Professional Documents
Culture Documents
083
UMG 104
Operating manual and
technical data
www.janitza.com
Power Analyser
Temperature
measurement
input
RS232 RS485
2 digital inputs
2 digital outputs
Power supply voltage
AB
Profibus
(optional)
4 x current
measurement
4 x voltage
measurement
UMG 104
General Information
Protected trademarks
Meaning of the symbols used
Installation 22
4
5
Installed position
22
Power supply voltage
23
Current measurement
24
Ammeter 26
Direct measurement
28
Voltage measurement
29
Interfaces 32
RS485 34
RS485 profibus DP V0 slave
36
Digital inputs and outputs
38
Temperature measurement input
42
Inspection on receipt
Scope of supply
Available accessories
Notes on Use
7
7
8
Product Description
10
Intended use
UMG104 features
Methods of measurement
Operating concept
GridVis programming software
Three-phase 4-wire systems
Three-phase 3-wire systems
10
11
12
12
13
14
16
Use 18
Key functions
Concealed key (service)
Display mode
Programming mode
Display password
18
18
19
20
21
43
43
43
44
45
45
46
Configuration 47
Current transformer ratio
47
Current measurement connection options 48
Voltage transformer ratio
49
Voltage measurement connection options 50
Interfaces 51
RS232 51
RS485 51
Profibus (optional)
52
Recordings 55
UMG 104
System information
56
Overrange 56
Serial number
57
Date 57
Firmware release
57
Time 57
58
Appendix 76
Measured value displays
Declaration of conformity
Dimensioned drawings
UMG104 connection example
76
77
78
79
80
Technical specifications
62
General information
62
Ambient conditions during operation
62
Transport and storage
62
Power supply voltage
63
Protection class
64
Inputs and outputs
65
Temperature measurement input
66
Interfaces 67
Measurement uncertainty
68
Measuring inputs
70
Voltage measurement
70
Parameter list
72
UMG 104
General Information
Protected trademarks
All trademarks and their resulting rights belong
to the respective holders of these rights.
UMG 104
c
m
Dangerous voltage!
Danger or risk of severe injury.
Disconnect the system and device
Note.
UMG 104
Inspection on receipt
Fault free and safe use of this device requires
appropriate transport, proper storage, erection
and assembly as well as careful operation and
maintenance. If it can be assumed that safe
operation is no longer possible, the device
must be immediately taken out of service and
secured against being accidentally started
up.
The device must be unpacked and packed
with the usual care, without the use of force
and only using suitable tools. The devices
must be visually inspected for perfect
mechanical condition. Please also note and
follow the installation instructions enclosed
with the device.
It can be assumed that safe operation is no
longer possible if the device, e.g.
has visible damage,
no longer works, despite intact mains power
supply,
has been exposed to unfavourable conditions
(e.g. storage outside the permissible climatic
limits without adjustment to the ambient
climate, condensation, or similar) for a lengthy
period or was exposed to unfavourable effects
or loads during transport (e.g. fall from a large
height even if there is no visible external
damage, or similar).
6
UMG 104
Scope of supply
Number Product No.
Name
1
52 20 xxx1)
1
33 03 083
1
51 00 116
1
10 01 807
1
10 01 808
1
10 01 809
1
10 01 810
1
89 10 051
1
52 00 008
UMG104 XX2)
Installation and start-up instructions.
CD with the following content:
- GridVis programming software,
- Functional descriptions, GridVis, UMG104 ..
- GSD file 0B41.GSD for profibus DP V0
Screw-type terminal, plug-in, 2 pin.
Screw-type terminal, plug-in, 3 pin.
Screw-type terminal, plug-in, 5 pin.
Screw-type terminal, plug-in, 6 pin.
Slot-head screwdriver (0.40x2 mm), ESD
RS485, external terminating resistor, 120 ohm
Available accessories
Product No.
Name
21 01 102
08 02 427
UMG 104
Notes on Use
Please read these operating instructions and
all other publications which have to be used
to work with this product (in particular for
installation, operation or maintenance).
Note and follow all safety instructions as well
as any warnings. If you do not follow the
instructions, personal injuries and/or damage
to the product could be the result.
Any unauthorised change or use of this device
which extends beyond the given mechanical,
electrical or other operating limits can cause
personal injuries and/or damage to the
product.
Any such unauthorised change is misuse
and/or negligence under the product's
warranty and therefore excludes the warranty
for cover of possible resulting injuries or
damage.
UMG 104
c
m
m
Important!
If the device is not operated according
to the instruction manual, protection
is no longer ensured and the device
can cause hazards.
UMG 104
Product Description
Intended use
The UMG104 is intended to be used for the
measurement and calculation of electrical
variables such as voltage, current, energy,
work, harmonic components, etc. in building
installations, at distribution boards, circuitbreakers and busbar trunking systems.
Measuring-circuit voltages and currents must
originate from the same system.
10
UMG 104
UMG104 features
- Measurement in IT, TN and TT systems,
- 4 voltage measurement inputs
- 4 current measurement inputs,
- Continuous scanning of the voltage and current measurement inputs,
- Energy measurement, measurement uncertainty class 0.5 for ../5A current transformers,
- Energy measurement, measurement uncertainty class 1 for ../1A current transformers,
- Registers more than 800 measured values (readings),
- Fourier analysis 1st to 40th harmonic component for U, I, P (consumption/supply) and Q
(inductive/capacitive),
- 2 digital inputs,
- 2 digital outputs,
- Temperature measurement input,
- LC display, backlight (optional),
- 2 keys,
- Profibus DPV0 (optional),
- RS485 (modbus RTU),
- RS232,
- Operating temperature range -10C .. +55C,
- Mounting on top hat rails 35 mm,
- Suitable for installation in distribution boards,
- Suitable for measurements in networks with frequency inverters.
11
UMG 104
Methods of measurement
Operating concept
m
12
UMG 104
PC
UMG
104
GridVis features
RS232
Interface
converter
RS232
PC
RS485
UMG
104
13
UMG 104
UL-N / UL-L
66 V / 115 V
120 V / 208 V
127 V / 220 V
220 V / 380 V
230 V / 400 V
240 V / 415 V
260 V / 440 V
277 V / 480 V
14
UMG 104
L1
230/400V 50/60Hz
L1
L2
240V
50/60Hz
L3
N
PE
L4 L1 L2 L3 N
Earthing the
system
4M
4M
4M
4M
4M
AC/DC
DC
Voltage measurement
Auxiliary power
UMG104
15
UMG 104
UL-L
66 V
115 V
120 V
127 V
200 V
230 V
240 V
260 V
277 V
347 V
280 V
400 V
415 V
440 V
480 V
16
UMG 104
L1
L1
L2
400V 50/60Hz
230/400V 50/60Hz
L2
L3
L3
N
Impedance
Impedance
L4
L1
L2 L3 N
L4
L1
L2 L3
Voltage measurement
UMG104 Auxiliary power
4M
4M
4M
Earthing the
system
4M
DC
AC/DC
4M
4M
4M
4M
4M
Earthing the
system
4M
AC/DC
DC
Voltage measurement
UMG104 Auxiliary power
17
UMG 104
Use
The UMG104 has a display, keys 1 and 2 and
the Service key to make it easier to install and
start up the UMG104 without a PC.
Important parameters such as current
transformers and device address are included
in the parameter list (see Appendix) and can
be directly programmed at the device.
A differentiation is made between operation
with the
display mode and
Programming mode.
Key functions
Press the key briefly:
page forwards
Digit/value +1
Press the key for long time:
page backwards
Digit/value -1
Simultaneously press both keys for around
1second and keep them pressed:
Switch between display mode and
programming mode.
18
Display
Key 1
Key 2
Concealed key
Keys 1 and 2
1
UMG 104
Display mode
After the power supply is resumed the device
is in Display mode.
In Display mode you can use Keys 1 and 2 to
page between the measured value displays.
1
N L1
V
Hz
Important!
The user can use the GridVis/Jasic to
reconfigure the function of the keys
and selection of the values to be
displayed.
UMG 104
Programming mode
The most important settings required for
operation of the UMG104 can be displayed
and changed in programming mode.
The parameter list in the Appendix contains
the addresses for the most important settings.
You can make further settings using the GridVis
software included in the scope of supply.
If you simultaneously press Keys 1 and 2 for
around 1 second, programming mode opens
via a password query. If a display password has
not been programmed, the first programming
menu opens directly.
Programming mode is denoted in the display
by the text PRG. The digits of the address
flash.
If you are in programming mode and have not
pressed a key for approximately 60 seconds or
simultaneously press Keys 1 and 2 for around
1 second, the device returns to display mode.
20
PRG
Address
Content
UMG 104
Display password
You can program a 4-digit display password
to make it difficult to accidentally change the
programming data directly at the device. A
display password is not set in the factory.
PRG
Content
Addr. Content
500
Display password
0 =the password is not queried.
21
UMG 104
Installation
Installed position
The UMG104 can be installed in control
cabinets or in small distribution boards
according to DIN 43880. It is mounted on a
35mm mounting v according to DIN EN60715.
It can be installed in any position.
22
UMG 104
Power supply
voltage Uh
Fuse
Disconnecting device
-
A disconnector or circuit-breaker
must be provided for the power
supply voltage in the building
installation.
- The disconnector must be installed
near the device and must be easy
for the user to reach.
-
The switch must be labelled as
a disconnecting device for this
device.
-
Voltages which are above the
allowable voltage range can destroy
the device.
m
c
Important!
The inputs for the supply voltage are
dangerous to touch!
23
UMG 104
Current measurement
The UMG104 is designed for the connection of
current transformers with secondary currents
of ../1A and ../5A. Only alternating currents,
not direct currents, can be measured.
Each current measurement input can be
permanently loaded with 6A or for 1 second
with 100 A.
L1
S1
L2
L3
N
c
m
c
24
Attention!
The current inputs are live.
S2
S1
S2
S1
Loads
S2
S1
S2
Important!
The UMG104 is not suitable for the
measurement of direct voltages.
Earthing current transformers
If a connection is provided for earthing
the secondary winding, this must be
connected with earth.
UMG 104
Current
Current
Current
Current
UMG 104
Ammeter
If you not only want to measure the current
with the UMG104 but with an ammeter also,
the ammeter must be connected in series to
the UMG104.
26
UMG 104
Example
The current is measured via two current
transformers. Both current transformers
have a transformation ratio of 1000/5A. The
summation measurement is performed with a
5+5/5A summation current transformer.
The UMG104 must then be set as follows:
Primary current: 1000A + 1000A = 2000A
Secondary current:
5A
27
UMG 104
Direct measurement
Nominal currents up to 5 A can also be
measured directly with the UMG104.
In this case it must be noted that each
current measurement input may be loaded
continuously with 6 A or for 1second with max
100 A.
As the UMG104 does not have any integrated
protection for the current measurement, this
protection (e.g. 6A fuse type C) must be
provided for during installation.
28
UMG 104
Voltage measurement
The UMG104 is designed for the measurement
of alternating voltages in 300 V systems in
which category III overvoltages can occur.
The UMG104 can only determine exact
measured values if a measurement-current
voltage greater than 10 Veff is applied to the
voltage measurement input L1.
The following must be noted when selecting
the instrument leads for the voltage
measurement:
The instrument leads required for the
voltage measurement must be suitable
for voltages up to 300 VAC to earth and
520VAC conductor to conductor.
Normal instrument leads must be fused by
an overcurrent protective device and routed
via disconnectors.
Short-circuit proof instrument leads must be
routed via disconnectors only.
Overcurrent
protective
devices
and
disconnectors must be positioned near the
device and must be easy for the user to
reach.
Disconnector
10A
(UL listed)
N
L3
L2
L1
Fig. 30.1 Connection example: Voltage measurement via short-circuit proof instrument leads.
c
m
Important!
The voltage measurement inputs are
hazardous live!
Important!
The UMG104 can only determine
exact measured values if a measurement-current voltage greater than
10 Veff is applied to the voltage
measurement input L1.
29
UMG 104
Voltage
Voltage
Voltage
Fig. 31.1 Connection examples for voltage measurement in three-phase 4-conductor systems.
(Connection option 0, see page 51)
Voltage
Voltage
Fig. 31.2 Connection examples for voltage measurement in three-phase 3-conductor systems.
(Connection option 1, see page 51)
m
30
Measuring-circuit
voltages
and
currents must originate from the same
system.
Important!
Voltages above 300 VAC to earth
must be connected via voltage
transformers.
UMG 104
S2
L4
4w 1m
I4
S1
L1
L1
L2
L2
L3
L3
S2
L4
3w 1m
S2
L4
2w 1n
PE
UMG 104
Interfaces
RS232
Shielding
m
C
32
Important!
Profibus, RS232, RS485 and
temperature measurement input are
not metallically separated from each
other.
UMG 104
PC
UMG104
Com1
Mini Combicon,
5 pin
33
UMG 104
RS485
Bus structure
Terminating resistors
RS485 Bus
AB
Correct
A
B
Incorrect
UMG 104
Shielding
A twisted-conductor and shielded cable must
be provided for connections via the RS485
interface. The shielding at both ends of the
cable must be connected to a large area of
the mounting plate or cabinet parts in order to
achieve an adequate shielding effect.
Cable type
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cables)
Unitronic BUS L2/FIP 1x2x0.64 (Lapp cables)
Cable length
1200 m for a baud rate of 38.4 k
C
m
For the wiring of the Modbus connection, CAT cables are not suitable. Please use the recommended
cables.
Important!
Profibus, RS232, RS485 and
temperature measurement input are
not metallically separated from each
other.
35
UMG 104
36
UMG 104
UMG104
Terminating resistors
D-sub,
9 pin,
socket
D-sub,
9pin,
connector
Other
profibus
stations
Screw-type terminals
UMG 104
m
38
Attention!
The digital outputs are not shortcircuit-proof.
24V
DC
+
UMG 104
24V
AC
~
~
24V
DC
Digital outputs
18
K1
Digital
Output 2
17
16
Digital
Output 1
K2
Digital
Output 1
16
Digital
Output 2
17
18
K1
Digital outputs
UMG104
K2
UMG104
39
UMG 104
Digital inputs
UMG104
24V
DC
- +
S1
S2
+
24V
=
-
40
Digital
Input 2
20
3,9V 4,4k
3,9V 4,4k
21
m
Fig. 40.1 Connection example.
Digital
Input 1
19
Attention!
The polarity of the feeding voltage
must be respected for the digital
inputs.
UMG 104
S0 pulse input
UMG104
24V
DC
- +
S0 pulse generator
1,5k
+
24V
=
-
Digital
Input 2
20
1,5k
3,9V 4k
3,9V 4k
21
UMG 104
KTY83
42
m
m
UMG 104
Frequency measurement
UMG 104
Minimum voltage
A measuring-circuit voltage greater than
10Veff must be applied to at least one
of the voltage measurement inputs. If an
adequately high measuring-circuit voltage
is not applied on the measuring input V1 the
UMG104 cannot determine exactly the system
frequency and can therefore also not take a
exactly measurement.
44
At least one phase (L) and the neutral conductor (N) must be connected to the voltage measurement input for the measurement.
UMG 104
Phase sequence
Check the direction of the voltage rotating field
in the measured value display of the UMG104.
A right rotating field usually exists.
45
UMG 104
46
UMG 104
Configuration
Current transformer ratio
You can assign each of the 4 current
transformer inputs its own current transformer
ratio. A current transformer ratio of 5 A/5 A
is programmed in the factory for all 4 current
transformer inputs.
You can program current transformers with the
same current transformer ratios in addresses
000 and 001. Program current transformers
with different current transformer ratios in
addresses 010 to 041.
A change in current transformer values in
address 000 or 001 overwrites the contents
of addresses 010 to 041 with the current
transformer values from addresses 000 and
001.
Address
000
001
L1 L2 L3 L4 (primary)
L1 L2 L3 L4 (secondary)
010
011
020
021
030
031
040
041
L1 (primary)
L1 (secondary)
L2 (primary)
L2 (secondary)
L3 (primary)
L3 (secondary)
L4 (primary)
L4 (secondary)
47
UMG 104
Connection option 0
Connection option 1
C
48
Address
Connection option
110
0=T
hree current transformers.
(Default factory setting)
1=T
wo current transformers
(Aron circuit)
UMG 104
Address
002
003
L1 L2 L3 L4 (primary)
L1 L2 L3 L4 (secondary)
012
013
022
023
032
033
042
043
L1 (primary)
L1 (secondary)
L2 (primary)
L2 (secondary)
L3 (primary)
L3 (secondary)
L4 (primary)
L4 (secondary)
49
UMG 104
Address
Connection option
111
0=T
hree-phase 4-conductor
systems (default factory
setting)
1 = t hree-phase 3-conductor
systems
Connection option 0
Connection option 1
C
50
UMG 104
Interfaces
The UMG104 has 4 serial interfaces:
- RS485
- RS232
- Profibus (optional)
All interfaces can be used simultaneously.
RS232
The following data must be programmed for
use of the RS232 interface:
- Baud rate,
- Operating mode.
Refer to the parameter list in the Appendix
for the default factory setting and the setting
ranges.
RS485
The following data must be programmed for
use of the RS485 interface:
- Device address,
- Baud rate,
- Operating mode.
Refer to the parameter list in the Appendix
for the default factory setting and the setting
ranges.
Addr.
Content
200
51
UMG 104
Profibus (optional)
Profibus profiles
The UMG104 can manage 16 profibus profiles. Each profibus profile contains 128 data
bytes maximum.
Content
200
52
PLC
Output area of the programmable controller
1. Byte = profile number
The variables for the
UMG104 follow from the
2nd byte.
Input area of the programmable controller
1. Byte = profile number
feedback
The requested variables
for the UMG104 follow
from the 2nd byte.
UMG104
UMG 104
Byte
Index Value type
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
1
5
9
13
17
21
25
29
33
37
41
45
49
53
57
61
65
69
73
77
81
85
89
93
97
101
105
109
113
117
Voltage L1-N
float
Voltage L2-N
float
Voltage L3-N
float
Voltage L4-N
float
Voltage L2-L1
float
Voltage L3-L2
float
Voltage L1-L3
float
Current L1
float
Current L2
float
Current L3
float
Current L4
float
Effective power L1
float
Effective power L2
float
Effective power L3
float
Effective power L4
float
Cosphi (math.) L1
float
Cosphi (math.) L2
float
Cosphi (math.) L3
float
Cosphi (math.) L4
float
Frequency
float
Effective power total L1-L4
float
Reactive power L1-L4
float
Apparent power total L1-L4
float
Cosphi (math.) total L1-L4
float
Effective current total L1-L4
float
Effective consumption total L1-L4 float
Ind. reactive consum. total L1-L4 float
THD voltage L1
float
THD voltage L2
float
THD voltage L3
float
Scaling
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Byte-
Index Value type
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
1
5
9
13
17
21
25
29
33
37
41
45
49
53
57
61
65
69
73
77
81
85
89
93
97
101
105
109
113
Values
format
Voltage L1-N
Float
Voltage L2-N
Float
Voltage L3-N
Float
Voltage L2-L1
Float
Voltage L3-L2
Float
Voltage L1-L3
Float
Current L1
Float
Current L2
Float
Current L3
Float
Effective power L1
Float
Effective power L2
Float
Effective power L3
Float
Cosphi (math.) L1
Float
Cosphi (math.) L2
Float
Cosphi (math.) L3
Float
Frequency
Float
Effective power total L1-L3
Float
Reactive power total L1-L3
Float
Apparent power total L1-L3
Float
Cosphi (math.) total L1-L3
Float
Effective current total L1-L3
Float
Effective consumption total L1-L3 Float
Ind. Reactive consum. total L1-L3 Float
THD voltage L1
Float
THD voltage L2
Float
THD voltage L3
Float
THD current L1
Float
THD current L2
Float
THD current L3
Float
Scaling
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
53
UMG 104
Byte-
Index Value type
1
2
3
4
5
6
7
8
9
10
11
12
13
1
5
9
13
17
21
25
29
33
37
41
45
49
54
1
1
1
1
1
1
1
1
1
1
1
1
1
Byte-
Index Value type
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
1
5
9
13
17
21
25
29
33
37
41
45
49
53
53
53
53
53
53
53
53
Values Scaling
Format
Effective power L1
Float
Effective power L2
Float
Effective power L3
Float
Effective power total L1-L3
Float
Current L1
Float
Current L2
Float
Current L3
Float
Current total L1-L3
Float
Effective consumption total L1-L3 Float
CosPhi (math.) L1
Float
CosPhi (math.) L2
Float
CosPhi (math.) L3
Float
CosPhi (math.) total L1-L3
Float
Reactive power L1
Float
Reactive power L2
Float
Reactive power L3
Float
Reactive power total L1-L3
Float
Apparent power L1
Float
Apparent power L2
Float
Apparent power L3
Float
Apparent power total L1-L3
Float
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
UMG 104
Recordings
2 recordings are preconfigured in the default
factory setting of the UMG104. Recordings
are adjusted and extended via the software
GridVis.
Recording 1
The following measured values are recorded
with the time base of 15 minutes:
Recording 2
The following measured values are recorded
with the time base of 1 hour:
Voltage effective L1
Voltage effective L2
Voltage effective L3
Voltage effective L4
Voltage effective L2-L1
Voltage effective L3-L2
Voltage effective L1-L3
Current effective L1
Current effective L2
Current effective L3
Current effective L4
Active Power L1
Active Power L2
Active Power L3
Active Power L4
Active Power Sum L1-L3
Active Power Sum L1-L4
Reactive power fundamental L1
Reactive power fundamental L2
Reactive power fundamental L3
Reactive power fundamental L4
Reactive power fundamental Sum L1-L3
55
UMG 104
System information
Overrange
Overranges are displayed as long as they exist
and cannot be acknowledged. An overrange
exists if at least one of the four voltage or
current measurement inputs lies outside their
specified measuring range.
If an overrange exists it is shown in the display
with EEEE.
The symbols L1, L2, L3 and L4 are used to
indicate at which input the overrange has
occurred. The V and A symbols indicate
whether the overrange occurred in the current
or in the voltage path.
m
56
Important!
Voltages and currents that lie outside
the permissible measuring range can
destroy the device.
L1 L2 L3 L4
VA
UMG 104
Serial number
Firmware release
Date
Time
UMG 104
Front film
The front film can be cleaned with a soft cloth
and standard household cleaning agent. Do
not use acids and products containing acid
for cleaning.
Battery
The internal clock is provided with power
from the power supply voltage. If the power
supply voltage fails the clock is supplied by
the battery. The clock supplies date and time
information, e.g. for recordings and minimum
and maximum values.
The life expectancy of the battery is at least
5 years, at a storage temperature of +45C.
The typical life expectancy of the battery is 8
to 10 years.
The device must be opened to change the
battery. If the device has been opened a
renewed safety check is necessary for safe
58
Disposal
Firmware update
If a firmware update has to be performed for
your UMG104 you can do this with the GridVis
software included in the scope of supply.
Service
Should questions arise, which are not
described in this manual, please contact the
manufacturer directly.
We will need the following information from
you to answer any questions:
- Device name (see rating plate),
- Serial name (see rating plate),
- Software release (see measured value
display),
- Measuring-circuit voltage and power supply
voltage,
- Precise description of the error.
UMG 104
Trouble shooting
Possible error
Cause
Remedy
No display.
Replace fuse.
Device is defective.
No current display.
Displayed
current
is too large or too
small.
EEEE and A
in the display.
59
UMG 104
Possible error
Cause
Remedy
Displayed
voltage
is too small or too
large.
Displayed voltage is
too small.
Overrange.
The peak voltage value at the measurement input has been exceeded
by harmonic components.
EEEE and V
in the display.
60
Voltage transformer
programmed.
incorrectly
Important!
Ensure
the
measurement inputs are not
overloaded.
UMG 104
Possible error
Cause
Remedy
No connection with
the device.
RS485:
- Device address is incorrect.
- Wrong protocol.
- Different bus speed.
- Termination missing.
RS232
- Device address is incorrect.
- Wrong protocol.
- Different bus speed.
- The concealed key
(service) was used.
Device is defective.
61
UMG 104
Technical specifications
General information
Net weight
Device dimensions
Housing flammability class
Installed position
Fixing/mounting
Battery
Backlight lifetime (optional)
: 350g
: approx l=107.5 mm, b=90 mm, h=82 mm
(according to DIN 43871:1992)
: UL94V-0
: any
: 35 mm top hat rail
(according to IEC/EN 60999-1, DIN EN 50022)
: Type VARTA CR2032, 3 V, Li-Mn
: 40000h (50% of initial brightness)
UMG 104
63
UMG 104
Protection class
Class II according to IEC 60536 (VDE 0106, Part 1), i.e. a PE terminal is not required!
Protection against ingress of solid foreign
bodies and water
64
UMG 104
: 20 Hz
: 200 ms
: 18V. 28 V DC (typically 4 mA)
: 0 .. 5 V DC, current less than 0.5 mA
: up to 30 m unshielded
: greater than 30m shielded
: 0.08 - 1.5 mm2
:1
mm2, only one conductor may connected per
terminal connection!
65
UMG 104
: approx 200 ms
: PT100, PT1000, KTY83, KTY84
: max 4 kohm
Sensor type
Temperature range
Resistance range
Measurement
uncertainty
KTY83
KTY84
PT100
PT1000
-55 .. +175 C
-40 .. +300 C
-99 .. +500 C
-99 .. +500 C
1.5% rng
1.5% rng
1.5% rng
1.5% rng
66
: up to 30 m unshielded
: greater than 30 m shielded
: 0.08 - 1.5 mm2
:1
mm2, only one conductor may be connected
per terminal connection!
UMG 104
Interfaces
RS232
Protocol
Transfer rate
RS485
Protocol, modbus RTU
Transfer rate
RS485 (optional)
Protocol, profibus (optional)
Transfer rate
67
UMG 104
Measurement uncertainty
The measurement uncertainty of the UMG104 applies to use of the following measuring ranges.
The measured value must lie within the given limits. Outside these limits the measurement
uncertainty is unspecified.
Measured value
Measurement uncertainties
Voltage
Current L
Current N
Power
Harmonic components U, I
Active energy
Current transformer ../5A
Current transformer ../1A
Reactive energy
Current transformer ../5A
Current transformer ../1A
Frequency
Internal clock
UMG 104
69
UMG 104
Measuring inputs
Voltage measurement
1)The UMG104 can only detect measurement values if a voltage L-N larger than 10Veff or a volt-
age L-L larger than 18Veff is applied to at least one voltage measurement input.
UMG 104
Current measurement
Nominal current
Rated current
Resolution
Measurement range
Crest-faktor
Measurement category
Specified impulse withstand voltage
Power input
Overload for 1 sec
Scanning frequency
:5A
:6A
: 1mA
: 0.001 .. 8.5Arms
: 2 (referring to 6 Arms)
: 300 V CAT III
: 4 kV
: approx 0.2 VA (Ri=5 mohm)
: 100 A (sinusoidal)
: 20 kHz
71
UMG 104
Parameter list
Add Name
Setting range
000
001
002
003
010
011
012
013
020
021
022
023
030
031
032
033
040
041
042
043
72
Units
Default
setting
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 999
A
A
V
V
5
5
400
400
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 999
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 999
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 999
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 999
A
A
V
V
A
A
V
V
A
A
V
V
A
A
V
V
5
5
400
400
5
5
400
400
5
5
400
400
5
5
400
400
UMG 104
Add Name
Setting range
Units
Default
setting
0 .. 9999
0 .. 1
0 .. 1
0 .. 1
112
113
114
0 .. 1
0 .. 1
0 .. 1
-
-
0
0
73
UMG 104
Add Name
Setting range
Units
Default
setting
1 .. 255
0 .. 4
1
4
0 .. 5
0 .. 6
0 .. 6
74
UMG 104
Add Name
Setting range
Units
Default
setting
400 Day
401 Month
402 Year
403 Hour
404 Minute
405 Second
406 Accept date and time
1 = accept set data
500 Device password
1 .. 31
1 .. 12
1 .. 9999
0 .. 23
0 .. 59
0 .. 59
0, 1
xx
xx
xxxx
xx
xx
xx
0
0 .. 9999
xxxx
600
601
602
603
0 .. 99
0 .. 16
0 .. 8
0 .. 9999
50
10
3
60
LCD, Contrast
LCD, Backlight, max. brightness
LCD, Backlight, min. brightness
LCD, Backlight,
Time to switch from maximum to
minimum brightness.
-
-
-
s
75
UMG 104
Voltage
L2-N
Voltage
L3-N
Voltage
L4-N
Voltage
L1-L2
Voltage
L2-L3
Voltage
L3-L1
Current
L1
Current
L2
Current
L3
Current
L4
Active Power
demand L1
Active Power
demand L2
Active Power
demand L3
Active Power
demand L4
Active Power
demand L1..L3
Active Power
demand L1..L4
Reactive
Power L1
Reactive
Power L2
Reactive
Power L3
Reactive
Power L4
Reactive
Power L1..L3
Reactive
Power L1..L4
Active Energy
demand L1..L3
Active Energy
demand L1..L4
cos(phi)
L2
cos(phi)
L3
cos(phi)
L4
cos(phi)
L1..L3
Frequency
Rotating field
Temperature
input
Date
Time
Serial
number
76
Firmware
Release
UMG 104
Declaration of conformity
The product fulfils the following EC Directives:
2004/108/EG
2006/95/EG
Considered standards:
Noise immunity
IEC/EN 61326-1:2013
IEC/EN 61000-4-2:2009
IEC/EN 61000-4-3:2011
IEC/EN 61000-4-4:2013
IEC/EN 61000-4-5:2007
IEC/EN 61000-4-6:2009
IEC/EN 61000-4-8:2010
IEC/EN 61000-4-11:2005
Noise emission
IEC/EN 61326-1:2013
IEC/CISPR11/EN 55011:2011
IEC/CISPR11/EN 55011:2011
Equipment safety
IEC/EN 61010-1:2011
IEC/EN 61010-2-030:2011
77
UMG 104
Dimensioned drawings
Front view
78
Side view
UMG 104
79
UMG 104
Change address
PRG
Address
Content
PRG
80
Address
Content