Professional Documents
Culture Documents
VOLUME 4II
ENGINEERING GUIDE
PDVSA N
TITLE
90618.1.072
0
REV.
AUG.93
DATE
PDVSA, 1983
CATHODIC PROTECTION
FOR APPROVAL
DESCRIPTION
22
L.T
PAG.
DATE AUG.93
ESPECIALISTAS
PDVSA 90618.1.072
ENGINEERING GUIDE
DATE
REVISION
CATHODIC PROTECTION
Main Menu
Table of Contents
Volume
AUG.93
Page 1
Table of contents
1
SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
3
DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTROCHEMICAL CORROSION . . . . . . . . . . . . . . . . . . . . . . .
2
2
5
6
4
6
FUNCTIONS OF CASING . . . . . . . . . . . . . . . . . . . . . . . . .
9
9
10
11
12
10
Types of Surveys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measurement of Potential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage Drop IR (Flow of Current)
...........................
Soil Resistivity Measurements (or water) . . . . . . . . . . . . . . . . . . . .
Current Requirement Surveys .. . . . . . . . . . . . . . . . . . . . .
14
15
17
18
21
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Table of Contents
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume
DATE
AUG.93
Page 2
1 SCOPE
This engineering guide describes some of the methods and basic design
procedures used to control corrosion in oil and fuel production, storage, and
transportation equipment, through cathodic protection.
2 DEFINITIONS
2.1 Cathodic protection is the technique used to reduce corrosion in metallic
surfaces, by passing sufficient cathodic current and making the dissolution
proportion of the anodes negligible. In simple terms, it is the use of direct current
from an external source to counteract the discharge of corrosive current in the
anodic areas of a metal structure, immersed in a conductive means or electrolyte,
such as soil and water. When a cathodic protection system is properly installed, all
the parts of the protected structure collect current from the surrounding electrolyte, and
the total exposed surface becomes a single cathodic area.
2.2 Cathodic protection is used only to control the resulting corrosion of a significant
flow of direct current, from an area of the structure (the anodic area) to another
(the cathodic area), through an electrolyte, This is called electrochemical
corrosion. The anodic area where the discharge into the electrolyte occurs is
corroded; on the other hand, the cathodic area takes the current and no corrosion
occurs; thus the element is cathodically protected
3 ELECTROCHEMICAL CORROSION
3.1
3.2
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
Contents
Volume Table of
DATE
AUG.
93
Page 3
4.2
4.3
5.2
Perhaps the most widely used criteria are the ones that use copper sulfate-copper
electrodes as a half-cell of reference. This electrode is just a copper bar immersed
in a copper sulfate saturated solution, introduced in a plastic cylinder with a
porous contact in the lower end (to contact the electrolyte) and a copper bar that
extends outside (to connect with the high resistance voltmeter or potentiometer).
5.3
5.4
A criterion associated with steel is to change the 300 millivolt potential (0.300
volts.) into the negative, or cathodic, direction of its initial value (natural potency).
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Table of Contents
5.5
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume
DATE
AUG.93
Page 4
5.6
5.7
5.8
In general, the maximum protection potential for cased pipes must be 2.0
volts.
5.9
The influence of IxR (electrolyte voltage drop) must be considered to apply the
0.85 V criterion.
6.1.1
6.1.2
Impressed current anodes, which are relatively inert and require a direct
current source of energy to force the flow of current.
6.2
6.2.1
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
Volume Table
DATE
AUG.
93
Page 5
work very well. Aluminum anodes have been tested on soil, but so far have not
been used for these purposes.
6.2.2 Magnesium anodes are used more on soil given their high driving potential.
Zinc is used mostly in low resistivity soils and water. Aluminum, as has already
been mentioned, is excellent in salt water and has the additional advantage of
having a high energy capacity per pound of anode. As a comparison, in regular
use magnesium is consumed at a rate of approximately 17 pounds per ampere
per year; zinc at a rate of 26 pounds; and an aluminum alloy that is commercially
available, at a rate of only 6.8 pounds.
TABLE I
ELECTROMOTIVE FORCES OF METALS (1)
METAL
Magnesium
Aluminum
2.37
1.66
Zinc
0.76
Iron
0.44
Tin
0.14
Lead
0.13
Hydrogen
(1)
(2)
VOLTS (2)
0.00
Copper
+ 0.34 - + 0.52
Silver
+ 0.80
Platinum
+ 1.20
Gold
+ 1.50 - + 1.68
From: Handbook of Chemistry and Physics, 41st edition, 1959 1960, Chemical
Rubber Publishing Co., pg. 1733.
Half-cell potential in salt solutions, measured with respect to the hydrogen
reference electrode.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
DATE
AUG.93
Page
6
Standard Table
of Contents
TABLE II
PRACTICAL GALVANIC SERIES
Metal
Volts.(1)
1.75
1.6
Zinc
1.1
1.05
0.8
0.5
0.8
0.2
0.5
0.5
Lead
0.5
0.2
0.2
0.2
Laminated steel
0.2
+ 0.3
(1) Typical potential observed in neutral soils and water, measured with
respect to the reference copper sulfate electrode.
6.3.2
Other types of anodes (called impressed current anodes) are iron-silicon alloys
and iron scraps, such as pipes or rails. Steel is quickly consumed (at a
discharge rate of approximately 20 pounds per ampere per year); the semi-inert
graphite or iron-silicon anodes are almost exclusively used on land. In salt water, a
type of alloy anode with 6% antimony 1% silver is used due to its low
consumption, generally 0.1 pounds per ampere per year.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
of Contents
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume Table
DATE
AUG.93
Page 7
6.3.4
When rectifiers are used as a source of power, there is a serious interference due
to the unprotected lines. When this happens, the extraneous line receives
protection where the current enters the pipe, but there is an accelerated corrosion
where the current leaves. If a proper metallic connection is made between the
protected and unprotected lines (extraneous) the problem doesnt occur. This
means, of course, that both structures are receiving cathodic currents and that the
current required for a proper protection is increased equivalently.
6.3.5
7 FUNCTIONS OF CASING
7.1
7.2
Almost all types of casings have imperfections, and corrosion occurs in the
ruptures of the insulation barrier, frequently at an accelerated rate on the small
metal area exposed. However, casing is a very effective weapon to control
corrosion, and when used together with cathodic protection, a complete control
may be obtained with a minimum amount of current applied.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
Volume Table
DATE
AUG.93
Page 8
7.3
In many cases, casing cannot be justified from the economic point of view as a
means to reduce the cost of corrosion control through cathodic protection. An
example is the submerged areas of off-shore metal platforms. However, in many
cases casings are essential from the economic point of view, like in high pressure
buried pipelines. Of course, the existing uncased pipes will be accepted as such, and
only the hot spots are usually checked and protected for economic reasons.
7.4
Usually, the casing used in pipes is thick, bituminous material that is applied
hot, with several reinforcements and layers. Similar materials can be applied
in buried tanks or in the bottom of the tanks. This may be 99% effective or
more, by protecting the metal from making contact with the soil or the water, and
reduce the amount of cathodic protection current required.
7.5
Thin layers of casing are also frequently used. Great progress has been
made in the development of adhesive tapes for lining which are widely used
today, while the conventional casing made of thin layers of vinyl or epoxy
are used for the internal lining of pipes, tanks and vessels in oil fields. The
adhesive tapes give results similar to the bituminous lining applied hot on pipelines,
while vinyl and epoxy must be treated carefully when applying cathodic
protection.
7.6
Cement layers are frequently used around the casing of wells, and inside the pipes
that transport corrosive water. Their effectiveness in controlling corrosion is related
to their thickness and continuity of coverage. These layers are relative conductive,
and they dont reduce the cathodic protection current requirements, just as
conventional casing.
7.7
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
Table of Contents
Volume
DATE
AUG.93
Page 9
8.1.2
Measurement of the voltage drop IxR (current flow), whether of the structure or
the surrounding electrolyte.
8.1.3
8.1.4
8.2.2
The structures may be any facility that is submerged or in contact with soil and
water. For the purposes of this specific section, it is easier to select a type of
structure, a buried steel pipeline for discussion, understanding that it applies to any
structure in the same environment.
8.2.3
Potentials usually vary between a few millivolts and several volts, and a high
sensitivity instrument must be used to obtain an exact measurement of the
potential against a reference CU/CUSO 4 electrode or any other.
8.2.4 This sensitive measuring instrument, plus two reference electrodes (usually
CU/CUSO4), test cables, and connection devices, form the minimum required
equipment to study voltage or difference in potential.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
8.2.5
Volume Table
DATE
AUG.93
Page 10
For the test, the structure is connected to vertical conductors through valve
boxes, or using a connection device, for example a connection bar. It is
extremely important to establish a good low resistance electrical connection
with the buried structure. The negative terminal of the voltmeter is connected
through the proper conductors to the contact on the pipe, and the positive
terminal is connected to the reference electrode. If the CU/CUSO4 electrode is
used, the pipe will show a positive polarity. The potential of the structure is
taken with the electrode firmly buried directly on the soil over the structure.
The structure earth potential is recorded (P/E). This procedure is repeated at
proper intervals throughout the system analyzed. The areas with greater positive
potential indicate anodic or corrosive areas.
The direction of the direct current flow in the structure (pipe) can be
established using a millivolt meter or a potentiometer. The area or point where
the current flows from the structure to the soil is where corrosion occurs. This
can be detected by looking at the direction and magnitude of the flow of current
on the pipe. The point where the maximum value is reached and the flow
direction changes is the point where corrosion is produced. The magnitude of the
flow of current, which may be calculated or estimated from the millivolt readings,
and the resistance of the pipe between the connection points, gives an
approximate loss of metal per year.
a.
Corrosion may even occur without a flow of measurable current on the structure,
due to the action of the element between the connection points. Thus, the
measurement of the flow of current on the structure is more useful for the
location of large anodic areas.
b.
Since measurements as low as one millivolt may occur, the resistance of the
test cables and the connections with the structure must be low, around one per
cent, compared to the internal resistance of the voltmeter.
c.
Knowing the resistance of the pipe, the flow of current may be calculated through
Ohms law, that is, I = E/R, where:
I = current in amps
E = difference of potential in volts
R = resistance of the pipe in Ohms (between connection points)
d.
If the resistance of the pipe analyzed is unknown, it may be estimated using the
published tables for steel pipes of different dimensions, or calibrating at the point,
applying a known current on a test section of the pipe.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
8.3.2
Volume Table
DATE
AUG.93
Page 11
Given that the same current flowing on the pipe also flows on the adjacent
ground, where the much greater resistance of the soil produce greater millivolt
readings that on the pipe, a modified technique is widely used for unlined
buried pipes.
This method is called the Surface potential or the two electrodes study, a n d
requires a high resistance voltmeter or a voltmeterp o t e n t i o m e t e r w i t h a p o l a r i t y c h a n g i n g s w i t c h , t w o CU/CUSO4
electrodes, and proper test cables. The study group must also have a pipe locator
and a soil resistivity meter, since it is essential to stop immediately over the pipe
and read the soil resistivity in anodic areas.
8.3.3
The two CU/CUSO4 electrodes, which must give reading of around two
millivolts between each other, are placed over the pipe at a proper distance,
usually 20 feet, and the difference of potential (in millivolts) and of polarity of the
electrodes is read on the meter and recorded. The electrodes are in fact
alternated throughout the line, maintaining the separation of the set, and the
millivolt and polarity readings are recorded throughout the length of the pipe under
study. It must be noted that the pipe-to-soil potentials are not necessary, although
they may be considered desirable.
8.3.4
The anodic and cathodic areas are identified as points of change of potential.
Given the importance of the anodic areas, they are identified throughout the
study; soil resistivity measurements, usually paired with the millivolt readings,
are obtained at each point. The corrosion engineer will need them to correctly
interpret the severity of the anodic areas and select the number and size of the
anodes required for the change of flow of corrosion current in those hot spots. The
experience of the corrosion engineer in charge is of the utmost importance, and has
been a vital factor in the great success obtained with this technique in thousands of
kilometers of uncased pipes in the last years.
Since the flow of current that comes and goes from the pipe will generally
occur in areas where the soil resistivity is lower, it makes sense to assume that
low resistivity areas are anodic. Thus, this method only determines the
possibility of corrosion occurring, and not whether corrosion occurs or not, or at
what speed.
8.4.2
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
Volume Table
DATE
AUG.93
Page 12
the Sheppard probe. Real resistivity values by themselves usually have little
significance. The great importance of the information obtained in the study is
the difference in soil resistance throughout the whole line. Some companies have
selected 2000 ohmscentimeters as the ideal value; for resistivities below this
value, severe corrosion is to be expected. However, it must be stated that
severe corrosion may also occur in uncased pipelines if there is an abrupt
resistivity change in the soil (for example, from 5,000 to 50,000 ohm
centimeters).
8.4.3
The results of the survey are used to select areas to install protection
systems, such as coatings and cathodic protection.
The real amount of current required for the cathodic protection of a structure
may be obtained by the corrosion engineers in different ways. In this cathodic
protection selection, there must be a total corrosion control (as evidenced by
fulfilling some selected criteria, such as a potential of 0.85 volts for a
CU/CUSO4 electrode), rather than the protection of a hot spot. The latter has a
well-defined place in the economic scheme of existing uncased pipelines, which
almost never justify 100 percent cathodic protection.
8.5.2
8.5.3
8.5.4
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
Contents
DATE
AUG.93
Page 13
and isolated from other structures, or a given portion of the line. In long lines,
several tests may be required, especially if substantial difference in the
condition of the casing and/or the soil resistivity in different areas are
expected. Temporary test currents of up to 10 amps may be applied through a
battery, and up to 100 amps may be applied with a generator for welding. The
temporary anode bed used to discharge the test current on the ground may be any
existing non-critical structure, that is not electrically connected to the pipe being
tested, such as an abandoned line section or well casing. In many cases, a
temporal anode bed will be created for test purposes, made of steel bars,
aluminum sheets or real anodes that may be left in place for a later permanent
installation, or install it so they can be removed and reused. It is desirable to
place the test beds, at least for large current consumption, at a distance from the
pipe similar to that expected for the permanent anode bed.
8.5.5 Studies performed on well casing for the application of cathodic protection
may include several of the above mentioned techniques. A well casing potential
profile is used to initially locate thick anodic and cathodic areas, and then
determine the effect of the temporal cathodic protection currents applied at the
well head.
8.5.6
To preserve the log time (as well as the shutoff time of the oil or gas well being
logged) predicted current estimates are frequently done, and there are several
techniques used to do so. Some operators use a practical rule of a certain amount
of current per unit of area (1 ma per square foot is typical) to obtain an estimate to
be confirmed through the voltage log record. Others use the E log I test
described in the next paragraph to make an estimate.
8.5.7
Basically, the E log I test consists in applying current increments to the well
casing during fixed time intervals, usually two or three minutes. After each time
interval, the current is interrupted and an immediate open circuit potential of the
casing to the reference electrode in the surface is obtained. These data, plotted in
log-log paper, gives a curve similar to that shown in figure 1. Due to theoretical
considerations, the current given by the intersection of two straight portions of
this curve (point A on Fig. 1.) should indicate the proper current to polarize, that
is, to protect the casing. Due to other considerations, and a better correlation with
the effect of the currents applied in the casing potential profile, in practice it is
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Table of Contents
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume
DATE
AUG.93
Page 14
more common to use the value of the current in the first point that falls on the
second straight portion of the curve (Point B) in the design of cathodic protection
systems for well casing.
The current well casing requirements, with few exceptions, fall between 1 and
25 amps. Lower requirements may be frequently supplied using galvanic anodes.
In many cases, the soil resistivity is too high for galvanic anodes, even for small
currents, and then an impressed current system is necessary. For economic
reasons, a rectifier-anode bed unit is frequently installed to care for several well
casings at a time, whether through negative connections to the different wells,
or using the pipes as conductors to the wells. In any case, the well casing
must be isolated from the flow pipe. A current control resistance may be
placed through this isolating accessory to drain a small current from the
flow line to the well (to achieve some cathodic protection to the flow line, while
eliminating any possible cathodic interference in it,). Alternatively, the current may
be drained from the well to the flow line where the latter has been used as a return
current conductor to the negative rectifier.
9.1.2
In uncased lines, cathodic protection isnt justified, except under very corrosive
conditions. These could be refurbished, cased, and subjected to a full cathodic
protection, as has been mentioned, or they could be studied through the
surface potential log technique (two electrodes and then apply protection to
hot spots with galvanic anodes. The areas known as leaks or hot spots
may be treated satisfactorily through galvanic anodes, particularly if there are no
other areas with problems.
9.1.3
The main and secondary pipes are usually studied and protected if they are not
cased, or are subject to total cathodic protection if they are cased. Almost all new
pipelines that are important are well cased, making the cathodic protection very
economical and relatively simple.
9.1.4
Any pipe for which a full cathodic protection is required must be electrically
isolated (using joints, flanges, couples, or nipples) so that the cathodic
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Table of Contents
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume
DATE
AUG.93
Page 15
protection current is confined to the target structure. For example, even a metallic
contact with a well casing without cathodic protection would cause a
substantial loss of protection in the flow line, due to the deviation of the
cathodic protection current to the casing, which has become part of the
cathodic protection circuit.
9.2.2
The typical protection current densities vary between 5 and 10 ma/square feet,
and the selection of the current source depends mainly on the availability of
alternating current. Occasionally direct current generators or alternators have
been used (with rectifiers) mounted on the pumping unit.
9.2.3
9.2.4
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
DATE
AUG.93
Page 16
Aluminum anodes have a smaller output but still enough, in salt areas of oil
fields, maintaining the current with efficiency between 60% and 70%.
9.2.6
9.2.7 Salt water storage tanks are usually protected from inside corrosion through
cathodic protection only, or a combination of coating and cathodic protection.
Whenever coating is used, it is important not to maintain a potential that is too high
through the coating layer, because blisters may occur causing severe damage.
This could easily happen if improper adjustments to the rectifying system are
made, and even magnesium anodes will develop damaging potentials unless
the current outflow is properly restricted. Again, aluminum with its low potential
provides a safe and better source of protection current for lined vessels.
9.2.8
Both the galvanic and the graphite anodes are typically suspended from the
tanks cover plates through special mountings on the plates. Thus, the anodes
may be easily inspected and replaced.
9.2.9 The outside bottom of production and storage tanks are in contact with the
soil, and although they arent usually corrosive, they frequently have this
condition due to salt water leakage or spillage. Thus, the protection of the
external tank bottom is important, whether with galvanic anodes located on the
ground around the tank, or installing impressed current. In smaller facilities it is
frequently possible to design an internal and external cathodic protection system,
using a simple rectifier. For larger systems it is better to use separate cathodic
protection systems, due to the issue of current control between very different
electric resistance circuits, where there are high currents involved.
9.2.10
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
Contents
DATE
AUG.93
Page 17
Given that small tanks or groups of tanks can be well protected with
galvanic anodes, the usual practice is to use large rectifying units together
with graphite or iron-silicon anodes, and distribute the necessary amounts
of current for the cathodic protection of these large areas of steel. A current
density of 1 ma/square foot is usually adequate, if the current is well
distributed.
c.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
Contents
Volume Table of
DATE
AUG.93
Page 18
have a potential between 0.15 V and 0.25 V greater (more negative) than the
minimum 0.85 V at the edge, to ensure that the central area will be close to or
at 0.85 V.
d.
e.
Recently, submarine steel oil storage tanks have been developed. These
tanks are of course subject to internal and external corrosion due to the
sea water. Since these are essentially marine structures, their protection
will be discussed in the upcoming off-shore equipment section:
The oil industry has made a great investment in off-shore drilling and
production structures, both fixed and floating (movable), including several
types of maritime terminals The corrosion of these structures has been a
very costly issue, and in the last 20 years many lessons have been learnt
regarding corrosion rates, the design of structures to minimize the damage
caused by corrosion, and the methods to fight corrosion.
9.4.2
Corrosion in off-shore structures can be divided into four zones of attack. There
are differences regarding the corrosion rate in the same zone: the four zones
are:
a. The mud zone, that is, the part of the structure below the bottom of the sea.
b. The submerged zone or underwater, where the metal is always covered with
water.
c. The splash zone, above the water level where the wave action usually keeps the
metal humid.
d. The spray zone, where the metal appears to be dry most of the time.
9.4.3
In the mud zone, the lack of oxygen tends to keep corrosion at a low level,
typically less than one mil per year
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
Volume Table
DATE
AUG.93
Page19
9.4.4
9.4.5
Any action of the sand or sediments at the mud line, due to the waves or water
currents, will significantly worsen the corrosion caused by abrasion. This is called
erosion-corrosion.
The spray zone appears to be dry, but there is always a small layer of salt on
those surfaces. Nighttime is the moment of greater corrosion activity in spray
zones. As the structure cools during the night and moisture increases, the salt
absorbs water from the air and the surface is quickly covered by a moist and
salty layer. The sun dries the moisture and reduces the rate of corrosion. The
layer caused by corrosion tends to fall off in layers, and this irregular
spalling of oxide promotes pitting. In general, the pitting is deeper on the shady
side of a structure than on the upper surfaces exposed and dried by the sun.
Corrosion control is achieved by using quality coatings on those surfaces
9.4.8
9.4.9
Typical impressed current systems use rectifiers with a large current outlet to
minimize the number and the space occupied by those units. The anode
material mostly used in the last years is an alloy of lead with 6% antimony and
1% silver, which has a typical consumption rate of 0.1 lb./ampyear.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Main Menu
of Contents
Volume Table
DATE
AUG.93
Page 20
Other anode materials used with some success are platinum-lead, graphite, and
an iron silicon-chrome alloy. Silver-antimony-lead anodes may be suspended or
placed on special steel supports to keep them well fastened to the submerged
elements of the platform. Suspended systems are somewhat more susceptible to
mechanical damage, but are easy to install and maintain.
9.4.10
Almost all galvanic anode systems installed in new structures use aluminum
anodes for the economic reasons previously mentioned in this chapter. The
anodes may be selected for a lifetime of 5, 10 or 20 years, and the shorter life
systems are more frequently selected for the movable equipment, and when their
replacement isnt problematic. Fixed structures have systems with 10 or 20 years
of duration, placed during their manufacturing process. Suspended magnesium
anodes are used where systems with a shorter lifetime are preferred, usually 1 1/2
to 2 years. These are frequently converted later on to systems that last 10 years using
aluminum anodes installed by divers.
9.4.11
Submarine oil storage units are frequently used in deep waters off-shore. Like
submergible drilling structures, they require internal and external protection. The
difficulty to maintain the electrical connections and the impressed current anodes
internally has led to the almost exclusive use of galvanic aluminum anodes for
the cathodic protection of the internal surfaces. The external cathodic protection
can be either impressed current or galvanic anodes, depending on each
specific case.
9.4.12 The dock, the columns, the breakwaters, etc., frequently have severe
corrosion, even in fresh water if it is flowing. Here the presence of alternating
current almost always leads to the installation of impressed current protection
systems. In known corrosive areas, particularly those where the current
density for cathodic protection is greater than normal due to contaminated water,
it is economically justified to coat the steel elements or pilots of those structures
before starting the construction. Impressed current anodes may be of the
different types described, and some constant current rectifiers have been used
in areas where the salinity is variable. Given the variability of some of the factors
affecting the design of cathodic protection for these structures, engineers
specializing in corrosion must deal with this issue, who must consider the
potential danger that unprotected vessels containing oil or oil products create
when fixed to a protected structure.
ENGINEERING GUIDE
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
Table of Contents
Main Menu
Manual Table of Contents
Standard Table of Contents
Volume
DATE
AUG.93
Page 21
10.2
10.3
10.4
The most widely used criterion to determine if the interference has been alleviated
in an extraneous structure is to restore the potential of the structure to the
electrolyte, at the point of discharge of the current, taking it to its initial value,
that is, the level it had before the cathodic protection system was energized.
10.5
GUIA DE INGENIERIA
PDVSA 90618.1.072
REVISION
CATHODIC PROTECTION
DATE
AUG.93
Page 22
Main Menu