You are on page 1of 12

Sheet No.

Component /Detail

Description

Draw ing Guide

MGE Galaxy 7000 250kVA 5+1 400V Parallel Module With 2000kVA SSC LIGHT Draw ing guide.

2-4

Solution

5-6

UPS

MGE Galaxy 7000 250kVA, 400V .

SSC

MGE Galaxy 7000 2000kVA SSC LIGHT 400V.

8-9

Battery

MGE Galaxy 7000 250kVA 5+1 400V Parallel Module With 2000kVA SSC LIGHT.

MGE Galaxy 7000 BATTERY CABINET.

10-11

System One Line Diagram MGE Galaxy 7000 250kVA 5+1 400V Parallel Module With 2000kVA SSC LIGHT System One Line Diagram.

12

System Wiring Diagram MGE Galaxy 7000 250kVA 5+1 400V Parallel Module With 2000kVA SSC LIGHT System Wiring Diagram.

Rating

SKU Number

250kVA

G7TUPS250

UPS COG Details in mm


X-Distance Y-Distance Z-Distance
706

680

350

Floor Loading Data

Dimensions
Weight
HxW xD
in kg
250kVA UPS
1900x1412x855
965
2000kVA SSC Light 1900x1012x849
660
1012 Wide
1900x1012x855 1419
Battery Cabinet
1412 Wide
1900x1412x855 1693
Battery Cabinet
Rating

Floor Loading
kg / m2
799
763
1640
1402

Galaxy 7000 UPS 250kVA 6Module (N+1) Site Planning Data, Parallel UPSs with Static-Switch Cabinet (SSC LIGHT)
Input and output Voltage : 400V AC

UPS
Rating

kVA

kW

250

225

UPS AC Input

BATTERY

UPS AC Output

System

UPS Mechanical Data

Recommended
Recommended
Typical
Nominal
Battery
Over current
Nominal
Over current
Dimensions
Nominal
Current
Current
Nominal Maximum
System Output
Protection
Output
Minimum / Battery
Protection
HxW xD
System Output
(A)
(A)
Input (V) Current Current(A)
kVA
Device Ratings
(V)
kW
Device Ratings Maximum
(mm) see note
Current (A)
Individual
(in UPS
see note 2
(A)
Individual UPS
VDC
Individual UPS
12
UPS
Cabinet)
(A)
(A)
400
351
442
630
528 / 576 238.6
570
400
360
630
1250
1803
1900x1412x855

1. Input current based on full rated output load.


2. Maximum (Max.) current is for duration of battery recharge.
3. Input and bypass cables must be run in separate conduits from output cables. Not more than
three conductors in raceway assumed; ambient temperature of 30C assumed.
4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC
output wiring and over current protection be sized to UPS full load rating to accommodate
possible future expansion.
5. Nominal battery voltage is shown at 2.0 volts/cell .
6. DC cables should be sized for a total maximum of less than 1% of CB rating.
7. Wiring requirements:
- AC Input/Output: 3, 3 or 4 wire + ground, depending on UPS configuration.
See Installation Manual and submittal drawings for specific instructions.
- DC Input: 2 wire (positive and negative) + ground
8. All wiring to be in accordance with all applicable national and/or local electrical codes.
9. Minimum access clearance per UPS drawings.
10. Top or bottom cable entry through removable access plates. Punch plates to suit conduit size, then replace.
11. Control wiring and power wiring must be run in separate conduit.
12. Weights and dimensions shown do not include battery cabinet(s), distribution cabinet(s), or other options.
13. Backup emergency generator must be properly sized for UPS application and equipped
with an isochronous governor for frequency regulation, and a UPS-compatible voltage
regulator for voltage stability.
14. If site configuration requires an external maintenance bypass, phase parity between UPS
input and UPS bypass must be ensured. Consult Schneider Electric applications engineer.
15. The UPS must be installed in a room with restricted access, in compliance with standard IEC 60364-4-42.
16.Cable installation to comply with EN60364-5-52, max ambient 30 deg C, cable sizes
shown refer to 600V rated,90 degree C multicore copper conductors with thermosetting insulation
17. Input I THD < 5% at Full Load
18. Output V THD < 2% Linear Load, <5% Non Linear Load
19. Input power-factor is > 0.99 for > 50% loading.

Efficiency Details
System
25% load load 50% 75% load 100% load
250 kVA 400 V
89.7
93.2
93.8
93.8

Heat
Heat
Losses
Average
Losses
Floor
in kW
weight
in kW
Loading
Batteies
Kg see
Batteies
kg / m2
fully
Note 12
charging
charged
990
820
8.2
14.9