Professional Documents
Culture Documents
I. INTRODUCTION
ZEQ
AB
IAB
LINE LB (healthy)
ZsA
EsA
LINE LA
(faulted)
AA
VAA
ZsB
(1d )Z0m
dZ0m
IAA
BB
ZLB
F
(1d )ZLA
dZLA
RF
DIST TRIP
REL
BA
VF
EsB
IF
Fig. 1. Distance protection of parallel lines under availability of complete measurements at one end.
Z1EQ
AB
~
IAB2
IAB1
Z1sA
dZ1LA
E1sA
E2sA=0
Z1LB
AA
VAA1
VAA2
IAA1
IAA2
BB
Z1sB
IF2
IF1
(1d)Z1LA
BA
~
E1sB
E2sB=0
IF1
IF2
(1)
( Z 1LB / Z 1LA ) I AB 2
I
I F 2 = AA2
1 d
(2)
where:
d unknown distance to fault [pu],
( Z 1LB / Z 1LA ) ratio of impedances of both lines (LA , LB)
for positive (negative) sequences.
For the sake of simplicity it is assumed in all further
considerations that positive sequence impedance of both
parallel lines is identical, i.e. ( Z 1LB / Z 1LA ) = 1 , what is a
common case.
The sequence components of a total fault current (1)(2)
can be used for determining a voltage drop across a fault path
resistance R F (Fig. 1):
V F = R F (a F1 I F1 + a F 2 I F 2 + a F 0 I F 0 )
(3)
where:
a F1 , a F 2 , a F 0 weighting coefficients for the positive,
negative and zero sequences.
As its innovative, the presented here approach delivers the
optimal estimation of this voltage drop. From the point of view
of the considered application (adaptive distance protective
relay) the meaning of the feature optimal corresponds to the
FAULT TYPE
a F1
aF2
aF0
a-g
b-g
1.5
1.5
1.5a
1.5a
0
0
c-g
1.5a
1.5a 2
a-b
0.5(1 a 2 )
0.5(1 a )
b-c
0.5(a 2 a )
0.5(a a 2 )
c-a
0.5(a 1)
0.5(a 2 1)
a-b-g, a-b-c,
a-b-c-g
b-c-g
1 a2
1 a
a2 a
a a2
a 1
a2 1
c-a-g
a = exp(j2 / 3) ,
j = 1
3
TABLE III
COMPOSITION OF FAULT LOOP SIGNALS
N 12
1 d
where after assuming ( Z 1LB / Z 1LA ) = 1 :
(4)
FAULT TYPE
a-g
b-g
c-g
a-b, a-b-g
a-b-c, a-b-c-g
I AA _ a + k 0 I AA0 + k 0m I AB 0
V AA _ b
I AA _ b + k 0 I AA0 + k 0m I AB0
V AA _ c
I AA _ c + k 0 I AA0 + k 0m I AB0
V AA _ a V AA _ b
I AA _ a I AA _ b
b-c, b-c-g
V AA _ b V AA _ c
c-a, c-a-g
V AA _ c V AA _ a
I AA _ b I AA _ c
I AA _ c I AA _ a
k 0 = ( Z 0 LA Z 1LA ) / Z 1LA
k 0 = Z 0 m / Z 1LA
R
real(V AA _ p ) d real( Z 1LA I AA _ p ) F real( N 12 ) = 0 (6)
1 d
FAULT TYPE
N 12
a-g
1.5[( I AA _ a I AA0 ) ( I AB _ a I AB 0 )]
b-g
c-g
a-b
0.5[( I AA _ a I AA _ b ) ( I AB _ a I AB _ b )]
0.5[( I AA _ b I AA _ c ) ( I AB _ b I AB _ c )]
0.5[( I AA _ c I AA _ a ) ( I AB _ c I AB _ a )]
b-c
c-a
a-b-g, a-b-c
a-b-c-g
b-c-g
[( I AA _ a I AA _ b ) ( I AB _ a I AB _ b )]
c-a-g
[( I AA _ c I AA _ a ) ( I AB _ c I AB _ a )]
[( I AA _ b I AA _ c ) ( I AB _ b I AB _ c )]
RF
(7)
imag(N 12 ) = 0
1 d
(8)
where:
U 1 p = Z 1LA I AA _ p .
The classic distance relay determines the fault loop
impedance from the fault loop signals defined in TABLE III:
V AA _ p
(9)
Z p _ classic =
I AA _ p
while according to the derived fault location algorithm:
Z p _ adapt =
Z 1LA
(10)
(1 z 1 )
(1 + z
(11)
where:
z 1 operator corresponding to a single sample delay,
w=
1
,
tan(0.51T )
RF
= Q ( n)
1 d
(12)
where:
n index marker for the present sampling instant,
P1 ( n ) , P2 ( n ) , Q (n ) coefficients determined with the
samples of the input signals (three consecutive samples) and
the impedance parameters (resistances / reactances) of parallel
lines, accordingly to the classified fault type.
In (12) there are two unknowns: d, (R F / (1 d ) ) . For
determining them different approaches have been considered:
application of the Least Error Square method,
filtering the input signals with a pair of orthogonal filters of
short data windows and formulating of (12) for both
orthogonal components,
additional formulating (12) for the other sampling instant, as
for example with using a single sample delay.
1
0
-1
-2
-4
where:
R1LA , X 1LA resistance and reactance of the protected
line LA for the positive sequence.
III. ATP-EMTP EVALUATION
The presented algorithm has been evaluated with using the
fault data obtained from versatile simulations using the ATPEMTP [10]. In the study the transmission network containing
the parallel lines of 120 km length, rated at 220 kV has been
modeled. Impedances of parallel transmission lines were
assumed as: Z1LA=(3.31+37.82j) , Z0LA=(33.00+123.18j) ,
(13)
Solving the set (12)(13) one gets the simple first order
formula for the sought distance to fault:
Q(n) P2 (n 1) Q (n 1) P2 (n)
d ( n) =
(14)
P1 (n) P2 (n 1) P1 (n 1) P2 (n)
-3
R
P1 (n 1)d + P2 (n 1) F = Q (n 1)
1 d
5
x10
3
PHASE VOLTAGES (V)
sw
1.5
20
40
60
Time (ms)
20
40
80
100
120
60
80
Time (ms)
100
120
4
x10
1
0.5
0
-0.5
-1
-1.5
800
600
400
200
0
-200
-400
-600
-800
0
20
40
60
80
Time (ms)
100
120
)
Fault Loop Resistance (
5
full cycle
Fourier
algorithm
actual
10
20
30
40
50
5
4
adaptive
algorithm
3
2
1
actual
0
0
10
full cycle
Fourier
algorithm
40
30
20
actual
10
0
0
10
20
30
40
50
30
40
50
40
50
50
50
20
40
adaptive
algorithm
30
20
actual
10
0
0
10
20
30
half cycle
Fourier
algorithm
classic
algorithm
15
20
10
adaptive
algorithm
5
1
actual
0
0.2
0.4
0.6
0.8
10
20
30
40
50
Fig. 7. Tripping time for the first distance protection zone under a-g faults at
different locations.
50
30
half cycle
Fourier
algorithm
30
20
actual
10
classic
algorithm
20
15
adaptive
algorithm
10
40
missing operation
25
10
20
30
40
50
0.2
0.4
0.6
0.8
Fig. 8. Tripping time for the first distance protection zone under a-b-g faults
at different locations.
[2]
VI. BIOGRAPHIES
Jan Izykowski (M97) was born in Poland in 1949. He
received his M.Sc., Ph.D. and D.Sc. degrees from the
Faculty of Electrical Engineering of Wroclaw University
of Technology (WUT) in 1973, 1976 and in 2001,
respectively. In 1973 he joined Institute of Electrical
Engineering of the WUT where he is presently an
Assistant Professor. His research interests are in power
system protection and fault location.
Eugeniusz Rosolowski (M97, SM00) was born in
Poland in 1947. He received his M.Sc. degree in
Electrical Eng. from the Wroclaw University of
Technology (WUT) in 1972 where he is presently an
Associate Professor. From 1974 to 1977, he studied in
Kiev Politechnical Institute, where he received his Ph.D.
in 1978. In 1993 he received D.Sc. from the WUT. His
research interests are in power system analysis and
microprocessor application in power systems.
Murari Mohan Saha (M76, SM87) was born in 1947
in Bangladesh. He received B.Sc.E.E. from Bangladesh
University of Engineering and Technology (BUET),
Dhaka in 1968 and completed M.Sc.E.E. in 1970. In
1972, he completed M.S.E.E. and in 1975 he was
awarded with Ph.D. from the Technical University of
Warsaw, Poland. He joined ASEA, Sweden, in 1975.
Currently he is a Senior Research and Development
Engineer at ABB Automation Technology Products,
Vsters, Sweden. His areas of interest are measuring
transformers, power system analysis and simulation, and
protective digital relays.