Professional Documents
Culture Documents
Bin Zhao
Xudong Yang
Key Words
Bypass factor E Particle tracking E CFD E Ventilation
effectiveness
Abstract
The ventilation bypass factor (marked as S) is a simple
and straightforward indicator describing the fraction
of the supply air that bypasses the occupied zone of
a ventilated room. Except for some special circumstances, this factor is very difficult to estimate
quantitatively. In this article, a method for calculating
S by computational fluid dynamics tools is proposed.
Fine particles with small inertia that can be regarded
as moving integrally with air are released at the air
supply inlet to represent the air path lines. S is
calculated by stating the trajectories of the particles
that enters/bypasses the occupied zone. A ventilation
situation is modelled numerically to demonstrate
the detailed procedure of the method. This new
method makes it possible to estimate quantitatively
the ventilation bypass factor and use it as a guide for
ventilation design.
Introduction
Indoor air quality (IAQ) problems pose one of the
most serious environmental risks world-wide today.
However, these are not problems without a solution.
Improvement of the air quality in a room, or other indoor
SAGE Publications 2007
Los Angeles, London, New Delhi and Singapore
DOI: 10.1177/1420326X07082793
Accessible online at http://ibe.sagepub.com
Figure 11 appears in colour online.
Outlet
Vs
Vs
2
Vsz
Occupied zone
S 1
Vsz
Vs
Calculation Principle
Figure 1 shows the schematic of a two-dimensional
model room with one air supply inlet and one outlet
created as an example. The selection of an occupied zone is
optional and should be determined by the requirement of a
Methods
473
1 m/s
3
2
Y
2
Y
1
1
0
0
0
2
Y
474
2
Y
2
X
Z. Liu et al.
S
W
Lamp
Outle
2
Hum
2
1.5
1
4
0.5
3
Z
OZ1
OZ2
OZ3
OZ4
200
300
500
1000
0.245
0.247
0.248
0.248
0.46
0.46
0.462
0.461
0.85
0.85
0.854
0.854
0.89
0.89
0.892
0.893
2
1
0
Y
Inlet
Case Description
A mock-up room (4.8 4.2 2.43 m) with detailed
measured data of velocity and temperature distribution
described in the literature [15] was selected as an example
so that the CFD model could be validated firstly and
then used to calculate S. Figure 7 shows the configuration
of the mock-up room.
The HVAC system, located outside of the office,
supplied a constant amount of air into the office through
two air supply inlets, which were placed on the floor.
The outlet was located in the centre of the ceiling. The
office also included 4 human simulators and 6 overhead
fluorescent lights. All the internal objects and their
location co-ordinates, sizes and heat flow rates are listed
in Table 2. Thermal boundary conditions are significant
for the accuracy of the simulation result. Heat was
transferred mainly by convection and radiation since the
mock-up room had excellent insulation and similar
temperature to the surrounding environment. Radiation
was not calculated in the simulation but this was taken
into account indirectly by setting the wall temperatures
instead. In this case, the ventilation rate was
0.0944 m3 s1 and here we assumed that the supply air
was discharged uniformly into the room. According to the
measurements, the incident angles were 908 and 758 from
the X direction and the estimated turbulence intensity
was 10% and 15% for air injection from the north and
S 1
151
0:245
200
475
Location (m)
Human 1
Human 2
Human 3
Human 4
Lamp 1
Lamp 2
Lamp 3
Lamp 4
Lamp 5
Lamp 6
North inlet
South inlet
Outlet
Size (m)
x
y
z
1.00
1.00
3.40
3.40
0.75
0.75
0.75
2.88
2.88
2.88
0.78
3.78
2.275
0.00
0.00
0.00
0.00
2.35
2.35
2.35
2.35
2.35
2.35
0.00
0.00
0.00
0.40
3.40
0.40
3.40
1.15
2.22
3.13
1.15
2.22
3.13
1.98
1.98
1.975
0.4
0.4
0.4
0.4
1.20
1.20
1.20
1.20
1.20
1.20
0.25
0.25
0.25
1.10
1.10
1.10
1.10
0.10
0.10
0.10
0.10
0.10
0.10
0.00
0.00
0.00
0.40
0.40
0.40
0.40
0.15
0.15
0.15
0.15
0.15
0.15
0.25
0.25
0.25
100
100
100
100
64
64
64
64
64
64
-
Ceiling
Floor
South wall
North wall
East wall
West wall
North supply
South supply
25.7
23
25.0
24.9
25.5
25.3
20.4
19.9
south inlets, respectively. Other thermal boundary conditions are listed in Table 3.
Comparison Between CFD and Experimental Data
To simulate the air flow and temperature distribution
of this case using CFD, a total number of 665,000 meshes
were used and the standard k" turbulence model was
employed. Figure 8 shows the calculated velocity and
temperature results at two important sections of the room.
In the model system, seven measuring positions were
selected, which were marked V1, V2, V3, V4, V5, V6 and
V7 as shown in Figure 9. The simulation results of velocity
and temperature were compared with the measurement
data given by reference [15] at the seven positions in
Figure 10.
As shown in Figure 10, the air velocity in most of the
space was lower than 0.1 ms1 and the hot-sphere
anemometers used for measurements might fail to give
accurate results. For the temperature profiles, there were
small differences at some positions such as V7; the
predicted temperature was a little lower than the measured
data. Overall, the predicted velocity and temperature
profiles matched the measured data quite well. The
agreement between simulated and measured velocity and
temperature suggests that the CFD model predicts the
airflow with reasonable accuracy, which thus could be
employed to calculate S next.
476
Calculation of S
To calculate S in this case, 121 particles with the same
property as those used in the two-dimensional cases
discussed above were released at the two inlets respectively. Their tracks are displayed in Figure 11 and different
occupied zones were defined as shown in Figure 12. The
particle counts entering the five occupied zones are listed
in Table 4 as well as the values of S obtained. The two
inlets are in OZ1 and supply air moves from OZ1 to outlet
on the ceiling, no supply air bypasses the zone and S for
OZ1 thus appears to equal zero. More supply air enters
OZ4 than OZ5 since the air injection from south inlet is
not vertical but has an angle towards the south wall.
Overall, the room has quite good ventilation effect since
most of the supply air reaches the four human simulators.
Conclusion
S is a terse parameter describing the proportion of
supply air bypassing the occupied zone to the total air sent
into a room. It indicates how much supply air is not used
for controlling the air quality of an occupied zone and that
engineers should design proper positions for and form
of air supply inlets and outlets to obtain a small enough S.
Z. Liu et al.
Fig. 8. Velocity vector plot and temperature contours at: (a) Z 2.1 m (the room centerline) and (b) X 3.6 m (two human simulators).
0
V7
0.6
1.2
V6
1.8
V4
2.4
V3
V5
V2
3.6
4.2
V1
4.2
3.6
2.4
1.8
1.2
1.6
4.8 Y
Fig. 9. Horizontal room section and measuring positions (V1, V2, V3, V4, V5, V6 and V7).
477
(a) 1.0
1.0
1.0
0.8
0.8
0.8
0.6
0.6
0.6
Z
Z
0.4
0.4
0.4
0.2
0.2
0.2
0.0
0.0
0.2
0.4
V3
V2
V1
0.0
0.0
0.6
0.2
0.4
0.0
0.0
0.6
1.0
1.0
0.8
0.8
0.8
0.6
0.6
0.6
0.4
0.4
0.4
0.2
0.2
0.2
V4
0.2
0.4
0.6
0.6
0.4
V
1.0
0.0
0.0
0.2
V5
0.0
0.0
0.2
0.4
V6
0.0
0.0
0.6
0.2
0.4
0.6
V
1.0
0.8
0.6
Z
0.4
0.2
V7
0.0
0.0
0.2
0.4
0.6
Fig. 10. Comparison of measured data with the simulation results. Symbols: measured data from Reference [15], Lines: simulation from
this study. (a) Z Z0/H, Z0 is the vertical location along the measure positions (m), H 2.26 m is the height of the room, V is the local
velocity (m s1); (b) T is the local air temperature (8C).
478
Z. Liu et al.
(b) 1.0
1.0
1.0
0.8
0.8
0.8
0.6
0.6
0.6
Z
0.4
0.4
0.4
0.2
0.2
0.2
20.0
25.0
T
30.0
V3
V2
V1
0.0
15.0
0.0
15.0
35.0
20.0
25.0
T
30.0
0.0
15.0
35.0
1.0
1.0
1.0
0.8
0.8
0.8
0.6
0.6
0.6
Z
0.4
0.4
0.4
0.2
0.2
0.2
25.0
T
30.0
30.0
V5
V4
20.0
25.0
T
0.0
15.0
35.0
35.0
0.0
15.0
20.0
20.0
25.0
T
30.0
35.0
V6
0.0
15.0
20.0
25.0
T
30.0
35.0
1.0
0.8
0.6
Z
0.4
0.2
V7
0.0
15.0
20.0
25.0
T
30.0
35.0
Fig. 10. Comparison of measured data with the simulation results. Symbols: measured data from Reference [15], Lines: simulation from
this study. (a) Z Z0/H, Z0 is the vertical location along the measure positions (m), H 2.26 m is the height of the room, V is the local
velocity (m s1); (b) T is the local air temperature (8C). (Continued).
479
(a)
OZ3
OZ2
OZ4
OZ5
North
wall
North
wall
Human 1
Human 3
(b)
121
69
76
62
12
121
63
60
20
45
0
0.45
0.44
0.66
0.76
OZ1
OZ2
OZ3
OZ4
OZ5
Acknowledgement
This project was financially supported by the Specialized
Research Fund for the Doctoral Program of Higher Education
of China, Approval Number 20060003065.
References
1 Brown SK, Sim MR, Abramson MJ, Gray CN:
Concentrations of volatile organic compounds
in indoor air - a review: Indoor Air 1994;4:
123134.
2 Sandberg M: Ventilation effectiveness and purging flow rate a review. Proc Intl Symp Room
Air Convection Ventilation Effectiveness,
Tokyo, Japan, 1992, pp. 2224.
3 Novoselac A, Srebric J: Comparison of air
exchange efficiency and contaminant removal
effectiveness as IAQ indices: ASHRAE Trans
2003;109(2):339349.
4 ASHRAE. ANSI/ASHRAE Standard 62-1999.
Ventilation for acceptable indoor air quality,
480
Z. Liu et al.
481