PRESENTATION
PILLARD ROTAFLAM
Burner Adjustment ( 1989 2002 )
Gaseous fuels
Liquid fuels
Pulverized fuels
Total combustion air = min combustion air for max (designed) burner capacity + 10% air excess
- All primary air dampers at the burner should be 100% open, incl. fan-inlet and outlet.
- The normal position of all burner cross-sections is the 0 position.
- To influence the flame shape they should only be retracted from the 0 position to minus.
- Adjustment > 0 is not recommendable and may have negative influence on the flame because
part of the impulse is lost.
- The flame stabilizer (central air tube) should always be retracted to position 10 / - 15 mm for
protection against damage by heat radiation of the flame. The quantity of central air is only
about 0,5 % of the primary air. The influence on the flame shape is not very big but the
central air is useful for the stabilization of the flame near the burner outlet.
PILLARD FEUERUNGEN GmbH - Aarstrae 168, 65232 Taunusstein - Tel.: 061282420 - Fax: 06128242112 - Mail: info@pillard.de - Web: www.pillard.de
2 of 5
Normal flame:
*All burner tip cross-sections (except of central: -10 / -15 mm) in 0 position.
*Differential pressure (primary secondary pressure) at the oil nozzle 1,0 to 2,0 bar.
PILLARD FEUERUNGEN GmbH - Aarstrae 168, 65232 Taunusstein - Tel.: 061282420 - Fax: 06128242112 - Mail: info@pillard.de - Web: www.pillard.de
3 of 5
Soft flame:
*Reduce axial air and reduce swirl air
PILLARD FEUERUNGEN GmbH - Aarstrae 168, 65232 Taunusstein - Tel.: 061282420 - Fax: 06128242112 - Mail: info@pillard.de - Web: www.pillard.de
4 of 5
All changes of operation conditions and burner adjustments should be done one by one, in small steps, with an
observation time of minimum 24 hours after each adjustment, to be able to see the reaction of the process!
Never change two or more conditions at the same time!
Adjustment of the burner tip is only recommendable in stable kiln operation!
PILLARD FEUERUNGEN GmbH - Aarstrae 168, 65232 Taunusstein - Tel.: 061282420 - Fax: 06128242112 - Mail: info@pillard.de - Web: www.pillard.de
5 of 5