV
R ( t d + 273.15 )
Eq. F.10 SI
eQA = eA
eQN = eN
eQC = eC
eQ =
ef
2
=0
eQf =
70.73 pbV
R ( t d + 459.67 )
p
( t t )
V = 1.0 0.378 e d w
1500
pb
Eq. F.11 SI
eQ = ec + eA
t d
1.0 pb V R
=
+
+
+
+
1 pb V R Td + 273.15
2
Eq. F.12 SI
2
t d
70.73 pb V R
=
+
+
+
+
70.73 pb V R Td + 459.67
2
Eq. F.13
Eq. F.14 SI
eV 2 = ( 0.00000725t w 0.0000542 ) ( t d t w )
e e
+ f + + eN2
2 2
Eq. F.15A
ePN = 2eN
ePC = 0
eP = e
ePf = 0
ePT = 0
Eq. F.16
ePg = eg
The uncertainty in the fan pressure only can be
determined from the above uncertainties by
combining:
eP = eg 2 + e 2 + ( 2eN )
Eq. F.15
2
=0
p
( t t )
V = 1.0 0.378 e d w
2700
pb
eQg
eQT
Where:
Eq. F.16A
eHN = 2eN
eHC = 0
eH = e
eHf = 0
eHT = eT
Eq. F.17
eHg = 0
Eq. F.17A
59
Test Point
+ Qx + Px
1
QKPX = Px
tan + tan
Eq. F.22
P
tan = 2
Q
Eq. F.23
And:
dP
tan =
dQ
QKQX
QX
QKX
Eq. F.25
eKX
QX
+ QX
QKPX
QKQX
dp
e
dQ
+ PPX
= eQX
2
2 P dP
Q dQ
P
2
2 P dP
Q dQ
Eq. F.26
Introducing correlation factors:
QKX
QKQX
Eq. F.24
dp
1
dQ
+ Px
= Qx
2 P dP
2 P dP
Q dQ
Q dQ
Eq. F.21
dp
dQ
FQ =
2 P dP
Q dQ
QKPX
QKX
Eq. F.27
And:
For QX:
QKQX tan = ( Qx QKQX ) tan
Eq. F.18
tan
QKQX = Qx
tan + tan
Eq. F.19
For PX:
QKPX ( tan + tan ) = Px
60
Eq. F.20
P
2
FP =
2 P dP
Q dQ
Eq. F.28
e
eKX = eQXFQ + PX FP
2
Eq. F.29
eKA = eA FQ
eKC = eCFQ
e
eKf = f FQ
2
e
eKg = g FP
2
eKN = eN ( FQ + FP )
eK =
e
2
2 .0
ed =
= 0.0038
( 60 + 459.7 )
Eq. F.30
( FQ + FP )
e
e
e
eK = + eN 2 + FP 2 g + FQ 2 eC 2 + eA 2 + f
2
2
2
2
Eq. F.31
(6) Fan power output is proportional to the third
power of airflow rate along a system characteristic.
Therefore:
eO = 3eK
5 .0
eW =
= 0 .5
( 60 50 )
eN = 0.005
eT = 0.02
eC = 0.012
eA = 0.005
Q
ef = ( 0.01) + 0.01 m
Q
Eq. F.32
And:
eg =
2
2
e 2
e
e
e = + eN2 + eT 2 + 9 FP 2 g + FQ 2 eC 2 + eA 2 + f
2
2
2
Eq. F.33
F.5 Example
The characteristic test curve for a typical backwardcurve centrifugal fan was normalized on the basis of
shut-off pressure and free-delivery airflow rate. The
resultant curve is shown in Figure F.1.
An uncertainty analysis based on this curve and the
maximum allowable measurement tolerances
follows:
( 0.01)
P P
+ 0.01 m + 0.1 v
P P
0.05
eb 2 =
= 0.00000308
28.5
= 0.00000238
2
2 .0
ed2 =
= 0.00001481
( 60 + 459.7 )
61
F.6 Summary
The example is based on uncertainties which, in turn,
are based on 95% confidence limits. Accordingly, the
results of 95% of all tests will be better than indicated.
Per unit uncertainties of one half those indicated will
be achieved in 68% of all tests while indicated per
unit uncertainties will be exceeded in 5% of all tests.
The examples from above provide the following
conclusions:
(1) The characteristic uncertainty for the specified
tolerances is about 1% near the best efficiency point
and approaches 2% at free delivery. The uncertainty
also increases rapidly as shutoff is approached.
(2) The fan efficiency uncertainty is about 3% near
the best efficiency point and exceeds 5% at free
delivery. The uncertainty increases rapidly near
shutoff.
62
63
0.05
0.04
en
0.03
0.02
ek
0.01
0
0
10
20
30
40
50
60
70
80
90
100
%Q
%P
dP
dQ
FP
FQ
e 2
+ eN2
2
eg 2
FP 2
2
2 2
ef 2
2
F
e
+
e
+
Q c
A
4
eK
e0
99
3.2
3.215
53.510-6
211.410-6
0.0172 0.0531
95
90
85
16
31.5
46
3.075
2.900
2.700
47.510-6
41.210-6
36.810-6
182.510-6
150.610-6
123.210-6
0.0162 0.0500
0.0149 0.0464
0.0138 0.0433
80
59.5
2.500
33.710-6
100.210-6
0.0129 0.0405
2.275
0.45769 0.54231
31.210-6
31.910-6
80.210-6
0.0120 0.0379
0.54786 0.45214
31.210-6
32.510-6
60.910-6
0.0112 0.0357
31.210-6
34.910-6
43.110-6
0.0105 0.0337
75
70
72
82.7
1.950
65
91.2
1.575
0.64051 0.35949
60
98
1.150
38.810-6
26.210-6
0.0098 0.0319
55
102.6 0.800
42.610-6
14.510-6
0.0094 0.0307
50
105.3 0.500
46.210-6
6.610-6
0.0092 0.0301
0.95006 0.04994
31.210-6
49.310-6
2.010-6
0.0091 0.0299
0.99082 0.00918
31.210-6
51.610-6
010-6
0.0091 0.0299
31.210-6
51.910-6
010-6
0.0091 0.0300
30
31.210-6
52.410-6
0.610-6
0.0092 0.0301
25
107
53.010-6
2.810-6
0.0093 0.0306
20
106
53.510-6
7.410-6
0.0096 0.0313
31.210-6
53.710-6
20.010-6
0.0102 0.0331
-0.016
31.210-6
54.010-6
64.010-6
0.0122 0.0386
31.210-6
54.110-6
259.810-6
0.0186 0.0571
45
40
35
15
10
5
107
0.250
107.9 0.050
108
64
Iteration 2:
0.99
Re2 = 196, 020
7.006 134.6
+
Re2
Re2
7.006
134.6
+
96, 020
1
196, 020
Ce2 = 0.9835
Iteration 1:
Step 1-1: Calculate Re, using
P 5
1097.8
Re =
CeD6Y
60 6
1 E 4
where:
6
Ce
D6
Y
P
(1-E 4)
=
=
=
=
=
=
=
1097.8
Re1 =
(0.99)(0.5)(0.998) (1.005 )( 0.0711)
( 60 ) 1.222 105
Re = 1, 363, 000D6
P x
1 4
7.006
(Re1 )
134.6
Re1
7.006
134.6
6
+
197, 397 197, 397
Ce1 = 0.9831
65
AMCA #1140
[3] ASHRAE Standard 41.5-75 (1975) Standard Measurement Guide, Engineering Analysis of Experimental Data,
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA 30329 U.S.A.
AMCA #1142
[4] ISO/TC 30/WG 8 (Secr. 7) 13E, 1969 Draft Proposal for an ISO Recommendation on Fluid Flow Measurement
In Closed Conduits by Means of Pitot Tubes, International Organization for Standardization, Geneva,
SWITZERLAND.
AMCA #2313
[5] FOLSOM, R. G., Review of the Pitot Tube, IP-142, 1955, University of Michigan, Ann Arbor, MI U.S.A.
AMCA #1144
[6] BOHANON, H. R., Air Flow Measurement Velocities, Memorandum Report to AMCA 210/ASHRAE 51P
Committee, April 18, 1973, (available from Air Movement and Control Association International, Inc., Arlington
Hieghts, IL 60004-1893 U.S.A.)
AMCA #1146
[7] WINTERNITZ, F. A. L. and FISCHL, C. F., A Simplified Integration Technique for Pipe-Flow Measurement,
Water Power, vol 9, no. 6, June, 1957, pp 225-234.
AMCA #1147
[8] BROWN, N., A Mathematical Evaluation of Pitot Tube Traverse Methods, ASHRAE Technical Paper No. 2335,
1975 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA 30329
U.S.A.
AMCA #1003
[9] BOHANON, H. R., Fan Test Chamber-Nozzle Coefficients, ASHRAE Technical Paper No. 2334, 1975,
American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA 30329 U.S.A.
AMCA #1038
[10] BOHANON, H. R., Laboratory Fan Test: Error Analysis, ASHRAE Technical Paper No. 2332, 1975, American
Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA 30329 U.S.A.
AMCA #1034
[11] IEEE Standard 112-1984 (R1996), Standard Test Procedure for Polyphase Induction Motors and Generators,
The Institute of Electrical and Electronics Engineers, New York, NY U.S.A.
AMCA #1149
[12] ASHRAE Standard 41.1-86 (RA91) Standard Measurements Guide, Section 6.12, American Society of
Heating, Refrigeration and Air-Conditioning Engineers, Inc., Atlanta, GA 30329 U.S.A.
AMCA #1168
[13] BS 848: Part 1: 1980, Fans for General Purposes Part 1. Methods of Testing Performance. British Standards
Institute.
[14] WHITAKER, J., BEAN, P. G., and HAY, E., Measurement of Losses Across Multi-cell Flow Straighteners, NEL
Report No. 461, July, 1970, National Engineering Laboratory, Glasgow, Scotland, U.K.
AMCA #1153
[15]ISO/TC 117 SC1/WG 1 (Denmark-4) 46E, 1971 Report on Measurements Made on the Downstream Side of
a Fan with Duct Connection. International Organization for Standardization, Geneva, SWITZERLAND
AMCA #1152
[16] POTTER, A. C. and BURKHARDT, K. W., Test Chambers for Fans, Results of Tests Conducted by AMCA
210/ASHRAE 51 Committee, 1975. Air Movement and Control Association International, Inc., Arlington
Heights, IL 60004-1893 U.S.A.
AMCA #1154
66
67
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
worlds manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.