You are on page 1of 2

Parameters for Dynamic Models of Power Plant Equipment

Given below are parameters that were used for dynamic simulation on the WECC 9 Bus System
whose topology is shown in [1]. While generator, exciter and governor were modeled for
generators 1 and 2 (at buses 1 and 2 in [1]), only generator and exciter were modeled for
generator 3 (at bus 3 in [1]). The meaning of parameters can be found in GE-PSLF or PTI/PSSE
manuals.
TABLE I
Generator Parameters; GENROU Model
Parameters
Gen 1
Gen 2
Gen 3
Rating (MW)
90
190
110
7.8
2.1
3
T'd0
0.021
0.04
0.047
T''d0
0.404
2.95
0.82
T'q0
0.06
0.15
0.07
T''q0
8.4
1.38
6.01
H
0
0
0
D
2.1
2.32
1.137
Xd
1.88
2.15
0.95
Xq
0.25
0.245
0.146
X'd
0.27
0.4
0.48
X'q
0.01
0.0181
0.012
X''d
0.01
0.0181
0.012
X''q
0.0171
0.013
0.0078
Xl
0.165
0.081
0.079
S(1.0)
0.414
0.271
0.265
S(1.2)
0
0
0
Ra
TABLE II
Exciter Parameters (Identical Parameters used for the Exciters of all three Generators); ST1A Model
Parameter
Value
Parameter
Value
0.01
0.065
tr
kc
0.1
0
vimax
kf
-0.1
0
vimin
tf
1.5
0
tc
tc1
7.0
0
tb
tb1
140
0
ka
klr
0.008
99
ta
vamax
6.18
-99
vrmax
vamin
0.7
99
vrmin
Ilr
TABLE III
Governor Parameters (Identical Parameters used for the two Governors); GGOV1 Model
Parameter
mwcap
r
Rselect
Tpelec
Maxerr
Minerr
Kpgov
Kigov
Kdgov
Tdgov
Vmax
Vmin
Tact
Kturb
wfnl
Tb
Tc
Flag

Gen 1
90
0.05
1
0.5
10
-10
3
0.55
0
1
1
0
0.15
2.7
0.205
2.5
0.8
0

Gen 2
190
0.05
1
0.1
10
-10
3
0.55
0
1
1
0
0.15
2.7
0.205
2.5
0.8
0

Parameter
Teng
Tfload
Kpload
Kiload
Ldref
Dm
ropen
rclose
Kimw
Pmwset
aset
Ka
Ta
Db
Tsa
Tsb
Rup
Rdown

Gen 1
0
3
4
2
1
0
99
-99
0
0
10
10
0.1
0
1
10
99
-99

Gen 2
0
3
4
2
1
0
99
-99
0
0
10
10
0.1
0
1
10
99
-99

Generator Parameters, assuming GENROU model, used for dynamic simulation of the IEEE 39
bus system are given below. Many of these parameters were obtained from [2]. Since [2]
assumes the two-axis model for generators, additional parameters had to be added to the
parameters in [2] so that the GENROU model could be used. The network topology and
parameters for the 39 Bus system can also be found in [2].
TABLE IV
Generator Parameters for the IEEE 39 Bus System; GENROU Model
Gen 31
Gen 32
Gen 33
Gen 34
Gen 35
Gen 36

Parameters

Gen 30

Rating (MW)

400

700

700

700

600

700

600

T'd0

5.7

7.8

5.69

5.4

7.3

5.66

6.7

T''d0

0.38

0.021

0.3793

0.36

0.4867

0.3773

0.4467

T'q0

1.5

0.404

1.5

0.44

0.4

1.5

T''q0

0.25

0.06

0.25

0.0733

0.0667

35.8

24

28.6

26

34.8

Xd

0.2495

2.1

0.262

Xq

0.237

1.8

X'd

0.0531

X'q

0.0876

X''d

Gen 37

Gen 38

Gen 39

600

800

1500

4.79

4.79

10.2

0.3193

0.68

0.08

0.41

1.96

1.96

0.2

0.25

0.0683

0.3267

0.33

0.03

26.4

24.3

34.5

34.5

42

0.67

0.254

0.295

0.29

0.2106

0.2106

0.1

0.258

0.62

0.241

0.292

0.28

0.205

0.205

0.069

0.25

0.0436

0.132

0.05

0.049

0.057

0.057

0.057

0.031

0.27

0.166

0.166

0.0814

0.186

0.0911

0.0587

0.0587

0.021

0.004248

0.01

0.003488

0.01056

0.004

0.00392

0.00456

0.00456

0.00248

0.0011

X''q

0.004248

0.01

0.003488

0.01056

0.004

0.00392

0.00456

0.00456

0.00248

0.0011

Xl

0.00304

0.0171

0.00295

0.0054

0.00224

0.00322

0.0028

0.00298

0.00125

0.0008

S(1.0)

0.081

0.165

0.081

0.081

0.081

0.081

0.081

0.081

0.081

0.34

S(1.2)

0.271

0.414

0.271

0.271

0.271

0.271

0.271

0.271

0.271

1.12

Ra

rcomp

xcomp

[1]. P.W. Sauer and M.A. Pai, Power System Dynamics and Stability, Illinois: Stipes Publishing
L.L.C, 2006, p. 125.
[2]. IEEE 10 Generator 39 Bus System, [Online]. Available: http://sys.elec.kitamiit.ac.jp/ueda/demo/WebPF/39-New-England.pdf/

You might also like