You are on page 1of 8

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste...

Page 1 of 8

Power Systems Engineering

Choosing Between
Resistor and Reactor
for Neutral Ground
Impedance

Enter your email


address to
subscribe to this
blog and receive
notifications of

Faults involving ground produce high fault

new posts by
email.

current magnitude especially when the


transformer(s) neutral is solidly grounded.
The neutral ground circuit in the transformer

Join 492 other


subscribers

provides the return path for the fault


currents. To limit this current, impedance
either in the form of a reactor or a resistor
is installed in the neutral circuit. See the

Subscribe

figure below.

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 2 of 8

Cable Volt Drop


Problems?

Eliminate Voltage Drop in lo


cable runs and Save on cab
costs

Ground Fault Current Path

The table below lists the differences between


utilizing a resistor or reactor as the

Recent Posts Tags

impedance in the transformer neutral circuit.

Choosing

Resistor

Reactor

Between
Resistor and
Reactor for
Neutral Ground
Impedance

Image

Image

courtesy:Postglover

courtesy:Trench

Power
Cable
Neutral
and System
Grounding

Pros

1. It uses actual

1. It uses inductive
Substation

resistance of the

reactance of the

design material

coil to create an

SCADA System Design Guide

impedance path

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 3 of 8

to limit the fault

for the fault

Cable and

current.

current.

Conduit
Installation in

2. It is universally

2. It is well suited

Substations -

applied without

for applications

Best Practices

any limitation.

which require
several thousand
amps to flow
through it for a

Substation SubSurface

short duration.
Engineering: An
Overview of
What a Geotech

Cons

1. It is expensive to

Survey Reveals

1. It is typically
Per Unit

build since it

applied in

must have

systems where

enough mass to

there is a desire

absorb the fault

to limit the

current energy.

ground fault

The price

current to a

increases with

magnitude that is

the increase in

25% to 60% of the

fault current it

three phase fault

can handle and

current. If the

time rating.

ground fault

System Practice
Problem

current is limited

Solved For
Easy
Understanding
What Do
Symmetrical,
Asymmetrical,
Momentary,
Interrupting,
Close &

to less than 25%

Latch

of the threephase fault

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 4 of 8

current then the

Ratings

neutral winding

Mean?

can be subjected
to transient over-

Power
Circuit

voltages

Breaker -

(explained

Operation

below).Therefore,

and Control

a surge arrester

Scheme

should be
installed in with

Determining
short-

the reactor to
circuit

achieve the
rating of

reduction in fault
circuit

current and

breakers

prevent transient
over-voltages

Direct

from damaging

Transfer

the neutral

Trip Scheme

winding of the
transformer.

More on transient overvoltages:


Transient over-voltages are produced by arcing faults,
not surges. The over-voltage occurs when the arc
strikes due to a line-to-ground fault and charges the
system capacitive reactance. When the arc momentarily
extinguishes, the charge needs to dissipate. When the

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 5 of 8

neutral ground resistor is used as the impedance,


its resistance is usually less than the capacitive
reactance, thereby allowing the voltage to discharge.
However, when the reactor is used and when its
reactive impedance is high (to limit ground fault
current to less than 25% of the three phase current), the
voltage cannot discharge. As the arc re-fires, the
charge can continually build, thus creating the overvoltage.

Summary:
If it is desired to limit the fault current to a
really low magnitude using the actual resistance
then a resistor is recommended. On the other
hand, if several thousand amps of fault current
is permissible in the system then the reactor is
recommended. In the either case, the reactor can
be an economical solution. Keep in mind, we
are talking about shunt air core reactor in the
transformer neutral for current limiting purpose.
Series reactors, however, are expensive. The
price of any neutral ground impedance device
increases with the increase in the continuous
current rating (for reactors), impedance rating,
and time rating.

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 6 of 8

*****
grounding
resistor

neutral grounding

reactor

transient overvoltage

Leave a Reply

AR CH IVES
January
2013
December
2012
September
2012
June 2012
May 2012

TAG C LOU D

arc
flash study arc
AC system

flash test
asymmetrical current

WEL COM E TO
P E GUR U

Protective
Relaying

base values
cable shield
grounding
direct buried conduits

direct
transfer trip
FACT generator swing

March

Ground grid
HVDC IEEE 1584

2012

John Camara Juan L.

January

B OOKS ON M Y
SH ELF

Lewis
Blackburn
Bala

2012

lockout relays modern

November

power system

NEC 2011
Handbook

Power System
Analysis and
Design

momentary rating

2011

NCEES Professional

August

Engineering

2011

neutral
grounding

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 7 of 8

July 2011
June 2011
May 2011
April 2011
March
2011

NFPA 70E
OSHA 1910 Pass
PE Exam

permissive
over reaching
transfer trip

per unit
system PE
Sample Problems

September
2010
July 2010

pilot
relaying
power blackout power

power
system Power
transformers
PPE
flow

June 2010

protective
relaying

reactive power support

short circuit
rating steady state
stability substation
conduit details

symmetrical
components
symmetrical current
system frequency
thermal limitation

transformers
voltage drop
limitation Zia A.
Yamayee

ABO UT

C ON TA CT

T E RM S & CO ND I T ION S

PRI VA CY POL IC Y

SI TE M AP

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

Choosing Between Resistor and Reactor for Neutral Ground Impedance | Power Syste... Page 8 of 8

http://peguru.com/2013/01/choosing-between-resistor-and-reactor-for-neutral-ground... 02-04-2015

You might also like