Professional Documents
Culture Documents
Effectiveness-NTU Method
H. Jaber
B. L. Webb
Department of Mechanical Engineering,
The Pennsylvania State University,
University Park, PA 16802
This paper develops the effectiveness-NTU design method for cooling towers. The
definitions for effectiveness and NTU are totally consistent with the fundamental
definitions used in heat exchanger design. Sample calculations are presented for
counter and crossflow cooling towers. Using the proper definitions, a person competent in heat exchanger design can easily use the same basic method to design a
cooling tower of counter, cross, or parallel flow configuration. The problems associated with the curvature of the saturated air enthalpy line are also treated. A
"one-increment" design ignores the effect of this curvature. Increased precision can
be obtained by dividing the cooling range into two or more increments. The standard
effectiveness-NTU method is then used for each of the increments. Calculations are
presented to define the error associated with different numbers of increments. This
defines the number of increments required to attain a desired degree of precision.
The authors also summarize the LMED method introduced by Berman, and show
that this is totally consistent with the effectiveness-NTU method. Hence, using proper
and consistent terms, heat exchanger designers are shown how to use either the
standard LMED or effectiveness-NTU design methods to design cooling towers.
Introduction
Berman (1961) described how the "log-mean enthalpy tions may be simplified using the moist air enthalpy potential
method" (LMED) may be applied to cooling tower design. He proposed by Merkel (1926). The enthalpy potential method is
also developed a correction factor to account for the curvature approximate, and combines the driving potential of the heat
of the saturated air enthalpy curve. In their 1940 publication, and mass transfer processes into a single enthalpy driving poLondon et al. introduced definitions of e and NTU to use in tential. The driving potential is the enthalpy difference of the
plotting cooling tower test data. However, these definitions moist air at the water film-air interface and the bulk air stream.
are not generally consistent with the basic defintions used today Webb (1988) presents a critical discussion of precise and apin heat exchanger design. They developed empirical curve fits proximate design methods. Attempts to apply the F-LMED or
of their e-NTU curves for design purposes. Moffatt (1966) is e-NTU methods to cooling tower design must use the enthalpy
apparently the first to derive the e-NTU equation for a cooling driving potential. Thus, the "log-mean enthalpy difference"
tower (counterflow). As will be shown later, his definitions do (LMED) corresponds to the "log-mean temperature differnot agree with the basic definitions of e and NTU for certain ence" (LMTD) of heat exchanger design. One problem ascombinations of water and air flow rate. Others have used sociated with use of the F-LMED or e-NTU methods for cooling
their e and/or NTU definitions for graphic representation of tower design is that the slope of the saturated air enthalpy
test data. Other than Moffatt (1966), no authors have at- curve (4) versus temperature is a curved line. So, use of the
tempted to employ these definitions actually to design a cooling F-LMED method will involve errors associated with approxtower.
imating this curve with a straight line. Berman (1961) rigorously
The F-LMTD and e-NTU methods have long been used for applied the F-LMED method to cooling towers, and defined
design of heat exchangers. It is desirable to apply the basic a correction factor (8) to correct for the curvature of the is
concepts of the F-LMTD and e-NTU methods to the design versus T curve. The correction factor essentially provides a
of evaporative heat exchangers (cooling towers and evaporative two-increment design (N= 2). The derivation of this correction
fluid coolers or condensers). The objective of this paper is to factor is presented in the Appendix.
show how the e-NTU method may be applied to cooling tower
Traditional cooling tower design methods typically use an
design. The present development will observe the precise con- incremental method, which approximates the 4 versus Tcurve
cept definitions used in the e-NTU method for heat exchangers into N segments, where N may be in the range of 4 or more.
and be applicable to all cooling tower operating conditions.
Each segment is a straight line approximation to the 4 versus
Traditional cooling tower design methods typically use a T curve. The simplest application of the F-LMED or e-NTU
method and nomenclature that are unlike the traditional F- methods to cooling tower design would use one segment (N
LMTD and e-NTU heat exchanger design methods. Hence, = 1). It will be shown that one may use N > 1 if increased
heat exchanger designers cannot successfully translate their accuracy is desired.
design methodology to cooling tower design. A key benefit of
Application of the e-NTU method to cooling tower design
the present development is that heat exchanger designers will requires physical and algebraic definition of the effectiveness
clearly understand how to apply their understanding of heat (e) and the "number of transfer units" (NTU). A number of
exchanger design to cooling towers.
attempts have been made to define e and NTU for cooling
Simultaneous heat and mass transfer processes occur in cool- tower design. However, virtually all of these definitions are
ing towers. Hence, the design equations must account for both flawed, in the sense that they are inconsistent with the corenergy transfer processes. The complexity of the design equa- responding basic definitions used for heat exchanger design.
Baker (1984) and the ASHVE Guide (1941) have defined e and
NTU strictly for convenience, and they have not attempted to
Contributed by the Heat Transfer Division and presented at the ASME Winter apply these definitions to the actual e-NTU design method.
Annual Meeting, Boston, Massachusetts, December 13-18, 1987. Manuscript Baker (1984) essentially dismissed his definition as being of
received by the Heat Transfer Division April 6,1988; revision received November
"no value." The e-NTU design method for heat exchangers
15,1988. Paper No. 87-WA/CRTD-2. Keywords: Heat Exchangers, Mass Transinvolves use of the "capacity rate ratio" (CR = Cmin/Cmax).
fer.
Journal of Heat Transfer
AIR FLOW
SPECIFIC HUMIDITY
<
X
V/
<
WATER FILM
Fig. 2 Gravity-drained water film with temperature, velocity, and humidity ratio profiles
Km
Le =
m =
m+
N =
NTU =
q =
R =
T =
U =
V =
W =
z =
kW/m 2 -s
13 = water film thickness, m
5 = enthalpy correction factor,
kJ/kg
e = thermal effectiveness = qact/
Qmax
Subscripts
1 = air or water inlet conditions
2 = air or water outlet conditions
a = air
act = actual heat transfer
av = average
C = cold fluid
f = liquid water
g = saturated water vapor
H = hot fluid
i = at air-water interface
m = moist air
s = saturated air
w = water
wb = wet bulb
mQ, 1 +di
W + dW
w'V
R,C
SYMBOL
1
1
10
15
in-
/
/
20
25
m 0 ,i
vdmw
//
<tz
,w
20-
h f -dh f
y'
Fig. 3 Control volume illustrating the heat and mass transfer processes
at the air-water interface
,**'
-.-.
O lf
.-"
10i
,/
i -
10
'
20
30
40
F - L M E D Formulation
Assuming a linear variation of is versus T, one may define
the log-mean enthalpy difference (LMED) for the cooling tower
process illustrated in Fig. 1 as
A/2-A/!
A/m =
ln(AI2/AIl)
(3)
Fig. 4 Enthalpy correction factor & versus the exit water temperature
TM for different cooling ranges R
(8)
= ('/i + n - 2 / | J / 4
The corresponding equation that occurs in the e-NTU development for a heat exchanger with CH = Cmin is
(4)
A/ 2 -A/,
ln[(A/2-5)/(A/1-6)]
Effectiveness-NTU Method
Figure 3 shows a control volume on a differential element
of the cooling tower. Equation (1) is the transport equation
for the energy transfer from water to air. An energy balance
on the water film and the air, over the length dz, gives
(6)
The e-NTU derivation is performed for a counterflow cooling tower, using the terminology defined in Fig. 1. The derivation essentially parallels that for a counterflow heat
exchanger. It is necessary to express dq in equation (1) in terms
of the air enthalpy. The slope of the is versus T curve is defined
as
f'=di/dTw
Journal of Heat Transfer
77T7?
d(TH-Tc)
{TH-TC)
(7)
KmUf'/myfip,,)
- Uma]dA
Ull/mfjCpH-l/mcCpddA
(9)
(10)
01)
(5)
UA and LMTD are used in heat exchanger design; the corresponding definitions for cooling tower design are KA and
LMED. The flow configuration correction factor (F) used in
heat exchanger design applies equally well to cooling tower
design.
dq = mwcpwdTw = madi
(12)
(13)
KmdA
ITlrr
(1-Cj)
(14)
UdA
Cmin
a-cR)
(15)
KA
(16)
Previous works on cooling towers, in which NTU was defined, have not observed the precise definition of equation
(16). Some authors (London et al., 1940; Moffatt, 1966; Zivi
and Brand, 1956) have defined KmA/ma as the "NTU of the
air," while others (Kelly, 1976; Keyes, 1972; Majumdar and
Singhal, 1983; Baker and Shryock, 1961) have defined KJ\./
mw as "the NTU of the water." The authors assert that equation (16) is the only correct and consistent definition.
Next, it is necessary to define the heat exchange "effectiveness" e. This will be defined identically to that used for heat
exchanger design
(17)
= 9act/<7,
act' ymax
basic definitions for effectiveness and NTU are used, and the
same algebraic equation for the e-NTU relationship applies.
A one-increment design (N= 1) may be performed very quickly.
The e-NTU (or the F-LMED) method is subject to approximations involved in linearizing the is versus Tcurve as a straight
line. However, the desired accuracy can be obtained by breaking the design down into N increments. Traditional cooling
tower design methods typically use an incremental method.
One may use the correction factor (5) given by equation (4)
for the e-NTU method, which essentially gives a two-increment
design. To do this, one redefines /,, and ia as (in 5) and (ii2
S), respectively. Hence, the definition of e is rewritten as
m
where
<7max mmmUi\
'l )
(18)
= exp[-NTU(l-C*)]
(19)
ig-h
in-ii
eCfl-1
(20)
Equating equations (19) and (20) gives the final e-NTU equation for the counterflow cooling tower
l-exp[-NTU(l-Q)]
'l-C/jexpI-NTUa-C*)]
(21)
R
R+A
(22)
(23)
(24)
/Wmin('il-5-'l)
Ai
(25)
_^^-^====
-2-
-2TVIB, C
SYM80L
-4,-C
-6-
"
- 8 -
SYMBOL
5
10
15
-6-
! 1
-8-
g
g
A,C
-4-
5
15
25,35
-10-
-10-
-12-
-12-
-14-
-14-
-16-
-16-
1.0, B
mjm,
1.0, Ft
-2SYMBOL
-4-
mw/ma
/{!
0.5
1.0
1.5
- 6 - '/
-8-
1
<
-10-12-14-16-
i "
i.o, r,
Tb = 20C, H
165
155 -
l\
145135
//
125CT>
-3
1 15 i
105 -
^>-
95^
<
fE
85-
LINE E - ^
//
V
//
//
//
z
/
W
Examples of Sizing and Rating Calculations
75S
/
A sizing problem determines the NTU (size of the tower)
65\
/
for given air and water conditions. A rating calculation de*
55termines the leaving water temperature for given air and water
AREA A ,
AREA A,
inlet conditions and the tower characteristic.
45T2
*~ T
-~T|
Counterflow Sizing Calculation. The following example
35- /
presents a one-increment sizing calculation for a counterflow
1
1
cooling tower. The same procedure would be used per incre35
40
15
20
25
30
10
ment for a multi-increment design. Both the e-NTU and LMED
TEMPERATURE, C
methods will be illustrated.
Fig. 9 Graphic representation of the enthalpy correction factor S
Consider the following operating conditions: Water enters
at a temperature of 35C and is cooled to 30C. The correThe air enthalpy change is found from the energy balance,
sponding saturation enthalpies are /sl = 129.54 kJ/kg and is2
= 99.96 kJ/kg. The air entering is 25C (wet bulb) with an equation (6): A/' = (mw/ma)cpwR - 20.93 kJ/kg; the air exit
enthalpy of /, = 76.6 kJ/kg. The mass flow rate ratio is mw/ enthalpy is i2 = 97.53 kJ/kg.
ma = 1.0. The average water temperature is T = (30 + 35)/
7 The LMED Method.
2 = 32.5C and the corresponding saturation enthalpy is isav
A/, = isl-ix = 99.96-76.6 = 23.36 kJ/kg
= 113.92 kJ/kg. The enthalpy correction factor is calculated
using equation (4) giving a value of 0.414 kJ/kg.
M2= isl-i2= 129.54-96.54 = 33.09 kJ/kg
wav
< wb<
5-35
20
20
20
12
10, 20
10
20
5-15
1.0
1.0
1.0
0.5-1.5
5
6
7
8
Table 3 Effect of the enthalpy correction factor (5) on a oneincrement design using the e-NTU method
TWb>
5-35
20
20
20
A, C
R, C
mw/ma
8
8
5-15
8
12
10-20
10
10
1.0
1.0
1.0
0.5-1.5
Error,
percent
<3
<3
<2
<3
5
6
7
8
= 0.555
= 0.708
NTU =KmA/mmin=
Cr = Mmin/mmm
= w + // = mwcpw/f
1
2
Figure
e = [ma(i2-ii)]/[mmin(isl-5-ii)]
The counterflow rating calculations may be performed without iterations using the following procedure:
ma = 0.724
e = ( m a A / ) / [ f f j + a , - 5 - / 1 ) ] = 0.486
At the calculated values of CR and e, one obtains NTU =
KmA/m^
= 0.84 and K^/rriy, = 0.608, as compared to the
given value of 1.87. One may continue the iterative calculation
using a bi-section method until the calculated tower characteristic agrees with the given value.
Conclusions
1 The analysis presented herein shows how the e-NTU theory of heat exchanger design may be applied to cooling towers.
The effectiveness and NTU are defined by equations (17) and
(16), respectively. The effectiveness and NTU definitions are
in precise agreement with those used for heat exchanger design,
and are applicable to all cooling tower operating conditions.
2 One-increment sizing calculations may be quickly performed for any flow configuration. The calculations are improved by using multi-increments and/or the enthalpy
correction factor.
3 The influence of the four independent variables, R, A,
Twb, and m/ma on the accuracy of the e-NTU method is
evaluated as a function of the number of increments used. The
ranges of the parameters considered is given in Table 1. The
calculations show that:
(a) The NTU is underpredicted when the e-NTU method is
used. For J? < 20C and Twb > 15C, the underprediction is 4-8 percent for a one-increment design, and
less than 3 percent for a two-increment design. The underprediction is highest for low wet bulb temperatures
and high cooling ranges.
(b) Use of the enthalpy correction factor reduces the error
associated with a lower number of increments. Moreover, a one-increment design with this correction factor
is equivalent to a two-increment design without the correction.
4 Using the methods outlined herein, a person competent
in the e-NTU (or the F-LMTD) method of heat exchanger
design can use the same procedure to design cooling towers of
any flow configuration.
5 Using the e-NTU curve for the appropriate flow configuration, one may quickly calculate the required NTU for specified operating conditions. This negates the need for the
extensive sets of curves given by Kelly (1976) and the Cooling
Tower Institute (1967).
References
ASHVE, 1941, ASHVE Heating, Ventilation, Airconditioning Guide, 19th
ed., Chap. 26, pp. 522-523.
Baker, D. R., and Shryock, H. A., 1961, "A Comprehensive Approach to
the Analysis of Cooling Tower Performance," ASME JOURNAL OF HEAT TRANSFER, Vol. 83, pp. 339-350.
Baker, D., 1984, Cooling Tower Performance, Chemical Publishing Co., New
York, Chap. 6, p. 101.
Berman, L. D., 1961, in: Evaporative Cooling of Circulating Water, 2nd ed.,
Henryck Sawistowski, ed., Pergamon Press, New York, Chap. 2, pp. 94-99;
translated from Russian by R. Hardbottle.
Cooling Tower Institute, 1967, Cooling Tower Institute Performance Curves,
The Cooling Tower Institute, Houston, TX.
Kays, W. M., and London, A. L., 1984, in: Compact Heat Exchangers, 3rd
ed., McGraw-Hill, New York, Chap. 2, p. 51.
Kelly, N. W., 1976, Kelly's Handbook of Crossflow Cooling Tower Performance, Neil W. Kelly & Associates, Kansas City, MO.
Keyes, R. E., 1972, "Methods of Calculation for Natural Draft Cooling
Towers," presented at the 13th National Heat Transfer Conference, Denver,
CO, Aug. 6-9.
London, A. L., Mason, W. F., and Boelter, L. M. K., 1940, "Performance
Characteristics of a Mechanically Induced Draft, Counterflow, Packed Cooling
Tower," Trans. ASME, Vol. 62, pp. 41-50.
Majumdar, A. K., Singhal, A. K., and Spalding, D. B., 1983, "Numerical
Modeling of Wet Cooling TowersPart 1: Mathematical and Physical Models,"
ASME JOURNAL OF HEAT TRANSFER, Vol.
Merkel, F., 1926, "Verdunstungskuhlung," VDI Zeitschrift deutscher Ingenieure, Vol. 70, pp. 123-128.
Moffatt, R. J., 1966,' 'The Periodic Flow Cooling Tower: A Design Analysis,''
Technical Report No. 62, Dept. Mechanical Engineering, Stanford University,
CA.
Webb, R. L., 1988, " A Critical Review of Cooling Tower Design Methods,"
in: Heal Transfer Equipment Design, R. K. Shah, E. C. Subbarao, and R. A.
Mashelkar, eds., Hemisphere Pub. Corp., Washington, DC, pp. 547-558.
Whillier, A., 1976, " A Fresh Look at the Performance of Cooling Towers,"
ASHRAE Trans., Vol. 82, pp. 269-282.
Zivi, S. M., and Brand, B. B., 1956, "Analysis of the Cross-Flow Cooling
Tower," Refrigeration Engineering, Vol. 64, No. 8, pp. 31-34.
A P P E N D I X
The derivation of the enthalpy correction factor is given
below with reference to Fig. 9. The saturation line is divided
into two straight line segments resulting in two trapezoids
whose areas are Ax and A2, respectively; hence
A i = (i,-i + ijav) (Twau - Tw2)/2
A1=(ia + iiv){Twl-Twav)/2
(26)
(27)
(29)