Professional Documents
Culture Documents
Synchronousgenerator
Asynchronousgenerator
PVinverter(andotherconverterswithlowpowerrating)
NordicWorkshoponPowerSystemProtectionandControl
TrondheimNorwayMay25,2016
TorIngeReigstad,SINTEFEnergi
Technologyforabettersociety
Synchronousgeneratorshortcircuitcurrentcontribution
Peakaccomponent:~6timesrated
Maxdccomponent:sameaspeakac
Goestosteadystatevalue,dependingonsynchronousreactanceandAVR
[R.Roeper"Kurzschlusstrme inDrehstromnetzen",Siemens
Schuckertwerke AG,1964]
Technologyforabettersociety
Synchronousgeneratorshortcircuitcurrentcontribution
Technologyforabettersociety
Synchronousgeneratorshortcircuitcurrentcontribution
Reactance
Description
Symbol
Range per-unit
Period
Sub-transient
reactance
Determines maximum
instantaneous current and
current at time Molded Case
Circuit Breaker usually open
Xd
0.09 0.17
0 6 Cycles
Transient
Reactance
Xd
0.13 0.20
6 cycles to 5
sec.
Synchronous
reactance
Xd
1.7 3.3
After 5 sec.
Zero sequence
reactance
Negative
sequence
reactance
X0
0.06 0.09
X2
0.10 0.22
Technologyforabettersociety
Asynchronousgeneratorshortcircuitcurrentcontribution
peakaccomponent:~6timesrated
maxdccomponent:sameaspeakac
decaystozero(noAVR)
2
ipos
1.8
Current [kA]
ineg
1.6
idc
1.4
i(t)
1.2
1
0.8
0.6
0.4
0.2
0
1.05
1.1
1.15
1.2
Time [s]
1.25
1.3
1.35
Technologyforabettersociety
PVinvertershortcircuitcurrentcontribution
APVinverter'scurrentcontributionduringafaultis
notzero
variesbydesign
Theoutputcurrentislimitedbythecurrentcarryingcapabilityofthepower
electronicswitches.
Model1
Genericmodel
Technologyforabettersociety
PVinverter:Model1
Model1:
Fastdisconnection(lessthanonecycle).
IfthePCCvoltagedropsbelow50%,theinvertercurrentisimmediatelyinterrupted.
Technologyforabettersociety
PVinverter:Model1
Technologyforabettersociety
PVinverter:GenericModel
GenericModel:
Operatefor4to10cyclesafterafaultincidentevenifthePCCvoltagedropsbelow50%.
Thecurrentisusuallybetween100%and120%oftheratedpoweroftheinverter.
ThecurrentcontributionlevelisafunctionofthevoltageattheterminalofthePVinverter
(PCC)duringafaultandtherebythetypeandlocationofthefault.
Technologyforabettersociety
PVinverter:GenericModel
Technologyforabettersociety
10
PVinvertershortcircuitcurrentcontribution
ThePVinvertersarefoundtodetectthefaultintwodifferentways:
Angleoffaultcurrents
Internalundervoltageprotection
Currentandvoltageunbalance
ThePVinverterfaultcurrent: inphasewiththevoltagemeasuredonitsterminalsbefore
thefaultoccurred.
Thesystemfaultcurrent:phaseshiftofapproximately8090degreeswithrespecttothe
systemsourcevoltage,dependingontheX/Rratio.
=>vectorsummationresultsinsmallervaluescomparedtoanarithmeticsummation.
FrequencyofPVinverterfaultcurrent:
Toolowvoltageattheterminaltodeterminefrequencyandphaseangle
=>thePLLoftheinverterwillsuddenlychangethefrequencyfrom+1Hzto+10Hz.
=>thevectorofthePVinvertercurrentwillrotatewithrespecttothesystemfaultcurrent.
Technologyforabettersociety
11
IEC60909:2016 Shortcircuitcontributionfromfullsize
converters
IEC609090:2016Shortcircuitcurrentsinthreephasea.c.systems Part0:Calculationof
currents
New:shortcircuitcontributionfrompowerstationunitswithfullsizeconverters(forinstancePV)
andfromwindpowerstationunitswithdoublyfedinductiongeneratorandfullconverters.
Fullsizeconvertershortcircuitcurrentcontribution
Modelledinpositivesequencesystembyacurrentsource
datashouldbeprovidedbythemanufacturerforthedifferenttypesofshortcircuits
theshortcircuitcurrentcontributionfromtheequivalentvoltagesourcesarecalculatedasearlier,
however,thecurrentcontributionsfromthefullsizeconvertsareaddedtothisvalue
Iftheshortcircuitcontributionsfromtheconvertersarenothigherthan5%oftheinitialshort
circuitwithoutthesepowerstationunits,theircontributionmaybeneglected.
PowerstationunitswithfullconverterareneglectedwhencalculatingtheDCcomponentofthe
shortcircuitcurrent.
Thepeakcurrentoftheconvertercontributionissquarerootof2timestherms value.
IEC60909doesnotconsiderthedynamicresponseandfrequencychangesofconverter
simulationsinthetimeframeisneededinordertoachieveamoreaccuratecurrentcontributionfrom
converters.
Technologyforabettersociety
12