LOAD CALCULATION

FOR DEADLOAD:
A. BEAMS WITH WALL LOADS
Concrete Masonry Units:
Concrete Masonry Units
-200 mm thick wall

3.97 kPa

Plaster

0.48 kPa

Water Proofing Membranes


Liquid Applied

0.05 kPa

Total

4.50 kPa

B. BEAMS WITH ROOF LOADS


Acoustical Fiber Board

0.05 kPa

C. BEAMS WITH FLOOR LOADS and CEILING


Slab (24 kN/m3 * 0.11m)

2.64 kPa

Acoustical Fiber Board

0.05 kPa

Finishes

1.53 kPa

Total

4.22 kPa

D. BEAMS WITH FLOOR LOADS W/O CEILING


Slab (24 kN/m3 * 0.11 m)

2.64 kPa

Finishes

1.53 kPa

Total

4.17 kPa

OTHER LOADS
Fixtures

0.10 kPa

Windows, glass, frame and sash

0.38 kPa

LOAD CALCULATION
FOR LIVELOAD:

Dining Room and Restaurant

4.80 kPa

Offices

2.40 kPa

Lobbies and ground floor corridors

4.80 kPa

Retail Store

4.80 kPa

Storage (light)

6.00 kPa

Event Hall
Movable seats

4.80 kPa

Ceiling Framing except


over stage

0.50 kN

Fire Sprinkler
Structural Support

1.10 kN

Flat or rise less than 4 units vertical


in 12 units horizontal (33.33 % slope).
Arch and dome w/ rise less than one
eight of span

1.00 kPa

LOAD CALCULATION
FOR WIND LOAD

Wind Speed (V = 200 kph)


(Reference: Section 207.5.4, Table 207.1 Wind Zone for Different Provinces in
the Philippines; NSCP 2010)
Importance Factor (Iw = 1.15)
For Essential
(Reference: Section 207.5.5, Table 201.3, Importance Factor; NSCP 2010)
Topographic Factor (Kzt = 1.0)
(Reference: Section 207.5.7; NSCP 2010)
Solving for Ps9
(Reference: Figure 207.2; NSCP 2010)
Interpolating Values:
1211.7
1211

1.09x
1.091.05

x = 1.078 = Ps9
Ps= K zt I w P s 9

Ps= (1.078 )( 1 ) ( 1.15 ) (0.55)

Ps=0.681835 kPa

Ground Floor
w=0.681835 Kpa(2.1 m)
w=1.4319 kN /m

Second Floor
w=0.681835 Kpa(3.05 m)
w=2.0795 kN /m

Third Floor
w=0.681835 Kpa (3.10 m)
w=2.1137 kN /m

Roof Deck
w=0.681835 Kpa (3.45 m)
w=2.3523 kN /m

LOAD CALCULATION
FOR SEISMIC LOAD
Use: 20 kN per Joint as Seismic load