Professional Documents
Culture Documents
Scope
1.0
This design guide presents preferred practice for relay co-ordination and
settings to achieve effective tripping of the electrical auxiliaries in power and
industrial plants. Part I of this guide details relay co-ordination procedures,
while Part II indicates methods of setting for different types of relays, for
various protections. Part III, the Appendix, includes worked out examples for
relay co-ordination as well as relay settings.
Part 1
Relay Co-ordination
1.0
1.1
The co-ordination starts from the extreme downstream protection, which may
be a fuse.
1.2
The co-ordination interval for the relay immediately above the fuse is decided
by the fuse positive tolerance, relay negative tolerance, relay overshoot and
a safety margin. A minimum co-ordination interval of 0.2 second is to be
maintained between the relay and the fuse.
1.3
1.4
For industrial plants, the operating time of the extreme upstream relay in the
plant, considered along with its breaker opening time, at the incoming power
supply fault level. The co-ordination starting from the extreme downstream
relays shall ensure that this requirement is met.
1.5
For the power plants, the opening time of the extreme upstream relays is
determined by the switchgear rating. Since the switchgear normally has 1
second rating, the maximum relay operating time should not exceed 0.9
second at the rated fault level.
1.6
The following procedures can also be considered to simplify the relay coordination procedure.
1.6.1 Use of very inverse and extremely inverse time relays on downstream side
feeders.
1.6.2 Reduction of the co-ordination interval between to 0.35 second although this
reduces the relay margin.
1.6.3 Elimination of the co-ordination interval between two relays, which will not
cause power interruption to other loads. For example, in co-ordination of
relays on the primary and secondary side of transformers and co-ordination
of relays on the breakers at the sending and receiving ends of a tie/radial
feeder.
1.6.4 The co-ordination interval between relays provided on incoming feeders and
the bus coupler can be eliminated in cases where the bus coupler is normally
kept open.
1.6.5 A differentially connected scheme for relays on incoming feeder can be
considered in cases where selective tripping is required and where the
coordination interval is to be reduced and bus coupler is normally kept
closed.
1.7
On any particular bus, amongst relays on various outgoing feeders, the relay
with highest operating time is to be considered for co-ordination with the
relay on the incoming feeder. It shall also be ensured that the relay on the
incoming feeder does not operate for the starting condition of the largest
motor.
1.8
The instantaneous relays on the primary side of the transformer feeder shall
be set above the through-fault level on the secondary side to prevent the
relay from operating for a secondary side fault. Generally, the setting
adopted is 1.3 times the through-fault current. This value covers the CT error,
relay error as well as the over-reach of the instantaneous relay.
1.9
1.10
1.11
Directional relays, when used for duplicate incoming feeders, are to be set at
50% of the sending end and non-directional relays over-current setting.
2.0
2.1
2.2
2.3
Part 2
network
3.0
General
3.1
3.2
Transformer feeder
3.2.1 The transformer feeders couple two switchboards at different voltage levels
with circuit breakers at both sending (HV) and receiving (LV) ends.
3.3
Motor feeder
3.3.1 The motor feeders are meant solely for the switching and protection of either
HT or LT motors.
3.4
Tie feeder
3.4.1 The tie feeders join two switchboards of identical voltage level with circuit
breakers at both the sending and receiving ends. Power flow through these
feeders is normally unidirectional, though the bi-directional power flow can be
allowed under certain specific circumstances.
3.5
4.0
Transformer feeders
4.1
Over-current protection.
4.2
4.3
when grading with outgoing transformer feeders with highest overcurrent elements on their primary side.
In both the above cases, two methods of setting this relay are possible.
The first with a low current setting, just above full load value, but with a
high time setting to avoid either relay operation during the motor
starting period or a high time setting to grade with the downstream
transformer feeder IDMT (51) protection on its primary (and not the
instantaneous protection).
The disadvantage with this method of setting, even though it offers a
certain degree of overload protection, is that the fault clearing time at
the system fault level would be relatively higher, thus, stressing the
system and equipment for an unnecessarily longer period.
The second, preferred alternative, is to choose a higher current setting
(which may be of the order of 2-4 times full load) to avoid the motor
4.4.1 Purpose of this relay is to provide protection in case of external earth faults in
effectively earthed and low resistance earthed systems.
4.4.2 The type of relay is same as 4.3.2, except for the setting range which is lower.
4.4.3 Setting procedure for this relay as defined in 4.3.4 for over-current relay is
generally applicable to this protection as well. However, for setting IDMT
earth fault relays, in the absence of any other constraint, the lowest setting
available may be generally chosen keeping in view the coordination
requirement detailed in 4.3.2 above and in Part 1 of this guide.
4.5
4.5.1 This relay provides instantaneous earth fault protection to all internal faults in
the transformer winding to which it is applied. As it is a unit protection, the
setting of this relay does not require coordination with other protection
schemes. In resistance earthed systems, this protection also supplements the
normal differential protection, since it offers protection to a larger percentage
of the transformer winding.
4.5.2 The type of relay used is high impedance, voltage operated relay.
4.5.3 Relay setting procedure
The maximum voltage that is likely to appear across this relay (V R) during
external faults is first calculated assuming that the worst condition of
impedance, i.e. the CT on one side saturating. The total relay circuit
Differential protection
4.7.1 This is a unit type protection provided against phase to phase as well as
phase to earth faults in both the transformer windings or at the transformer
terminals.
4.7.2 A percentage biased differential relay is recommended for this application.
For the transformers of large ratings, the relay should have additionally 2 nd
and 5th harmonic restraint feature as detailed in the transformer protection
guide.
4.7.3 Relay setting procedure
A biased differential relay is used to prevent operation under through fault
condition, as even under normal external fault condition, a certain differential
current can flow through the operating winding of the relay due to following
reasons.
i.
ii.
iii.
iv.
4.8
4.9
Over-temperature protection
5.0
Motor feeders
5.1
5.2
5.2.1 The purpose of this relay is to provide protection against overloading and to
certain extent against single-phasing to all the motors generally up to 120 kW
rating.
5.2.2 The relay is three phase, bi-metallic, temperature compensated, thermal
relay, either operated directly by the motor current or through CT for the
motors of large ratings. The relay shall be hand reset or auto-reset type.
5.2.3 Relay setting procedure
The operating value of this relay is generally set at the motor full load current
or at marginally lower current.
5.3
5.3.1 The relay works as back-up protection to the motors under stalling condition.
The motors of 100 kW and above are considered to cover under this
protection depending on their criticality. In case where thermal protection is
not effective under stalling, i.e. where thermal withstand characteristics of
the motor lies below the relay operating characteristics in either the cold or
hot condition, this relay becomes the main (and only) protection under
stalling condition.
5.3.2 Two instantaneous relays having high drop off to pick up ratios (above 80%)
in R and B phases with one common timer (on delay type) is used for this
protection.
5.3.3 Relay setting procedure
In case where a detailed relay application check is not carried out, i.e. for the
motors of less than 125 kW rating, the current setting chosen on each
instantaneous OC relay shall equal twice the motor full load current. The
common timer shall be 1 sec more than the starting time of the motor at the
minimum permissible voltage during starting, i.e. 80% off rated voltage for
the motors rated more than 125 kW, a detailed relay application check for
thermal overload shall be carried out. Procedure for this check is detailed
under thermal overload protection.
i.
ii.
If however, the relay hot and cold characteristics cuts the corresponding
motor withstand curve, at any point, which is say X time the full load
current then the current setting shall be twice the full load current of the
motor. (X x IFL) multiplied by 0.9, whichever is lower. The time setting
chosen shall be detailed under i. above.
iii.
In case where the locked rotor withstand time under hot condition is less
than or nearly equal to the starting time of the motor, at either 80%,
5.4.1 Purpose of this relay is to provide protection to the motor against overheating
due to either overloads or presence of negative sequence components under
hot and cold conditions.
5.4.2 A thermal relay with inverse characteristics, sensing and compensating for
load current simulate a thermal image of the motor under hot and cold
condition is used. The relay senses current from at least twp phases. A choice
of characteristics is available with a wide range of time constants to match
the varied motor withstand curves encountered. As an alternative, an inverse
relay sensing only total load current can be used with a separate
instantaneous negative sequence relay.
5.4.3 Following procedure may be followed for deriving the relay setting.
i.
Current setting
The current setting chosen would be calculated as follows.
I Rel I FL x
CTS R
x
CTP
Where,
IRel = current setting on relay
IFL = full load current of motor in amp
CTP = rated CT primary current
CTS= rated CT secondary current
R = overload factor of motor, if any (R = 1for CMR motor)
= pick-up value of relay in terms of number of times current setting
In case the relay has current setting is available steps, next higher
setting (with respect to the calculated setting) would be chosen.
ii. Setting of time constant
The time constant of the relay chosen would be less than the time
constant of the motor being protected.
iii. Selection of relay characteristics
Relay application checks are to be carried out on all motors above 125
kW. This check consists of plotting he motor withstand curves and relay
operating characteristics under both hot and conditions together with the
motor starting current Vs time characteristics on the graph.
Normal relay available in the market have a choice of various operating
characteristics under both hot and cold conditions. Ideally, the motor
curves and relay curves should be chosen as follows.
(a) Case I
(i)
Both the relay hot and cold characteristics lie completely below
corresponding motor withstand curves up to the locked rotor
value.
5.5.2 Type of relay used is instantaneous over-current relay, one on each phase
having low transient overreach (less than 5%) to prevent pick-up during
transient inrush currents when the motor is started.
5.5.3 The relay shall be set at 1.5 times the motor starting current. The additional
factor of 0.5 takes care of the current transformer and relay errors, transient
overreach of the relay and tolerance on the starting current.
5.6
5.6.4
relay works as back-up protection to the motors under stalling condition. The
motors of 100 kW and above are considered to cover under this protection
depending on their criticality. In case where thermal protection is not
effective under stalling, i.e. where thermal withstand characteristics of the
motor lies below the relay operating characteristics in either the cold or hot
condition, this relay becomes the main (and only) protection under stalling
condition.