SDMO
Control unit
TELYS
V 6.1.0 (16/11/2006)
33502019901_0_1
33502019901_0_1
1/88
1. Introduction to TELYS
1.1. Introduction
TELYS is a command / control module designed to control the generating set.
This module, with a 12V or 24V direct current supply, is incorporated into the following control consoles:
NT 2500
Circuit breaker rating 125 A
NT 3500
Circuit breaker rating 250 A
NT 4500
Circuit breaker rating 250 A (1)
33502019901_0_1
2/88
33502019901_0_1
3/88
2. Description
2.1. Standard configuration
The TELYS module is composed of a polycarbonate cover plate, a screen, signalling LEDs, control components and
electronic boards.
The functional connections are as follows:
Voltage/Current
Measurements
Input/Output Board
Engine
Alternator
33502019901_0_1
4/88
13
12
10
11
Emergency stop button for switching off the generating set in the event of a fault which could endanger personnel
or damage equipment
Key switch for starting up/shutting down the module
Electronic board protection fuse
Scrolling and selection wheel for scrolling through screens and selecting items simply by pressing the wheel
STOP button, press to switch the generating set off
START button, press to switch the generating set on
Power ON LEDs and fault warning LEDs
Location of USB ports
Mounting bolt.
LCD for displaying alarms and faults, operating status, electrical and mechanical quantities.
ESC button: return to the previous selection and fault RESET function
MENU button to access the menus
Lighting for emergency stop button
33502019901_0_1
5/88
1
2
USB key connection (HOST): file transfer between US key and TELYS and vice-versa
Connection for microcomputer (DEVICE):
file transfer between PC and TELYS and vice-versa
main module power supply
Protective cover.
33502019901_0_1
6/88
J21
J24
J1M
J20
J23
J14
J15
J5
J1
J33B
J3M
J27
J18
J25
J17
J16
33502019901_0_1
7/88
33502019901_0_1
8/88
o
SERIAL No.: 08030010000
SOFTWARE: 5.3.5
NOMINAL VOLTAGE: 400V
FREQUENCY: 50Hz
NOMINAL KW: 320kW
EARTH SYSTEM: TNS
q
Fig. 2.5 Description of the screen (example)
n Zone 1:
o Zone 2:
33502019901_0_1
9/88
Display
Fixed
"MANUAL" Mode
Flashing
Fixed
Activation conditions
TELYS
in
manual
mode
(MANUAL)
For 5 seconds when switching from
AUTO mode to MANUAL mode
TELYS in automatic mode (AUTO)
Flashing
Flashing
Fixed
Fixed
"AUTO" Mode
Maintenance indicator
(available 1st half of 2007)
Fixed
Flashing
Fixed
Not used
33502019901_0_1
10/88
Alarm
Low
level
fault
Alarm / Fault
high fuel level
High
level
fault
alarm
Min battery
voltage
(flashing)
Oil pressure
Alarm / Fault
No
preheating
fault alarm
Battery
charge
indicator
(flashing
bars)
Max battery
voltage
(flashing)
Oil pressure / temperature indicator
High or low oil
level
Alarm /
Fault
Emergency stop
Overspeed fault
33502019901_0_1
Non-starting
fault
11/88
Pictograms
Data displayed
Fuel Level Indicator
Indication of Temperature of High Temperature coolant
(HT) (units according to settings menu)
P1
Generating set start-up or generating set started or generating set switching off in progress
Screen no.
Pictograms
Data displayed
Engine Speed Indication
Indication of Temperature of High Temperature coolant
(units according to settings menu)
P2
Pictograms
Data displayed
Fuel Level Indicator
P3
Default
screen in
operation
P4
U31 Alternator composite Voltage Indicator
Alternator Frequency Indicator
33502019901_0_1
12/88
Screen no.
Pictograms
Data displayed
V1 Alternator single Voltage Indicator
V2 Alternator single Voltage Indicator
P5
V3 Alternator single Voltage Indicator
Alternator Frequency Indicator
U12 Alternator composite Voltage Indicator
V2 Alternator single Voltage Indicator
P6
V1 Alternator single Voltage Indicator
Alternator Frequency Indicator
P8
Three phase Alternator current indicator
Neutral Alternator current indicator
Total Active Power Indicator
Total Reactive Power Indicator
P9
Total Effective Power Indicator
Total Power Factor Indicator (lagging or leading)
33502019901_0_1
13/88
Screen no.
Pictograms
Data displayed
Fuel Level Indicator
P10
Screen order of appearance according to network type with the generating set on.
Order of appearance
1
2
3
4
5
6
7
3P+N
P3
P4
P5
P8
P9
P2
P10
3P
P3
P4
P8
P9
P2
P10
Type of network
2P+N
P3
P6
P8
P9
P2
P10
1P+N
P3
P7
P9
P2
P10
Screen
G1
G2
Data displayed
33502019901_0_1
14/88
Screen
Data displayed
OPERATION
MANUAL
G3
Press START
to start
24/08/2005
13:12
OPERATION
AUTO
G4
WARNING
START-UP POSSIBLE
IMMEDIATELY
24/08/2005
13:12
WARNING
G5
AUTOMATIC Start
19 min 30 sec
24/08/2005
13:12
33502019901_0_1
15/88
Screen
G6
START-UP
IN PROGRESS
24/08/2005
Data displayed
AIR PREHEATING
G7
10 seconds
24/08/2005
13:12
Screen
Data displayed
AVAILABLE POWER
G8
Default
screen
75%
24/08/2005
13:12
AUTOMATIC STOP
IN PROGRESS
G9
LOAD SUPPRESSION
1 min 30 sec
24/08/2005
13:12
33502019901_0_1
16/88
Screen no.
G 10
Screen
Data displayed
AUTOMATIC STOP
IN PROGRESS
COOLING DOWN
1 min 30 sec
24/08/2005
13:14
Generating setstop
Screen no.
Screen
Data displayed
G 11
OFF
IN PROGRESS
24/08/2005
Operating mode changeover (switching from Manual Mode to Auto Mode following auto start demand)
Screen no.
G 12
Screen
Data displayed
Start Demand
AUTO
Do you wish to change
to Auto Mode?
WARNING
Immediate start
OK
Esc
33502019901_0_1
17/88
Generating set stop request due to fault or by pressing STOP in Auto Mode
Screen no.
Screen
Data displayed
Manual Mode
activated
G 13
OK
Esc
2.2. Options
The presence of optional boards indicated on the electrical diagram depends on the options fitted to the generating set.
In order to have additional inputs and outputs, TELYS can be fitted with five logic input/output boards.
The input/output board holds additional logic inputs and outputs (all or nothing), which can be used if those of the basic
module are not sufficient.
These inputs can be used to detect additional alarms or faults and outputs can be used for data transfers or to control
options.
33502019901_0_1
18/88
Composition:
The input/output board comprises 4 inputs and 6 outputs (M1E1 for Module1/Input1 and M1S1 for Module1/Output1).
A green LED is used to indicate the status of each output (output activated).
4 Logic Inutps
Supply LED
12 / 24 V supply
End of line
resistance (2)
3 Logic outputs
3 Logic outputs
(1) CAN bus for connection between the basic board and the input/output boards. The maximum possible length of the
CAN BUS is 200 metres.
(2) CAN connection loopback (factory fitted).
33502019901_0_1
19/88
3. Introduction to menus
4 menus accessible by pressing the "MENU" button allow interaction with the user. The menus displayed depend on the
configuration of the generating set. The menus are the following:
9 "Actions" menu
9 "Information" menu
9 "Settings" menu
9 "Country" menu
Warning
MENUS
1/4
1 ACTIONS
2 INFORMATION
3 SETTINGS
4 COUNTRIES
12
OK
Esc
Selection activated
When the conditions for a menu (or sub-menu) to be displayed are not met, it will not appear.
Display conditions:
o Generating set status (in operation or stopped, MANUAL or AUTO mode)
o Access level (user or installer)
o Generating set equipment (options)
For reasons of operating security, access to the menu contents (settings) is restricted and depends on authorised access
levels. The contents of each access level and the configuration mode of these levels are described in the section entitled
"Access levels".
The tree structure of the menus is describes on the following pages:
33502019901_0_1
20/88
33502019901_0_1
21/88
33502019901_0_1
22/88
33502019901_0_1
23/88
MANUAL Operation
AUTO Operation
O
Function
12
OK
Esc
12 CONTROL LOAD
12
OK
Esc
12
OK
Esc
Min: 0
Max: 99 or =unlimited
12
OK
Esc
33502019901_0_1
24/88
14 PROGRAMMES
1/8
PROGRAMME 1
PROGRAMME 2
PROGRAMME 3
PROGRAMME 4
12
OK
Esc
8 possible programmes
Selection:
Frequency (Not activated, None, Day,
Week, Month or Year)
Load (OFF Load or ON Load)
Programme start and end dates and times
(1)
WARNING
Warning
33502019901_0_1
25/88
2 INFORMATION
5/5
21 GENSETDATA
22 COUNTERS
23 EVENTS
24 PARAMETERS
12
OK
Esc
22 COUNTERS
23 EVENTS
24 PARAMETERS
25 COMMUNICATION
12
OK
Esc
22 COUNTERS
1/3
221 TIMETABLE
TOTAL:
221 TIMETABLE
222 ACTIVE ENERGY
223 REACTIVE ENERGY
12
OK
19358 H 56 min
PARTIAL:
1359 H 30 min
Esc
Esc
33502019901_0_1
hours
of
the
26/88
23 EVENTS
005/101
23/08/06 13:46
Press STOP
FAULT
23/08/06 13:45
Fail to start
12
OK
Esc
24 PARAMETERS
1/7
241 GENERAL DELAYS
242 HORN
243 ALT. VOLTAGE
244 ALT. FREQUENCY
12
OK
Esc
24 PARAMETERS
7/7
244 ALT. FREQUENCY
245 BATTERY VOLTAGE
246 OVERLOAD ALARM.
247 FUEL PUMP
12
OK
Esc
31 COMMUNICATION
1/3
311 RS485 INTERFACE
312 ETHERNET
313 JBUS
12
OK
Esc
RS485 INTERFACE
Speed: in Bauds
Data: in bits
Parity: with or without
STOP: x Bit
ETHERNET
Generating set IP Address
Subnetwork mask
Gateway IP address
DHCP
JBUS
Address
33502019901_0_1
27/88
33502019901_0_1
3 SETTINGS
1/7
31 COMMUNICATION
32 FREQUENCY
33 VOLTAGE
34 50Hz <> 60Hz
12
OK
Esc
3 SETTINGS
6/7
34 50Hz <> 60Hz
35 NOMINAL VOLTAGE
36 PARAMETERS
37 INSTALLER ACCESS
12
OK
Esc
28/88
3.3.1 Communication
This menu is used to configure the communication parameters.
RS 485 INTERFACE
Speed:
Data:
Parity:
Stop:
12
9600 Bauds
8 bits
Without
1 bit
OK
Esc
362 ETHERNET
1/4
3 IP ADDRESS
SUBNETWORK MASK
GATEWAY
DHCP
12
OK
Esc
JBUS
Address:
Min. : 1
Max. : 254
Esc
005
Ok
IP ADDRESS
GensetIPAddress
172 .023.017.201
12
OK
Esc
12
OK
Esc
GATEWAY
Gateway IP address
172 .023.017.200
12
OK
Esc
DHCP
DHCP
NO
Esc
Ok
33502019901_0_1
29/88
3 SETTINGS
4/7
34 50Hz <> 60Hz
35 NOMINAL VOLTAGE
36 PARAMETERS
37 INSTALLER ACCESS
12
OK
Esc
50 Hz
12
OK
Esc
The frequency can only be changed when the generating set is stopped.
Warning
3.3.3 Changing the voltage
This menu permits a new voltage for the power supply from the generating set to be entered in the generating set
configuration (applies to dual voltage generating sets)
The tree structure of the menu is as follows:
NOMINAL VOLTAGE
3 SETTINGS
4/7
400 Vac
34 50Hz <> 60Hz
35 NOMINAL VOLTAGE
36 PARAMETERS
37 INSTALLER ACCESS
12
OK
Esc
Min.:
Max.:
12
380
480
OK
Esc
The voltage must also be changed when the generating set is stopped.
Warning
33502019901_0_1
30/88
SECURE ACCESS
Enter password
* * * *
12
OK
* * * *
12
Esc
Esc
ACTIVE ENERGY
REACTIVE ENERGY
0 h 0 min
RESET?
0 kWh
RESET?
0 kVar
RESET?
Esc
OK
OK
Esc
Esc
OK
OK
05 Sec
Min. : 0
Max. : 99
Esc
MICRO DISCONNECTION
01 Min
Min. : 0
Max. : 99
OK
Esc
MAINS RETURN
Min. : 0
Max. : 99
OK
33502019901_0_1
Esc
OK
31/88
30 Sec
Min: 0
Max: 99
Esc
05 Min
Min: 0
Max: 99
OK
Min: 0
Max: 99
Esc
OK
France only
France only
COOLING DOWN
02 Min
01 Min
Min: 0
Max: 99
Esc
Esc
OK
STOP I>>
02 Min
Min: 0
Max: 99
OK
STANDBY
Min: 0
Max: 99
Esc
OK
Esc
OK
U&F STABLE
05 Sec
Min: 0
Max: 99
Esc
OK
364 HORN
Delay
Fault
Auto start
HORN OFF
HORN
Activated if
Without
05 Min
HORN
Activated on request
AUTO Start
YES
Min: 0
Max: 99
Esc
OK
Esc
Ok
4 possible choices:
Without (deactivated)
Activated for Alarms
Activated for Faults
Activated for Alarms & Faults
33502019901_0_1
Esc
Ok
Possible choices:
YES
NO
32/88
05 Sec
05 Sec
-- V
Min: 0
Max: 99
Esc
Min: 0
Max: 99
OK
OK
Min: 0
Max: 99
OK
Esc
Esc
OK
Min: 0
Max: 99
Esc
Esc
Min: 0
Max: 99
Min: 0
Max: 99
OK
Esc
OK
05 Sec
05 Sec
- - Hz
Min: 0
Max: 99
Esc
Min: 0
Max: 99
OK
Esc
Min: 0
Max: 99
OK
Min: 0
Max: 99
OK
Esc
OK
Min: 0
Max: 99
Esc
Esc
Min: 0
Max: 99
OK
33502019901_0_1
Esc
OK
33/88
01 Sec
01 Sec
-- v
Min: 0
Max: 99
Min: 0
Max: 99
Esc
OK
Min: 0
Max: 99
Esc
OK
Min: 0
Max: 99
OK
OK
Min: 0
Max: 99
Esc
Esc
Min: 0
Max: 99
Esc
OK
Esc
OK
OK
If no value is displayed, this means the corresponding alarm has been deactivated
o
Activation Threshold
20 %
20 %
Min: 0
Max: 99
12
OK
Esc
Esc
Deactiv. Threshold
Min: 0
Max: 99
OK
33502019901_0_1
Esc
OK
34/88
12
OK
Esc
41 LANGUAGES
42 HOURS
43 DATE
44 UNITS
12
OK
Esc
41 LANGUAGES
1/5
41 LANGUAGES
5/5
FRANCAIS
ENGLISH
ESPANOL
PORTUGUES
12
OK
Esc
DEUTCH
12
17
46
Esc
Esc
43 DATE
42 TIME
Hours:
Minutes:
OK
44 UNITS
Day:
26
Month: 10
Year:
2006
Format:
DD/MM/YYYY
OK
List of languages
9 FRANAIS (French)
9 ENGLISH
9 ESPANOL (Spanish)
9 PORTUGUES (Portuguese)
9 DEUTCH (German)
12
OK
Esc
Possible formats:
DD/MM/YYYY
YYYY/MM/DD
33502019901_0_1
Bars
Pressures:
Temperatures:
12
OK
C
Esc
Possible formats:
Pressure: Bar or PSI
Temperature: C or F
35/88
Alarms
OK=HELP
Faults
OK=HELP
Faults have priority over alarms. Faults are displayed in the descending order of their appearance (from the most recent to
the oldest).
33502019901_0_1
36/88
FAULT
ALARM
Low coolant Level
06/10/06 10:30
FAULT
Emergency Stop
06/10/06 15:30
OK=HELP
Esc=RESET
OK=HELP
Press OK (on the scrolling and selection wheel) to access the help message if it is available (example below)
HELP
Esc=EXIT
33502019901_0_1
37/88
Esc=RESET
OK=LIST
The faults list can be accessed by pressing OK (of the scrolling and selection wheel) (examples below)
FAULTS
1/2
FAULT 25/12/05 15:30
Emergency Stop
ALARM 25/12/05 15:30
Low Fuel Level
12
OK=HELP
HELP
Check:
- Emerg. Stop Pos.
- Connector(s)
Esc
33502019901_0_1
38/88
This represents the system or component at fault, for example: SPN 100,
indicates an oil pressure problem or a problem with the oil pressure sensor.
This represents the type of fault that has occurred. This may be an electrical,
mechanical or equipment fault.
This term, used in the J1587 standard, has an equivalent in the J1939 standard
(SPN).
However, this term corresponds, more particularly, to an assembly of
components, for example, the injection system.
This term, used in the J1587 standard, has an equivalent in the J1939 standard
(SPN).
However, this term corresponds, more particularly, to a specific component,
for example, a sensor.
This term, used in the J1587 standard, has an equivalent in the J1939 standard
(SPN).
PPID corresponds to PID, but is only used by VOLVO.
This represents the type of fault that has occurred. This may be an electrical,
mechanical or equipment fault. VOLVO uses a SID-FMI or PID-FMI or
PPID-FMI combination.
This represents the type of fault that has occurred. This may be an electrical,
mechanical or equipment fault.
This represents the system or component at fault, for example: SPN 100,
indicates an oil pressure problem or a problem with the oil pressure sensor.
This represents the type of fault that has occurred. This may be an electrical,
mechanical or equipment fault.
The MDEC general system faults are indicated on the equipment in the
following way: fault code numbers (generated by the ECU - Engine control
unit).
33502019901_0_1
39/88
In the event of a fault, the screen will display the following message:
FAULT
ALARM
ENGINE GENERAL 110 18
25/12/2005 15:30
OK=HELP
For JOHN DEERE (JD), PERKINS (PE) and VOLVO (VO) engines, the codes displayed are SPN and FMI codes.
4.5. Horn reset
Depending on the settings made (menu 364 - HORN), the activation of an alarm and/or a fault leads to the horn
sounding and the following screen appearing:
HORN STOP
PRESS OK
25/12/2005
This screen will display first any messages relating to the alarms
and faults that appear as soon as OK is pressed.
15:30
33502019901_0_1
40/88
5. Access levels
Different generating set parameters access levels are available with the TELYS unit (levels 0 and 1).
5.1. List of access levels
The list of access levels is as follows:
Level
Who?
A
User
access
User
access
Level
0
Level 1
Installer
access
How?
TELYS unrestricted
access
TELYS with
customer access
code
TELYS with
access code
supplied by the
agent
What?
Modification of generating set control parameters (delay
for mains return, horn usage, etc.)
User parameters protected
Modification of parameters relating to certain automatic
and safety functions of the generating set that can be
adjusted during installation.
33502019901_0_1
41/88
Level 0B
This level allows the user to protect access to the settings of level 0A.
The access code is programmed by the user and can be modified by the user. Access level 1 makes it possible to modify
the code. The code is entered in menu 361.
o
SECURE ACCESS
Enter password
* * * *
12
OK
* * * *
12
Esc
OK
Esc
33502019901_0_1
42/88
6. Exterior communication
Control of the generating set and viewing of the operating parameters can be carried out remotely, without having to
install specific software, via a computer network, a landline telephone network or a mobile telephone network.
The external communication of TELYS, is the devices integrated to the main board that make external communication
possible. Each communication mode conforms to the international standards in force.
All the communication ports can be used simultaneously.
6.1. Series communication with the RS485 port
This communication port is used for a permanent or non-permanent connection between TELYS and the following
equipment:
9 a PC type computer
9 a programmable logic controller (PLC)
9 a modem
9 all equipment fitted with an RS485 interface
The parameters of this port are as follows:
o speed: communication speed 2400, 4800, 9600, 19200, 38400 Bauds
o data: data format: 7 or 8 bits
o parity: parity check: without, even, odd,
o stop: stop bit: yes or no.
o address no.: from 1 to 255
o signal type: Rx, Tx, transmission and reception of data
o signal transmission: twisted pair armoured cable.
All these parameters can be accessed from the menu no. 31 "COMMUNICATION".
The connector is the following:
Detachable screw block type.
Non-isolated input
The base must be closed at the extremities.
Filtered and protected from EMC overvoltage.
End of line resistance configuration switch (120 ohms) positioned to one side on the main board marked R31
Maximum communication speed of the port: 38400 bauds
Port conforms to RS485 standards
Connector
no.
1
2
3
Designation
L0
L1
L2
Electrical
specifications
0 Vdc
5 Vdc
5 Vdc
Marking on male
connector
0 Vdc
A+
B-
33502019901_0_1
43/88
Additional language file: contains all the messages that may appear on the
display, translated into a language not integrated with the TELYS base
TELYS has 5 languages: French, English, Spanish, Portuguese, German. Space
is provided for an additional language depending on customer requirements
Configuration parameters
File containing all the configuration parameters (operation) relating to each
Contents
generating set
Transfer and/or recover parameters configured in the factory or with the user
Usage
during installation
Events
Contents
Usage
Software (soft)
Contents
Usage
File containing all the data necessary to facilitate the diagnosis of faults.
Contains the list of all the events that have occurred with TELYS (operator
actions, fault displays, etc.). Maximum number of events: 300.
In the event of a fault, the user of the generating set will be able to give the
repair agent a file containing all the date required to facilitate repair. The file
can be sent by email once it has been recovered from the USB key
TELYS operation software
This function is used to transfer, to save and to update software saved on the
main board and all the boards containing associated software.
33502019901_0_1
44/88
33502019901_0_1
45/88
USB
5/6
Download Events
Download Configuration
Download Languages
Download Software
12
OK
Esc
Download Configuration
Download Languages
Download Software
Download All
12
OK
Esc
File Transfer
Completed
Esc
9 to transfer the following information from a USB key to TELYS (operation known as "copying"):
o configuration parameters
o software version
o additional language
o all data.
USB to TELYS transfer screens
The transfer screens are displayed following connection of the USB key and software recognition.
They only appear if the screen is on the homepage (not within a menu). The transfer screens
are displayed only a few seconds after the USB key is inserted.
Data transfer with a USB key (USB Host port) requires that TELYS be powered on.
The transfer of "configuration parameters" and "all data" files from the key to TELYS can only be
made with the generating set stopped. The files to be transferred to TELYS must be located at the
"root" of the key and not in a sub-folder.
USB
6/6
Download Languages
Download Software
Download All
Upload Configuration
12
OK
Esc
Example of screen
Note: once loading is complete, TELYS will reinitialise itself.
33502019901_0_1
46/88
24/08/2005
13:12
33502019901_0_1
47/88
s Press START:
AVAILABLE POWER
AIR PREHEATING
START-UP
IN PROGRESS
100.0%
10 seconds
24/08/2005
13:12
24/08/2005
13:12
24/08/2005
13:12
AVAILABLE POWER
100.0%
13:12
33502019901_0_1
48/88
AVAILABLE POWER
100.0%
13:12
1 ACTIONS
1/5
11 MANU <> AUTO
12 CONTROL LOAD
13 TEST GENERATING SET
14 PROGRAMS
15 TEST LAMPS
12
OK
Esc
12 CONTROL LOAD
12
OK
Esc
After the circuit breaker is closed, the following display appears (the generating set is supplying the application):
OFF
IN PROGRESS
24/08/2005
13:12
q Switch TELYS off by turning the key to "OFF" (without forcing it to the "OFF" position).
33502019901_0_1
49/88
Danger
24/08/2005
13:12
33502019901_0_1
13:12
50/88
t Following activation of the remote order (or following a programme), the following sequence occurs
WARNING
AIR PREHEATING
START-UP
IN PROGRESS
AUTOMATIC Start
6 seconds
22/03/2006
4 seconds
02:02
22/03/2006
02:04
22/03/2006
02:05
24/08/2005
13:12
33502019901_0_1
51/88
AVAILABLE POWER
100.0%
13:12
AUTOMATIC STOP
IN PROGRESS
AUTOMATIC STOP
IN PROGRESS
LOAD SUPPRESSION
52 seconds
22/03/2006
02:05
COOLING DOWN
1 min 37 sec
22/03/2006
02:06
OFF
IN PROGRESS
22/03/2006
02:05
02:07
33502019901_0_1
52/88
8. Fault finding
Problem
Probable causes
No LED displays and no Faulty module supply fuse
screen display
Faulty battery
Remedial action
Check and replace the fuse
Check and replace the battery if necessary
9. Maintenance
9.1. Replacing the fuse
n
Use a suitable screwdriver or your hand to turn the cap anti-clockwise until it can be removed.
o
Remove and replace the fuse (use a fuse of the same size and rating).
p
Refit the cap in the reverse order to removal.
33502019901_0_1
53/88
10. Appendix
28
3
4
29
3
4
14
84
2
31
91
91
91
3
4
7
8
9
10
13
14
Perkins
Volvo
10.1.
DESCRIPTION
Throttle #3 Position
Throttle Voltage high, short to V+
Throttle Voltage low, short to VThrottle #2 Position
Throttle Voltage high, short to V+
Throttle Voltage low, short to VThrottle Voltage out of range
Vehicle speed
Vehicle invalid or missing
Vehicle speed mismatch
Accelerator pedal position
Throttle Voltage high, short to V+
Throttle Voltage low, short to VThrottle calibration invalid
PWM throttle abnormal pulse width
Throttle invalid (CAN value)
Throttle voltage out of range low
Throttle calibration aborted
Throttle voltage out of range
33502019901_0_1
COMMENTARY
Short to V+
Short to VShort to V+
Short to V-
54/88
94
94
1
3
4
5
10
13
16
17
18
97
97
0
3
4
16
31
98
98
1
3
4
5
100
100
100
1
3
4
5
17
18
Perkins
Volvo
John
Deere
DESCRIPTION
Fuel rail pressure sensor
Fuel supply pressure extremely low
Fuel rail pressure input voltage high
Fuel rail pressure input voltage low
Fuel rail pressure sensor open circuit
Fuel rail pressure lost detected
Fuel rail pressure higher than expected
Fuel supply pressure moderately high
Fuel rail pressure not developped
Fuel supply pressure moderately low
Water in fuel sensor
Water in fuel continuously detected
Water in fuel input voltage high
Water in fuel input voltage low
Water in fuel detected
Water in fuel detected
Oil level sensor
Oil level value below normal
Oil level sensor input voltage high
Oil level sensor input voltage low
Oil level sensor open circuit
Oil pressure sensor
Engine oil pressure extremely low
Oil pressure sensor input voltage high
Oil pressure sensor input voltage low
Oil pressure sensor open circuit
Engine oil pressure low
Engine oil pressure moderately low
33502019901_0_1
COMMENTARY
Short to V+
Short to V-
Short to V+
Short to V-
Short to V+
Short to V-
Short to V+
Short to V-
55/88
102
273
102
0
1
3
4
15
16
105
105
0
3
4
5
16
106
106
0
3
5
107
107
0
3
4
5
31
108
274
108
3
4
17
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
56/88
110
110
110
0
3
4
5
15
16
31
111
111
0
1
3
4
153
153
0
3
5
158
158
1
17
160
2
168
168
172
172
2
172
3
4
5
15
16
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
57/88
174
174
0
3
4
15
16
31
175
175
0
3
4
5
177
9
189
0
31
190
190
190
0
2
9
11
12
15
16
228
261
252
252
13
11
Perkins
Volvo
John
Deere
DESCRIPTION
Fuel temperature sensor
Fuel temperature high most severe
Fuel temperature sensor input voltage high
Fuel temperature sensor input voltage low
Fuel temperature high
Fuel temperature high moderately high
Fuel temperature sensor faulty
Oil temperature sensor
Oil temperature extremely high
Oil temperature sensor input voltage high
Oil temperature sensor input voltage low
Oil temperature sensor open circuit
Transmission oil temperature sensor
Transmission oil temperature invalid
Rated engine speed
Engine speed derated
Engine speed derated
Engine speed sensor
Overspeed extreme
Engine speed sensor data intermittent
Engine speed sensor abnormal update
Engine speed sensor signal lost
Engine speed sensor signal lost
Overspeed
Overspeed moderate
Speed sensor calibration
Engine timing abnormal calibration
Software
Incorrect engine software
33502019901_0_1
COMMENTARY
58/88
234
253
2
281
281
3
4
5
282
282
3
4
285
285
3
4
286
286
3
4
5
323
323
3
4
5
324
324
3
4
5
443
443
3
4
523
9
Perkins
Volvo
John
Deere
DESCRIPTION
Check system parameters
Incorrect parameters
Action alert output status
Action alert output open/short to B+
Action alert output short to ground
Action alert output open circuit
Overspeed output status
Overspeed output open/short to B+
Overspeed output short to ground
Coolant temperature output status
Coolant temperature lamp open/short to B+
Coolant temperature lamp short to ground
Oil pressure output status
Oil pressure output open/short to B+
Oil pressure output short to ground
Oil pressure output open circuit
Shutdown output status
Shutdown output open/short to B+
Shutdown output short to ground
Shutdown output open circuit
Warning output status
Warning output open/short to B+
Warning output short to ground
Warning output open circuit
ENGINE RUN output status
Engine run output open/short to B+
Engine run output short to BGear selection
Gear selection invalid
33502019901_0_1
COMMENTARY
59/88
608
611
250
3
4
620
262 232
3
4
626
44
3
4
5
627
1
4
628
629
240
254
2
8
11
12
13
19
630
632
253
2
5
Perkins
Volvo
John
Deere
DESCRIPTION
Data link faulty J1587
Injector wiring status
injector wiring shorted to power source
injector wiring shorted to ground
5 Volt sensor power supply
Sensor power supply open/short to B+
Sensor power supply short to ground
Start enable device (intake heater and ether)
Start enable device output short to B+
Start enable device output short to ground
Start enable device output open circuit
Power supply
Injector supply voltage problem
ECU unswitched power missing
Memory fault in EMS2
ECU status
RAM cell test failure
CPU watchdog reset test failure
Main and fuelling ASIC test fail
RAM adress test failure
Watchdog trip failure
ECU to injection pump communication error
Data set memory EEPROM
Injection status
Fuel shutoff error
Fuel shutoff non-functional
33502019901_0_1
COMMENTARY
60/88
636
21
2
3
8
9
10
637
22
2
3
7
8
9
10
639
247 231
2
9
11
12
13
640
11
31
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
61/88
651
651
2
3
4
5
6
7
11
652
652
2
3
4
5
6
7
11
653
653
2
3
4
5
6
7
11
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
Cylinder #1 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
Cylinder #1 unknown error/mechanical failure
Cylinder #2 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
Cylinder #1 unknown error/mechanical failure
Cylinder #3 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
Cylinder #1 unknown error/mechanical failure
33502019901_0_1
62/88
654
654
2
3
4
5
6
7
11
655
655
2
3
4
5
6
7
11
656
656
2
3
4
5
6
7
11
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
Cylinder #4 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
Cylinder #1 unknown error/mechanical failure
Cylinder #5 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
Cylinder #1 unknown error/mechanical failure
Cylinder #6 status
Short circuit high side to B+
Short circuit high side to low side or low side to
B+
Short circuit high or low side to ground
Cylinder #1 circuit open
Cylinder #1 circuit shorted
Cylinder #1 balancing error/mechanical failure
33502019901_0_1
63/88
676
3
5
677
3
3
4
5
678
41
3
4
723
342
2
11
12
729
3
5
810
2
861
861
3
4
898
9
970
2
31
971
31
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
64/88
1069
2
9
31
1076
0
1
2
3
5
6
7
10
13
1077
7
11
12
19
31
1078
7
11
31
1079
3
4
Perkins
Volvo
John
Deere
DESCRIPTION
Tire size status
Tire size error
Tire size invalid
Tire size error
Fuel Injection pump status
Pump control valve closure too long
Pump control valve closure too short
Pump detected defect
Pump solenoid current high
Pump solenoid circuit open
Pump solenoid circuit severely shorted
Pump control valve closure not detected
Pump solenoid circuit moderately shorted
Pump current decay time invalid
Fuel injection pump controller status
Attempting to fuel without command
Pump supply voltage out of range
Pump self test error
Pump detected communication error
Pump initiated engine protection
ECU/Pump timing status
ECU/Pump timing moderately out of
synchronisation
ECU/Pump timing speed out of synchronisation
ECU/Pump timing extremely out of
synchronisation
Sensor supply voltage (+5 Volt)
Sensor supply voltage high
Sensor supply voltage low
33502019901_0_1
COMMENTARY
65/88
1080
3
4
1109
31
1110
31
1111 268
2
1266 1266
3
4
1347
3
5
7
10
1348
5
10
1485
1485
2
3
1568
2
4
9
1569
31
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
66/88
1639
1
2
16
18
1690 1690
2000
6
13
Perkins
Volvo
John
Deere
DESCRIPTION
COMMENTARY
33502019901_0_1
67/88
Meaning/Cause
Measures
023
Coolant level too low
024
030
033
044
045
051
052
065
066
067
068
069
Engine documentation
Engine documentation
Engine documentation
Engine documentation
Engine documentation
Engine documentation
Check coolant level in expansion
tank
Engine documentation
Check coolant level in expansion
tank
Engine documentation
Restart the engine, eliminate
cause of overspeeding
Check filter
Engine documentation
Check coolant level Engine
documentation
Check coolant level Engine
documentation
Engine documentation
Engine documentation
Check low pressure fuel side
Engine documentation
Check low pressure fuel side
Engine documentation
Engine documentation
Engine documentation
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
33502019901_0_1
2000
4000
68/88
No.
Meaning/Cause
070
071
072
073
074
075
076
077
078
079
080
081
082
083
089
Measures
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
The measured value is read in via
the CAN. The alarm is handled in
MDEC.
High pressure system leaking, air
in the system
Engine documentation
Interface transformer malfunction
or interface transformer wiring
B48
Engine documentation
Interface transformer faulty or
leakage in the high pressure
system
Engine
Documentation
Message also appears when very
large generators are in use and the
rundown time exceeds 20 s
Fault irrelevant
2000
4000
33502019901_0_1
69/88
No.
090
091
092
093
094
095
099
100
101
102
103
104
105
106
107
118
119
120
121
Meaning/Cause
Measures
2000
4000
Electronics service
Electronics service
Electronics service
Electronics service
Electronics service
Electronics service
Electronics service
Electronics service
Check battery / generator
33502019901_0_1
70/88
No.
122
134
136
Meaning/Cause
Measures
137
139
140
142
144
145
147
149
151
170
33502019901_0_1
2000
4000
71/88
No.
171
173
Meaning/Cause
Measures
186
187
188
189
180
181
182
183
184
185
205
208
2000
4000
Electronics service
Electronics service
33502019901_0_1
72/88
No.
Meaning/Cause
Measures
211
215
216
Sensor defect (coolant level)
220
223
229
230
Sensor defect (camshaft speed)
231
Sensor defect (fuel pressure)
240
245
246
250
33502019901_0_1
2000
4000
73/88
No.
266
267
Meaning/Cause
Sensor defect (analog speed setting)
speed is set to a fault value or
remains set to the actual speed
(adjustable, MP180.14)
Used in test stand mode only:
Sensor defect (analog speed setting)
speed is set to a fault value or
remains set to the actual speed
(adjustable, MP180.14)
Sensor defect frequency setting
270
271
272
273
274
275
276
277
278
301
302
303
304
305
306
Measures
Short-circuit or wire breakage,
check set speed transmitter and
wiring
Electronics service
Short-circuit or wire breakage,
check set speed transmitter and
wiring
Electronics service
Short-circuit or wire breakage,
check set speed transmitter and
wiring
Electronicsservice
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Electronics service (external
device faulty)
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
33502019901_0_1
2000
4000
74/88
No.
307
308
309
310
311
312
313
314
315
316
317
318
319
Meaning/Cause
Cylinder A7 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder A8 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder A9 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder A10 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B1 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B2 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B3 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B4 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B5 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B6 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B7 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B8 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cylinder B9 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Measures
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
Replace solenoid valve if this
occurs frequently
Engine documentation
33502019901_0_1
2000
4000
75/88
No.
320
Meaning/Cause
Cylinder B10 :
- FPGA fault status = 2
- Time-of-flight t < 600 s
- Time-of-flight t > 1400 s
Cabling fault cylinder A1
misfiring
321
Measures
Replace solenoid valve if this
occurs frequently
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
33502019901_0_1
2000
4000
76/88
No.
Meaning/Cause
Cabling fault cylinder A8
misfiring
328
Measures
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
33502019901_0_1
2000
4000
77/88
No.
Meaning/Cause
Cabling fault cylinder B5
misfiring
335
Measures
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
33502019901_0_1
2000
4000
78/88
No.
Meaning/Cause
Fault (interruption) in cabling of
cylinder A2 misfiring
342
Measures
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
SV short-circuit or +SV line
shorted to electronic ground
(Requirement : Engine block
grounded)
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
33502019901_0_1
2000
4000
79/88
No.
Meaning/Cause
Fault (interruption) in cabling of
cylinder B1 misfiring
351
Fault (interruption) in cabling of
cylinder B2 misfiring
352
Fault (interruption) in cabling of
cylinder B3 misfiring
353
Fault (interruption) in cabling of
cylinder B4 misfiring
354
Fault (interruption) in cabling of
cylinder B5 misfiring
355
Fault (interruption) in cabling of
cylinder B6 misfiring
356
Fault (interruption) in cabling of
cylinder B7 misfiring
357
Fault (interruption) in cabling of
cylinder B8 misfiring
358
Fault (interruption) in cabling of
cylinder B9 misfiring
359
Fault (interruption) in cabling of
cylinder B10 misfiring
360
361
Measures
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
Check cabling and solenoid valve
for interruption
Replace solenoid valve or cable
harness
Engine documentation
PA circuit faulty or free-wheeling
transistor short-circuit Replace
Engine Control Unit
ECU
33502019901_0_1
2000
4000
80/88
No.
362
Meaning/Cause
Measures
363
TAA2 faulty
382
TAA3 faulty
383
TAA4 faulty
384
33502019901_0_1
2000
4000
81/88
No.
Meaning/Cause
Measures
TAA5 faulty
385
TAA6 faulty
386
E02
399
E12
E13
E14
E22
E23
E24
E25
E28
E29
4000
E11
Temperature sensor in PIM A 521
faulty
Power supply (+5VDC) of PIM
A521 out of range (>5.25V)
Power measurement of PIM A
521 faulty
PIM A 521 communication via
CAN1 bus (default) faulty
PIM A 521 communication via
CAN2 bus (redundant) faulty
Electronics temperature of PIM A
522 too high (>95C)
Temperature sensor in PIM A 522
faulty
Power supply (+5VDC) of PIM A
522 out of range (>5.25 V)
Current measurement of PIM A
522 faulty
PIM A 522 communication via
CAN1 bus (default) faulty
PIM A 522 communication via
CAN2 bus (redundant) faulty
During self-test, BOB 1 was not
detected in slot 3 of PIM A 522 (e.g.
no or wrong printed circuit board
inserted or BOB 1 faulty)
During self-test, BOB 1 was not
detected in slot 4 of PIM A 522 (e.g.
no or wrong printed circuit board
inserted or BOB 1 faulty)
2000
33502019901_0_1
82/88
No.
E33
E34
E35
E36
E38
E55
E56
E57
E58
E60
E63
E66
E67
E68
E69
E71
Meaning/Cause
Measures
33502019901_0_1
2000
4000
83/88
No.
E77
E78
E79
E80
E82
E83
E84
E88
E89
E90
E91
E93
E99
F00
F01
Meaning/Cause
Measures
33502019901_0_1
2000
4000
84/88
No.
F02
F04
F05
F06
J30
J31
Meaning/Cause
Measures
33502019901_0_1
2000
4000
85/88
10.3.
Parameter type
Parameter
Meaning
Air preheating delay
Duration of air preheating before starting for a Diesel engine
Micro disconnection
Delay between remote order and start-up of the generating set
delay
Mains return delay
Delay between cooling of the generating set and the remote order
Delay between appearance of EJP warning and start-up of the
EJP warning delay generating set
Note: if the generating set is fitted with a motorised circuit
(France only)
breaker, it will close when the delay has expired
The EJP top signal sometimes undergoes transitional status
EJP top loss time fluctuations. To dampen this phenomena, this delay prevents
(France only)
repeated switching of the normal/safety inverter.
EJP top loss acknowledgement delay
Standby delay
Delay before TELYS switches to standby
General time delays
Time period for which the generating set cooling continues to
Cooling delay
operate after the set has been operating in automatic mode (after
output is started)
Coolant temperature Time for which the generating set is cooled following detection of
stop delay
a coolant temperature fault
Time for which the generating set is cooled following detection of
Stop
delay
I>>
an overload or short circuit fault.
(overload or short
If the setting is equal to 0, the generating set will stop
circuit)
immediately.
Delay before min/max voltage and min/max frequency faults are
recognised.
U&F
stabilisation
This delay begins from the starter cut-off threshold. Once the
delay
delay has expired, the normal/safety inverter will operate if the
frequency and voltage are outside of the permitted values.
Activation time of the horn for Faults and Alarms and interval
Horn delay
between two horn activations
Horn
Fault
Activation or not of the horn for a fault
Auto Start
Horn activated following Automatic start
Min & fault alarm
Time before alternator min voltage fault is declared
delay
Max & fault alarm
Time before alternator max voltage fault is declared
delay
Threshold for nominal voltage set in the Factory when the min
Min. alarm threshold
alternator voltage alarm is activated
Alternator voltage
Threshold for nominal voltage set in the Factory when the min
Min. fault threshold
alternator voltage fault is activated
Threshold for nominal voltage set in the Factory when the max
Max. alarm threshold
alternator voltage alarm is activated
Threshold for nominal voltage set in the Factory when the max
Max. fault threshold
alternator voltage fault is activated
33502019901_0_1
86/88
Parameter type
Alternator
Frequency
Battery voltage
Overload
Fuel pump
Parameter
Meaning
Min & fault alarm
Time before alternator min frequency fault is declared
delay
Max & fault alarm
Time before alternator max frequency fault is declared
delay
Threshold for nominal frequency set in the Factory when the min
Min. alarm threshold
alternator frequency alarm is activated
Threshold for nominal frequency set in the Factory when the min
Min. fault threshold
alternator frequency fault is activated
Threshold for nominal frequency set in the Factory when the max
Max. alarm threshold
alternator frequency alarm is activated
Threshold for nominal frequency set in the Factory when the max
Max. fault threshold
alternator frequency fault is activated
Min & fault alarm
Time before battery min voltage fault is declared
delay
Max & fault alarm
Time before battery max voltage fault is declared
delay
Threshold for Vcc supply voltage when the min battery voltage
Min. alarm threshold
alarm is activated
Min. fault threshold
Threshold for Vcc supply voltage for the min battery voltage fault
Threshold for Vcc supply voltage when the max battery voltage
Max. alarm threshold
alarm is activated
Max. fault threshold
Threshold for Vcc supply voltage for the max battery voltage fault
Overload alarm
Threshold for the factory setting for nominal current
Activation threshold
Fuel level indicator threshold to activate the Fuel pump control
Deactivation threshold Fuel level indicator threshold to deactivate the Fuel pump control
33502019901_0_1
87/88
10.4.
Enclosure D - Glossary
Title
Meaning
Equipment that requires only to be connected for it to be immediately recognised
and made operational
Data transfer speed
Data unit with the value of 0 or 1
Supplementary bit added to the positioned character used to detect transmission
errors
Bit indicating the end of a character
Any number, letter, punctuation mark etc., that is part of a message
Business sized local network
File Transfer Protocol: transfer protocol for files. The transfer is made between two
separate addresses on the Internet.
Universal Serial BUS: universal communication BUS
Local Area Network: groups together networks adapted to the size of an industrial
site and which the furthest points are separated by a distance not exceeding a few
kilometres. These are sometimes known as local business networks.
Simple Mail Transfer Protocol: electronic messaging application
TCP (Transmission Control Protocol): data transmission protocol
IP (Internet Protocol): Internet interconnection protocol
Computer identifier (of the generating set)
Name given to each network connected to the Internet
Equipment that enables switching from one computer network to another
Dynamic Host Configuration Protocol: automatic configuration application enabling
a computer unit (TELYS) to be attributed with an IP address if DHCP is configured
to "YES"
Assembly of electrical conductors fitted in parallel and allowing data transfer
This communication mode uses the ModBus RTU standard protocol. The main
functions of this protocol are commonly referred to as JBUS
Device that automatically repeats signals it receives and passes them on from one
unit to another
Connection mode only involving 2 parties
33502019901_0_1