Professional Documents
Culture Documents
+
=
l
(8)
Substitution of the total fault current (8) into the
generalized fault loop model (1) yields:
0
)) 1 ( cosh(
) e ( a ) e ( a
) (
A
1
c1
j
2 F2
j
1 F1
F A Fp
=
d Z
M M
R d V
l
(9)
where:
) (
A Fp
d V defined in (2)(5), with use of the weighting
coefficients specified for different faults in Table I,
) e (
j
1
M , ) e (
j
2
M quantities defined in (7),
F1
a ,
F2
a share coefficients dependent on the fault type, as
gathered in Table II.
The derived fault location formula (9) is compact and
covers different fault types, what requires setting the
appropriate fault type coefficients, as provided in Table I and
Table II.
There are three unknowns in the fault location formula (9):
distance to fault (d
A
), fault resistance (R
F
) and synchronization
angle (). In order to cope with solution for such number of
unknowns, additional equation involving the synchronization
angle has to be formulated. For this purpose the boundary
conditions of different fault types and also the analysis of pre-
fault state have been considered.
Excluding the zero sequence components (a
F0
=0 as in
Table II), the total fault current is:
F2 F2 F1 F1 F
a a I I I + = (10)
Two recommended characteristic sets of the share
coefficients for the considered here phase-to-ground and
phase-to-phase faults are provided in Table III. The other sets
can be determined as well. However, use of the sets from
Table III will result in getting simple analytic solution for a
sought synchronization angle ().
TABLE III
TWO SETS OF SHARE COEFFICIENTS FOR PHASE-TO-GROUND FAULTS AND
PHASE-TO-PHASE FAULTS
Fault Type
ISET IISET
SET I
1 F
a
SET I
2 F
a
SET II
1 F
a
SET II
2 F
a
ag 0 3 3 0
bg 0 3a 3a
2
0
cg 0 3a
2
3a 0
ab 0 1a 1a
2
0
bc 0 aa
2
a
2
a 0
ca 0 a
2
1 a1 0
Applying the sets from Table III the total fault current can
be expressed as follows:
F2
SET I
F2 F1
SET I
F1 F
a a I I I + = (11)
or alternatively:
F2
SET II
F2 F1
SET II
F1 F
a a I I I + = (12)
Comparing (11) with (12) and taking into account (7) one
gets the following formula for the synchronization operator for
faults in Table III:
A2
SET I
F2 A1
SET II
F1
B1
SET II
F1 B2
SET I
2 F c1
ph ph g, ph
j
a a
) a a (
] [e
N N
I I Z
= (13)
In case of phase-to-phase-to-ground faults an analysis of the
boundary conditions yields the following relation between the
zero-, positive- and negative-sequence components of the total
fault current [6]:
F2 F2 F1 F1 F0
I b I b I + = (14)
where:
F2 F1
, b b coefficients delivered in Table IV.
TABLE IV
COEFFICIENTS INVOLVED IN THE RELATION (14)
Fault Type
F1
b
F2
b
abg
a a
2
bcg 1 1
cag
a
2
a
Substituting (7) into (14) results in:
)) 1 ( cosh(
] )[e ( ) (
(15)
)) 1 ( cosh(
] [e
A
1
c1
g ph ph
j
A2 F2 A1 F1 B2 F2 B1 F1 c1
A
0
c0
g ph ph
j
A0 B0 c0
d Z
N b N b I b I b Z
d Z
N I Z
+ + +
=
+
l
l
For three-phase balanced faults one can derive for the pre-
fault state (superscript: pre) positive-sequence:
pre
A1
1
c1
pre
A1
1
pre
B1 c1
3ph
j
) cosh( ) sinh(
] [e
I Z V
I Z
l l +
= (16)
Distance to fault is not involved in determination of the
synchronization operator (16).
After resolving (9) into the real and imaginary parts and
taking the respective relation: (13) or (15) or (16), one of the
known numeric procedures for solving nonlinear equations can
be applied. It has been checked that the Newton-Raphson
iterative method is a good choice for that.
III. ATP-EMTP BASED EVALUATION STUDY
Performance of the presented method was analysed using a
digital model running on ATP-EMTP simulation software
program [7]. A single-circuit transmission line was used in the
simulation. The main parameters of the modeled transmission
system were assumed as follows:
rated voltage: 400kV
line length: 300km
system frequency: 50 Hz
phase angle of EMFs of Systems: A: 0
o
, B: (30
o
)
sequence impedances of equivalent systems:
Z
1SA
=Z
1SB
=(1.307+j15) ,
Z
0SA
=Z
0SB
=(2.318+j26.5)
line impedances:
Z
1L
=(0.0267+j0.3151)/km
Z
0L
=(0.275+j1.026)/km
line shunt capacitances:
C
1L
=0.013F/km, C
0L
=0.0085F/km.
Different scenarios with changing of a fault were
considered in the performed evaluation study. Fault type, fault
resistance and equivalent system impedances were changed.
The two-end measurements obtained from the simulation
were perfectly synchronized. Therefore, an intentional de-
synchronization of the measurements was introduced.
In order to examine the errors of the presented fault
location algorithm itself, the errorless transformation of
instrument transformers (both for current and voltage) was
assumed at the first stage of the evaluation. Then, the
instrument transformers with typical parameters were included
into the simulation model.
Analog low-pass filters with 350Hz cut-off frequency were
also included. The sampling frequency of 1000Hz was applied
and the respective phasors were determined with use of the
DFT algorithm.
0 0.02 0.04 0.06 0.08 0.1 0.12
4
3
2
1
0
1
2
3
4
Time [s]
S
I
D
E
A
P
h
a
s
e
v
o
l
t
a
g
e
s
:
v
A
[
1
0
5
V
]
a b c
0 0.02 0.04 0.06 0.08 0.1 0.12
3000
2000
1000
0
1000
2000
3000
Time [s]
S
I
D
E
A
P
h
a
s
e
c
u
r
r
e
n
t
s
:
i
A
[
A
]
a b c
0 0.02 0.04 0.06 0.08 0.1 0.12
4000
2000
0
2000
4000
Time [s]
S
I
D
E
B
P
h
a
s
e
c
u
r
r
e
n
t
s
:
i
B
[
A
]
a b c
0.06 0.07 0.08 0.09 0.1 0.11 0.12
0.76
0.78
0.8
0.82
0.84
Time [s]
D
i
s
t
a
n
c
e
t
o
f
a
u
l
t
[
p
.
u
.
]
p.u. 0.8123
0
120)ms A(90
=
d
p.u. 0.8
A_actual
= d
iter. 2nd
A
d
p.u. 0.7994
iter. 2nd
120)ms A(90
=
d
0
A
d
0.06 0.07 0.08 0.09 0.1 0.11 0.12
24.2
24.6
25
25.4
25.8
iter 2nd
F
R
00 . 5 2
0
120)ms F(90
=
R
= 25
F_actual
R
=
95 . 4 2
iter 2nd
110)ms F(90
R
0
F
R
Time [s]
F
a
u
l
t
r
e
s
i
s
t
a
n
c
e
[
]
0.06 0.07 0.08 0.09 0.1 0.11 0.12
4.9
4.95
5
5.05
5.1
Time [s]
S
y
n
c
h
r
o
n
i
s
a
t
i
o
n
a
n
g
l
e
:
]
o
actual
00 . 5 =
o
110)ms (90
4.9809 =
Fig. 3. The sample fault example: a) three-phase voltage of side A, b) three-phase current of side A, c) three-phase current of side B, d) calculated distance to
fault, e) calculated fault resistance, f) calculated synchronization angle
The obtained results for the distance to fault, fault
resistance and synchronization angle of all test cases were
correct and accurate.
Fig. 3 presents the measured three-phase signals and the
calculation results for the sample single phase ag fault. The
following specifications for this fault were taken:
d
A_actual
=0.8p.u., R
F_actual
=25,
actual
=5
o
. The measurements
from the bus A (both current and voltage) were intentionally
delayed by 5
o
with respect to the measurement of the current
from the remote line terminal (B).
In Fig. 3a3c the three-phase measured signals are shown.
For the applied comparatively high fault resistance (25) there
are no visible d.c. components in phase currents (they decay
with a high speed). Distance to fault (Fig. 3d) and fault
resistance (Fig. 3e) are obtained in iterative calculations. The
start of these calculations (iteration number 0) was taken by
transferring the equations to the form relevant for a lumped-
parameter line model. This results in obtaining some errors in
calculated results. As for example, the distance to fault
averaged within the interval from 90 to 110ms (or from 30 to
50ms of the fault time since the fault was applied at t=60ms) :
p.u. 8123 . 0
0
110)ms A(90
=